{"product_id":"hima-f3236-16-channel-digital-input-module","title":"HIMA F 3236 HIQuad X 16-Channel Digital Input Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eF 3236\u003c\/strong\u003e (also designated as \u003cstrong\u003eF3236\u003c\/strong\u003e) is a safety-related 16-channel digital input module engineered for integration within the \u003cstrong\u003eHIQuad X\u003c\/strong\u003e programmable electronic system. This hardware device acts as a safe separation component for processing binary data from field instrumentation sensors or mechanical contacts into the central system logic. The module automatically executes self-testing subroutines during operation, performing cross-talking checks with a walking-zero test sequence and inspecting internal filter capacitor health to maintain predictable safety parameters. To ensure direct signal routing to marshalling cabinets or field accessories, the assembly utilizes custom-matched \u003cstrong\u003eHIQuad X\u003c\/strong\u003e system cables with dedicated front cable plug connections.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eProvides 16 safety-related digital input processing channels\u003c\/li\u003e\n\u003cli\u003eAutomated full operational self-testing covering walking-zero input cross-talking parameters\u003c\/li\u003e\n\u003cli\u003eContinuous hardware diagnostic monitoring of onboard filter capacitor functionality\u003c\/li\u003e\n\u003cli\u003eSafe separation architecture certified for safety-critical plant application deployment\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSafety-related automation input signal monitoring\u003c\/li\u003e\n\u003cli\u003eHigh-integrity plant discrete loop processing\u003c\/li\u003e\n\u003cli\u003eEmergency shutdown and safety isolation sensor setups\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003ePart Type Designation\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eAlternative Designation\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eCompatible System Cable\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eF 3236\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eF3236\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eZ 7116\/3236\/..\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ch4\u003eInput Parameters\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eValue\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1-signal, 6 mA (including cable plug) or mechanical contact 24 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSwitching Time\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003etyp. 8 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch4\u003eOperating Power Requirements\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eValue\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e5 V DC Supply Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e120 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e24 V DC Supply Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e200 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch4\u003eMechanical Properties\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eValue\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eHIMA Paul Hildebrandt GmbH + Co KG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSpace Requirement\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 TE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eConnection Interface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFront cable plug connector\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eConnector Pin\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eFunction\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eColour\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003ed2\u003c\/td\u003e\n\u003ctd\u003eChannel 1 Connection\u003c\/td\u003e\n\u003ctd\u003ews\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed4\u003c\/td\u003e\n\u003ctd\u003eChannel 2 Connection\u003c\/td\u003e\n\u003ctd\u003ebr\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed6\u003c\/td\u003e\n\u003ctd\u003eChannel 3 Connection\u003c\/td\u003e\n\u003ctd\u003egn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed8\u003c\/td\u003e\n\u003ctd\u003eChannel 4 Connection\u003c\/td\u003e\n\u003ctd\u003ege\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed10\u003c\/td\u003e\n\u003ctd\u003eChannel 5 Connection\u003c\/td\u003e\n\u003ctd\u003egr\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed12\u003c\/td\u003e\n\u003ctd\u003eChannel 6 Connection\u003c\/td\u003e\n\u003ctd\u003ers\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed14\u003c\/td\u003e\n\u003ctd\u003eChannel 7 Connection\u003c\/td\u003e\n\u003ctd\u003ebl\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed16\u003c\/td\u003e\n\u003ctd\u003eChannel 8 Connection\u003c\/td\u003e\n\u003ctd\u003ert\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed18\u003c\/td\u003e\n\u003ctd\u003eChannel 9 Connection\u003c\/td\u003e\n\u003ctd\u003esw\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed20\u003c\/td\u003e\n\u003ctd\u003eChannel 10 Connection\u003c\/td\u003e\n\u003ctd\u003evio\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ed22\u003c\/td\u003e\n\u003ctd\u003eChannel 11 Connection\u003c\/td\u003e\n\u003ctd\u003ews-br\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eModule Insertion\u003c\/strong\u003e: Slide the hardware card carefully into the specified rack position along the chassis guide tracks, confirming the 4 TE space requirement constraints are met.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCable Interface\u003c\/strong\u003e: Connect the specific system cable plug matching the \u003cstrong\u003eZ 7116\/3236\/..\u003c\/strong\u003e standard directly to the front faceplate interface receptacle.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSignal Line Management\u003c\/strong\u003e: Group and route the multi-core input lines cleanly toward marshalling cabinets to avoid ambient electromagnetic coupling.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eCE Mark\u003c\/li\u003e\n\u003cli\u003eRequirement Class AK 1 to 6\u003c\/li\u003e\n\u003cli\u003eDNV Type Approval (Certificate No. TAA000032E)\u003c\/li\u003e\n\u003cli\u003eEnvironmental Categories: Temperature: B (from 0 Celsius), Humidity: B, Vibration: A, EMC: B\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"HIMA","offers":[{"title":"Default Title","offer_id":52695396581739,"sku":"F3236","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/hima-f3236-16-channel-digital-input-module-gjaelownecn_eac622d9-a125-4818-8fea-fb24b53b1676.jpg?v=1766133418","url":"https:\/\/www.plcprotech.com\/de\/products\/hima-f3236-16-channel-digital-input-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}