IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

The GE Fanuc IC693CPU360 and IC693CPU364 share the same Series 90-30 CPU class, but they are not drop-in equivalents for every rack. The CPU364 adds an embedded Ethernet interface and draws more current from the +5 VDC backplane supply.

Start with the power budget

The IC693CPU360 draws 670 mA from the +5 VDC supply. The IC693CPU364 draws 1.51 A. That 840 mA difference matters in racks with high I/O loading or an older 30 W power supply.

Before a CPU364 replacement, total the +5 VDC demand for the CPU and every installed module. Compare the result with the selected Series 90-30 power supply rating. Do not assume that available physical slots mean available power.

Ethernet is the main functional difference

The CPU360 has one built-in serial port. It supports SNP and SNP-X slave protocols through the connector on the PLC power supply. Ethernet requires a separate communications module.

The CPU364 adds an internal Ethernet interface. It supports direct 10BASE-T cabling or AAUI through an external transceiver. The serial port remains available.

This changes the replacement scope. A CPU360 rack using an external Ethernet module may need revised cabling, IP addressing, and rack documentation if Ethernet moves to the CPU364.

Shared controller limits

Item IC693CPU360 IC693CPU364
Processor 80386EX, 25 MHz 80386EX, 25 MHz
User memory Up to 240 KB with firmware release 9.0 or later 240 KB
Typical Boolean scan 0.22 ms per 1K contacts 0.22 ms per 1K contacts
Discrete inputs / outputs 2,048 / 2,048 2,048 / 2,048
Baseplates Up to eight Up to eight
+5 VDC load 670 mA 1.51 A
Embedded Ethernet No 10BASE-T or AAUI
GE Fanuc IC693CPU360 Series 90-30 CPU module

Replacement checks

  1. Record the current CPU firmware and program-memory allocation.
  2. Export the PLC project before removing the installed CPU.
  3. Calculate the +5 VDC rack load with the proposed CPU.
  4. Record serial settings and any Ethernet module configuration.
  5. Confirm the target IP address, subnet, and network path.
  6. Check the rack count and expansion or remote-baseplate arrangement.
  7. Test I/O, communications, clock-dependent logic, and fault handling after the change.

See the current product records for the IC693CPU360 and IC693CPU364.

Source basis