{"product_id":"basler-electric-decs-200-1l-digital-excitation-control-system","title":"Basler Electric DECS-200-1L Digital Excitation Control System","description":"\n\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eBasler Electric DECS-200-1L\u003c\/strong\u003e Digital Excitation Control System provides precision excitation control for synchronous generators by regulating the direct current applied to the generator exciter field. Equipped with a pulse width modulated (PWM) power stage, the system delivers high performance across non-linear load applications and supports output capabilities of 32 Vdc, 63 Vdc, or 125 Vdc at up to 15 Adc. Operating modes include Automatic Voltage Regulation (AVR) with 0.25% accuracy, Field Current Regulation (FCR\/Manual mode), Var control, and Power Factor (PF) control.\u003c\/p\u003e\n\u003cp\u003eThe controller features true RMS single- or three-phase sensing for generator voltage, bus voltage matching, and generator current. Interface options consist of contact inputs, proportional ±10 Vdc or 4–20 mA inputs, a front-panel RS-232 port (COM0), a side RS-232 port for unit autotracking (COM1), and a side RS-485 port supporting Modbus RTU protocol (COM2). Integrated machine protection capabilities include generator overvoltage\/undervoltage, field overvoltage\/overcurrent, loss of sensing, loss of field, exciter diode monitoring (EDM), and overexcitation\/underexcitation limiting.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMicroprocessor-based digital excitation control with pulse width modulated power stage\u003c\/li\u003e\n\u003cli\u003eSingle or three-phase true RMS sensing for generator and bus voltage\u003c\/li\u003e\n\u003cli\u003e0.25% voltage regulation accuracy over the load range\u003c\/li\u003e\n\u003cli\u003eFour operating modes: Automatic Voltage Regulation (AVR), Field Current Regulation (FCR), Var control, and Power Factor (PF) control\u003c\/li\u003e\n\u003cli\u003eInternal autotracking between modes for bumpless transfers\u003c\/li\u003e\n\u003cli\u003e20 standard preprogrammed stability selections and user customizable PID settings\u003c\/li\u003e\n\u003cli\u003eUnderfrequency compensation or V\/Hz ratio limiter with adjustable corner frequency\u003c\/li\u003e\n\u003cli\u003eSoft start voltage buildup with adjustable time rates\u003c\/li\u003e\n\u003cli\u003eReactive droop and reactive differential (cross-current) paralleling compensation\u003c\/li\u003e\n\u003cli\u003eIntegrated Exciter Diode Monitoring (EDM) for detecting open and shorted diodes\u003c\/li\u003e\n\u003cli\u003eSequence of Events Recording (SER) storing up to 127 event reports\u003c\/li\u003e\n\u003cli\u003eIntegrated COMTRADE-compliant oscillography logging up to 8 records\u003c\/li\u003e\n\u003cli\u003eFront panel HMI with backlit LCD display, programming keys, and diagnostic LEDs\u003c\/li\u003e\n\u003cli\u003eMultiple communication ports: RS-232 front (COM0), RS-232 side (COM1), and RS-485 side (COM2) with Modbus protocol\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eExcitation voltage and current regulation for synchronous generators\u003c\/li\u003e\n\u003cli\u003eUtility paralleling power generation systems requiring Var or Power Factor control\u003c\/li\u003e\n\u003cli\u003eBrushless generator exciter field control with diode health monitoring\u003c\/li\u003e\n\u003cli\u003eGenerator protection and overexcitation\/underexcitation limiting\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eTracking Option\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003ePower Supply Option\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eDECS-200-1L\u003c\/td\u003e\n\u003ctd\u003e1 (Internal autotracking)\u003c\/td\u003e\n\u003ctd\u003eL (24\/48 Vdc)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBasler Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDECS-200-1L\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eControl Power Input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16-60 Vdc (24\/48 Vdc nominal, Style L), Burden = 30 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAC Operating Power Input (32 Vdc Output)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e60 Vac nominal (56-70 Vac +\/-10%), 1 or 3 phase, 50-500 Hz, 780 VA burden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAC Operating Power Input (63 Vdc Output)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e120 Vac nominal (100-139 Vac +\/-10%), 1 or 3 phase, 50-500 Hz, 1570 VA burden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAC Operating Power Input (125 Vdc Output)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e240 Vac nominal (190-277 Vac +\/-10%), 1 or 3 phase, 50-500 Hz, 3070 VA