{"product_id":"honeywell-fc-qpp-0002-cc-v1-0-safety-manager-quad-processor-module","title":"Honeywell FC-QPP-0002 CC V1.0 Safety Manager Quad Processor Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell FC-QPP-0002 CC V1.0\u003c\/strong\u003e is an enhanced-performance Quad Processor Pack designed as the core processing engine for Honeywell Safety Manager systems. Installed within the CPCHAS-0001 or CPCHAS-0002 Controller chassis, this module manages system operations by processing field input signals, executing safety logic diagrams created in graphical Functional Logic Diagrams (FLDs), and driving output interfaces. Operating as a direct, one-on-one spare replacement for the first-generation QPP-0001 in systems running Safety Manager firmware release R121 or higher, it offers complete backward compatibility and flexible deployment across non-redundant and redundant architecture models.\u003c\/p\u003e\n\u003cp\u003eEngineered to meet stringent industrial safety standards, the \u003cstrong\u003eFC-QPP-0002 CC V1.0\u003c\/strong\u003e features a dual-processor, dual-memory architecture running synchronized internal execution paths. Hardware data-comparators continuously monitor every read and write cycle between both microprocessors. If a data discrepancy occurs, the integrated watchdog triggers an immediate safety response. With internal diagnostic coverage exceeding 99%, a single \u003cstrong\u003eFC-QPP-0002 CC V1.0\u003c\/strong\u003e module can run applications up to SIL3 without operational time limitations. When deployed in a dual-processor redundant Controller chassis configuration, the two modules communicate over a dedicated high-speed link to establish a 2oo4D voting architecture.\u003c\/p\u003e\n\u003cp\u003eThis processing module incorporates an 8-digit front-panel User Interface Display for real-time operational status, system diagnostics, and IP network verification. A three-position key switch (RUN, IDLE, STOP) provides hardware-level operational control, while dedicated power, temperature, and battery line monitors continuously check module status. The \"FC-\" prefix and \"CC V1.0\" designator indicate factory conformal coating, delivering high environmental protection against airborne contaminants and atmospheric humidity in harsh control cabinet environments.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eDual Synchronous Processor Architecture:\u003c\/strong\u003e Operates two lockstep microprocessors with real-time hardware data-comparators for continuous cross-checking of read\/write operations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSIL3 Certified Safety Performance:\u003c\/strong\u003e Diagnostic coverage exceeding 99% enables single-module deployment up to SIL3 and 2oo4D voting capability in redundant Controller configurations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOn-Board High-Speed Memory:\u003c\/strong\u003e Features 2 x 2 MB system\/application Flash, 1 x 16 MB backup Flash, 2 x 256 KB battery-backed SRAM, and 2 x 512 KB dedicated SRAM for redundant processor data exchange.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAdvanced Dual-Section Watchdog:\u003c\/strong\u003e Includes a fully testable 1oo2D watchdog circuit monitoring execution loop timing, memory integrity, 5 Vdc\/24 Vdc power rails, and Emergency Shut Down (SD) inputs.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIntegrated Emergency Shut Down (SD) Input:\u003c\/strong\u003e Galvanically isolated 24 Vdc input de-energizes watchdog outputs directly during safety trips, independent of the main processors.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDiagnostic User Interface:\u003c\/strong\u003e Eight-digit front-panel LED display with navigation buttons provides live scrolling access to chassis diagnostics, IP configurations, battery voltage, and internal module temperatures.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConformal Coating:\u003c\/strong\u003e CC V1.0 specification provides protective PCB coating against corrosive atmospheric gases, humidity, and airborne dust particles.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSafety Instrumented Systems (SIS):\u003c\/strong\u003e Central logic solver execution for Emergency Shutdown (ESD), Process Safety Management, and Fire and Gas (F\u0026amp;G) monitoring loops.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCritical Burner Management Systems (BMS):\u003c\/strong\u003e High-reliability flame safety control, furnace shutdown logic, and boiler protection systems.