{"product_id":"triconex-3006-main-processor-module-processor-module-ii-enhanced","title":"Module processeur principal II amélioré Triconex 3006","description":"\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003e3006 (3006)\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eis a\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eTriconex Main Processor Module II Enhanced\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003edesigned for Triple Modular Redundant safety controllers. The\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eprocessor executes control logic in parallel with two additional processors to form a fault tolerant TMR architecture. It manages I\/O communication, performs voting operations, and supervises diagnostics across the Tricon backplane.\u003c\/p\u003e\n\u003cp\u003eThis processor module is widely deployed in emergency shutdown systems, burner management, and turbine protection platforms in oil and gas, power generation, and petrochemical plants. The module maintains deterministic scan execution while handling triplicated input tables and output voting. When one processor channel fails, the remaining channels maintain operation without process interruption, minimizing unplanned downtime and improving safety system availability.\u003c\/p\u003e\n\u003ch3\u003eHardware Architecture and Processing Core\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eTriconex 3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eMain Processor Module belongs to the Processor Module II Enhanced family. The module operates as one of three identical processors installed in the main chassis.\u003c\/p\u003e\n\u003cp\u003eKey architecture characteristics:\u003c\/p\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eTriple processor channel operation A B C\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eParallel execution of user control logic\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eDedicated I\/O processor for bus communication\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eTriplicated TriBus synchronization and voting\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eFault tolerant communication with I\/O modules\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eShared memory table for input and output voting\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eHot replacement supported in TMR configuration\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eEach\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eprocessor exchanges input tables across the TriBus. The system compares data and selects the majority value. If disagreement occurs, the faulty channel is automatically corrected. This mechanism ensures deterministic and safe execution of safety logic.\u003c\/p\u003e\n\u003cp\u003eThe module communicates with I\/O modules through the triplicated I\/O bus. The processor assembles input tables, executes control algorithms, and transmits validated output tables to output modules.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable class=\"w-fit min-w-(--thread-content-width)\"\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003cth class=\"\"\u003eParameter\u003c\/th\u003e\n\u003cth class=\"\"\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e3006\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eTriconex\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eMain Processor Module II Enhanced\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eArchitecture\u003c\/td\u003e\n\u003ctd\u003eTriple Modular Redundant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProcessor Channels\u003c\/td\u003e\n\u003ctd\u003e3 independent channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMemory\u003c\/td\u003e\n\u003ctd\u003eSRAM with battery backup\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommunication\u003c\/td\u003e\n\u003ctd\u003eTriBus and triplicated I\/O bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eTricon v9 systems\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInstallation\u003c\/td\u003e\n\u003ctd\u003eMain chassis processor slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHot Swap\u003c\/td\u003e\n\u003ctd\u003eSupported in TMR system\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHumidity\u003c\/td\u003e\n\u003ctd\u003e5 to 95 percent non condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eApprox 20 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eApprox 330 x 40 x 260 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e4 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eTechnical FAQs\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eIs the 3006 processor compatible with 8120E main chassis?\u003c\/strong\u003e\u003cbr\u003eYes. The\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eoperates with Tricon main chassis including 8110 and compatible expansion architectures.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eHow many 3006 processors are required in one system?\u003c\/strong\u003e\u003cbr\u003eThree\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003emodules form the TMR controller. Each processor handles one independent channel.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eCan the 3006 be replaced online?\u003c\/strong\u003e\u003cbr\u003eYes. The Tricon architecture supports online replacement. The remaining processors maintain control.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eWhat is the replacement for 3006 processor?\u003c\/strong\u003e\u003cbr\u003eTypical upgrade paths include 3007, 3008, or 3009 depending on firmware and system revision.\u003c\/p\u003e\n\u003chr\u003e\n\u003ch3\u003eField Installation Recommendations\u003c\/h3\u003e\n\u003cp\u003eInstall three identical\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003emodules from the same firmware revision. Mixed revisions may cause synchronization faults.\u003c\/p\u003e\n\u003cp\u003eEnsure chassis cooling airflow remains unobstructed. Processor modules generate continuous heat under full scan load.\u003c\/p\u003e\n\u003cp\u003eVerify backplane connectors before insertion. Misalignment may cause TriBus communication failure.\u003c\/p\u003e\n\u003ch3\u003eReliability and Operational Advantages\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003e3006\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eprocessor provides deterministic scan execution for SIL rated safety loops. The triplicated architecture eliminates single point processor failures.\u003c\/p\u003e\n\u003cp\u003eThe module supports online diagnostics and automatic fault isolation. This reduces maintenance time in critical plants.\u003c\/p\u003e\n\u003cp\u003eRobust industrial design allows operation in high vibration cabinets. Conformal coated boards improve resistance to corrosive atmospheres.\u003c\/p\u003e\n\u003cp\u003eBackward compatibility with earlier Tricon systems simplifies controller upgrades while preserving field wiring.\u003c\/p\u003e","brand":"Triconex","offers":[{"title":"Default Title","offer_id":53102421508459,"sku":"3006","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/3006-s0120xprvaf.png?v=1776137094","url":"https:\/\/www.plcprotech.com\/fr\/products\/triconex-3006-main-processor-module-processor-module-ii-enhanced","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}