{"product_id":"abb-npct-01c-64009486-pulse-counter-timer-unit","title":"ABB NPCT-01C 64009486 Pulse Counter \/ Timer Unit","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eABB NPCT-01C 64009486\u003c\/strong\u003e is a high-precision pulse counter and timer unit engineered for high-performance speed and position measurement within industrial environments. Operating as a critical module for the DriveBus communication interface protocol, this device integrates seamlessly with the AC 800M controller system architecture. It features dedicated processing hardware capable of executing fast, programmable, hardware-based counter functions, holding registers for event capturing, and accelerated digital output control driven directly by real-time position or time intervals. Designed specifically for high-reliability applications, it contains two advanced encoder inputs, four digital inputs, and four digital outputs to provide comprehensive synchronization and industrial input\/output monitoring capabilities.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eDual encoder inputs configured for precise technical speed and position measurement tracking.\u003c\/li\u003e\n\u003cli\u003eFour discrete digital inputs paired with four hardware-driven digital outputs for rapid process control responses.\u003c\/li\u003e\n\u003cli\u003eEdge oscillation inhibition mode (EOSC_MODE) explicitly designed to reject false pulse edge occurrences generated by slow-speed mechanical vibrations or motor shaft oscillation.\u003c\/li\u003e\n\u003cli\u003eFlexible position calculation supporting both a standard incremental mode and a synchronized absolute mode referenced to the encoder zero pulse.\u003c\/li\u003e\n\u003cli\u003eIntegrated watchdog function providing real-time diagnostic connection supervision between the main interface module and the hardware logic.\u003c\/li\u003e\n\u003cli\u003eDedicated 24-bit internal data word configuration optimized for accurate mathematical scaling and frequency calculation conversion.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSectional drive automation architectures, including rolling mill drive systems and advanced paper machine drive control systems.\u003c\/li\u003e\n\u003cli\u003ePrecise rotational frequency and tacho frequency scaling application loops.\u003c\/li\u003e\n\u003cli\u003eReal-time industrial angular displacement tracking and position synchronization.\u003c\/li\u003e\n\u003cli\u003eHigh-speed hardware-based event capturing and digital status recording.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eTechnical Value\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct ID\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e64009486\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eABB Type Designation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNPCT-01C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReplaced Product ID (OLD)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e61258507, 64014528\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNew Part \/ Pulse Counter and Timer Unit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCountry of Origin\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFinland (FI)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCustoms Tariff Number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e90329000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEncoder Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDigital Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDigital Outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInternal Data Width\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSpeed Calculation Intervals\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e250 us \/ 10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eHardware Filter Options (DI)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 us \/ 5 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWatchdog Time Out Settings\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 ms \/ 1 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Net Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.92 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGross Weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.92 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eDIN Rail Mounting:\u003c\/strong\u003e Hook the upper lip of the unit's base plate onto a standard horizontal TS 35\/7.5 DIN rail interface and snap the mechanical assembly into position before engaging the three-position locking mechanism (OPEN, SLIDE, LOCKED).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAddress Configuration:\u003c\/strong\u003e The hardware identification number assigned inside the Control Builder software tree environment must precisely match the device address index physically selected via switch S1 on the physical module body.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGrounding Connection:\u003c\/strong\u003e Utilize the integrated metallic backplate locking system to establish an effective structural ground connection path straight through to the grounded DIN rail framework.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring and Signal Shielding:\u003c\/strong\u003e Ensure appropriate cable routing isolation rules are executed for high-frequency encoder wiring lines to successfully isolate structural noise from primary power distribution paths.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":52668514337131,"sku":"NPCT-01C 64009486","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/abb-npct-01c-64009486-pulse-counter-timer-unit-5gkk5iuey22_d8753b76-dcff-47b9-80f8-a329efa17c45.jpg?v=1765532620","url":"https:\/\/www.plcprotech.com\/fa\/products\/abb-npct-01c-64009486-pulse-counter-timer-unit","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}