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTurbomachinery Safety Interlocks:\u003c\/strong\u003e Over-speed protection logic, auxiliary trip coordination, and emergency shutoff control for turbines and compressors.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundant Safety Controller Upgrades:\u003c\/strong\u003e One-on-one replacement for legacy QPP-0001 modules in Safety Manager systems running firmware R121 or higher.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ch4\u003eGeneral\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExact Model Number\u003c\/td\u003e\n\u003ctd\u003eFC-QPP-0002 CC V1.0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eQuad Processor Pack (Control Processor Module)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Platform\u003c\/td\u003e\n\u003ctd\u003eSafety Manager\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eController Chassis Compatibility\u003c\/td\u003e\n\u003ctd\u003eCPCHAS-0001, CPCHAS-0002\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFirmware Requirement (QPP-0001 Replacement)\u003c\/td\u003e\n\u003ctd\u003eSafety Manager Release R121 or higher\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConformal Coating\u003c\/td\u003e\n\u003ctd\u003eYes (FC \/ CC V1.0 Series)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostic Coverage\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 99%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety Integrity Level\u003c\/td\u003e\n\u003ctd\u003eUp to SIL3 (Single Module), 2oo4D Architecture (Redundant Pair)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch4\u003eElectrical \u0026amp; Power Ratings\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e24 V Supply Voltage Range\u003c\/td\u003e\n\u003ctd\u003e24 Vdc (-15% \/ +30%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e24 V Supply Current\u003c\/td\u003e\n\u003ctd\u003eMax. 25 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5 V Supply Voltage Range\u003c\/td\u003e\n\u003ctd\u003e5 Vdc (+\/- 5%)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5 V Supply Current\u003c\/td\u003e\n\u003ctd\u003eMax. 1.2 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEmergency Shut Down (SD) Input Voltage (High)\u003c\/td\u003e\n\u003ctd\u003e15 Vdc to 32 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEmergency Shut Down (SD) Input Voltage (Low)\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 4 Vdc (Reverse polarity protected)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEmergency Shut Down (SD) Input Current\u003c\/td\u003e\n\u003ctd\u003eApprox. 8 mA at 24 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e+24 V_SD Output Supply Voltage\u003c\/td\u003e\n\u003ctd\u003e15 Vdc to 31 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e+24 V_SD Output Resistance\u003c\/td\u003e\n\u003ctd\u003eApprox. 1.1 kOhm (Short circuit proof)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWatchdog Output Current (WDout)\u003c\/td\u003e\n\u003ctd\u003e750 mA per output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch4\u003eMemory \u0026amp; Processor Specifications\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem \/ Application Program Flash\u003c\/td\u003e\n\u003ctd\u003e2 x 2 MB Flash\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBackup Program Flash\u003c\/td\u003e\n\u003ctd\u003e1 x 16 MB Flash\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBattery-Backed Data SRAM\u003c\/td\u003e\n\u003ctd\u003e2 x 256 KB SRAM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRedundant Communication Data SRAM\u003c\/td\u003e\n\u003ctd\u003e2 x 512 KB SRAM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIObus Communication Drivers\u003c\/td\u003e\n\u003ctd\u003e4 Integrated Channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch4\u003eEnvironmental \u0026amp; Mechanical\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature Range\u003c\/td\u003e\n\u003ctd\u003e-5 degC to +70 degC (+23 degF to +158 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature Range\u003c\/td\u003e\n\u003ctd\u003e-40 degC to +85 degC (-40 degF to +185 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e10% to 95% (Non-condensing)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePhysical Dimensions (H x W x D)\u003c\/td\u003e\n\u003ctd\u003e176 x 88.5 x 212 mm (6.93 x 3.48 x 8.35 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Weight\u003c\/td\u003e\n\u003ctd\u003e1.3 kg (2.87 lbs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections \/ Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eInterface\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eFunction\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eFront Panel 8-Digit Display\u003c\/td\u003e\n\u003ctd\u003eReal-time system messaging, diagnostic scrolling, IP address verification, and software version readout\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus LED Indicator\u003c\/td\u003e\n\u003ctd\u003eMulti-color LED indicating system operational state (Off: Power down\/STOP, Green: Normal, Red: Hardware error)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProcessor Status Key Switch\u003c\/td\u003e\n\u003ctd\u003eHardware selection switch for RUN, IDLE, and STOP processor operating states\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eController Backplane Connector\u003c\/td\u003e\n\u003ctd\u003eProvides interface to internal 5 Vdc \/ 24 Vdc power rails, IObus channels, 1oo2D redundant links, and the 24 Vdc SD input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n\u003cli\u003e\n\u003cstrong\u003eVerify System Requirements:\u003c\/strong\u003e Prior to installing the \u003cstrong\u003eFC-QPP-0002 CC V1.0\u003c\/strong\u003e as a replacement for a QPP-0001, ensure the Safety Manager system software is at firmware Release R121 or higher.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eObserve Safety Controls:\u003c\/strong\u003e Turn the front-panel Processor Status Key Switch to \u003cstrong\u003eSTOP\u003c\/strong\u003e before attempting module insertion or removal from the Controller chassis backplane.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eChassis Alignment:\u003c\/strong\u003e Align the module card edges with the pre-determined Control Processor slot rails inside the CPCHAS-0001 or CPCHAS-0002 chassis. Slide the unit firmly until backplane connectors seat completely.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEmergency Shut Down Wiring Check:\u003c\/strong\u003e If utilizing the external 24 Vdc Emergency Shut Down (SD) trip input, verify proper connection of external potential-free contacts via a SICP-0002\/L3 cable assembly. If unused, ensure the default SD jumper link remains installed on the controller backplane.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eKey Switch Initialization:\u003c\/strong\u003e Rotate the key switch from STOP to IDLE or RUN to initiate processor boot cycles and self-diagnostic power-up routines.\u003c\/li\u003e\n\u003c\/ol\u003e\n\u003ch3\u003eConfiguration \u0026amp; Commissioning\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eFirmware Flash Maintenance:\u003c\/strong\u003e Flash memory on the \u003cstrong\u003eFC-QPP-0002 CC V1.0\u003c\/strong\u003e can be updated directly through the system network interface without physically removing the module from the Controller chassis.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eStatus Display Verification:\u003c\/strong\u003e Use the front-panel \u003cstrong\u003eUp\u003c\/strong\u003e and \u003cstrong\u003eDown\u003c\/strong\u003e scroll buttons to inspect system node numbers, assigned IP addresses (COM 1A\/1B, COM 2A\/2B), supply rail voltages (Vcc, Vb), and internal operating temperature readings (Tmp).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDiagnostic Monitoring:\u003c\/strong\u003e If a hardware fault occurs, scroll to the Fail menu to inspect stored diagnostic events, including specific chassis, slot, module ID, and associated error codes.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRedundant System Synchronization:\u003c\/strong\u003e In dual-controller systems, monitor the LED display during power-up to confirm the module transitions through PowerUp, Sync, and Running states without fault indicators.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eCE Mark:\u003c\/strong\u003e European Conformity Compliance\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eUL Listed:\u003c\/strong\u003e Underwriters Laboratories Certified\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCSA Certified:\u003c\/strong\u003e Canadian Standards Association Approved\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTUV:\u003c\/strong\u003e Safety Approved for High-Integrity Safety Applications (up to SIL3)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFM Approved:\u003c\/strong\u003e Factory Mutual Recognized for Hazardous Locations\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52668015018347,"sku":"FC-QPP-0002 CC V1.0","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/honeywell-fc-qpp-0002-v1-0-quad-processor-dkael0wssrl_d92b083d-edc1-4cd8-b7ab-bbde6ab75ecf.jpg?v=1765505144","url":"https:\/\/www.plcprotech.com\/it\/products\/honeywell-fc-qpp-0002-cc-v1-0-safety-manager-quad-processor-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}