burden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Continuous Field Voltage Output\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e32 Vdc, 63 Vdc, or 125 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated Continuous Field Current Output\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15 Adc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated 10-Second Forcing Voltage Output\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 Vdc (32 Vdc mode), 100 Vdc (63 Vdc mode), 200 Vdc (125 Vdc mode)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRated 10-Second Forcing Current Output\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30 Adc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMinimum Field Resistance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2.13 Ohms (32 Vdc), 4.2 Ohms (63 Vdc), 8.3 Ohms (125 Vdc)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGenerator Voltage Sensing Input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 or 3 phase, ranges: 100V\/50Hz (85-127V), 120V\/60Hz (94-153V), 200V\/50Hz (170-254V), 240V\/60Hz (187-305V), 400V\/50Hz (340-508V), 480V\/60Hz (374-600V), 500V\/50Hz (425-625V), 600V\/60Hz (510-660V); Burden \u0026lt; 0.1 VA\/phase\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBus Voltage Sensing Input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 phase, ranges: 100V\/50Hz (85-127V), 120V\/60Hz (94-153V), 200V\/50Hz (170-254V), 240V\/60Hz (187-305V), 400V\/50Hz (340-508V), 480V\/60Hz (374-600V), 500V\/50Hz (425-625V), 600V\/60Hz (510-660V)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eGenerator Current Sensing Input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1A and 5A AC ranges ( metering\/control \u0026amp; cross current compensation); Burden \u0026lt; 1 VA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eContact Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e11 dry contact switching inputs supplied with 24 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAnalog Remote Set Point Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSelectable +\/-10 Vdc or 4-20 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eContact Outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eResistive: 7.0 A at 24 Vdc, 0.7 A at 48 Vdc, 0.2 A at 125 Vdc, 7.0 A at 120\/240 Vac\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAVR Regulation Accuracy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e+\/-0.25% over load range at rated power factor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-40 degC to +60 degC (-40 degF to +140 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStorage Temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-40 degC to +85 degC (-40 degF to +185 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSalt Fog\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePer MIL-STD-810E, Method 509.3 (100 hrs salt fog, 100 hrs drying)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eShock\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e15 Gs in three mutually perpendicular planes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eVibration\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5-26Hz: 1.2Gs; 27-52Hz: 0.914mm double amplitude; 53-500Hz: 5.0Gs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions (H x W x D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e304 mm x 205 mm x 171 mm (12.0 in x 8.08 in x 6.76 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWeight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6.35 kg (14 lbs)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eConnector Pin\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eFunction\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eBATT+ (B7)\u003c\/td\u003e\n\u003ctd\u003eDC Control Power Input (+24\/48 Vdc)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBATT- (B8)\u003c\/td\u003e\n\u003ctd\u003eDC Control Power Input (-24\/48 Vdc)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eL (B9)\u003c\/td\u003e\n\u003ctd\u003eAC Control Power Input Line\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eN (B10)\u003c\/td\u003e\n\u003ctd\u003eAC Control Power Input Neutral\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eC (C4), B (C3), A (C2), GND (C1)\u003c\/td\u003e\n\u003ctd\u003eInput Operating Power Connections and Chassis Ground\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eE1 (A1), E2 (A2), E3 (A3)\u003c\/td\u003e\n\u003ctd\u003eVoltage Sensing Inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCTB 1AMP (B1), CTB 5AMP (B2), CTB COM (B3)\u003c\/td\u003e\n\u003ctd\u003eCurrent Sensing Channel B\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCTCC 1AMP (B4), CTCC 5AMP (B5), CTCC COM (B6)\u003c\/td\u003e\n\u003ctd\u003eCross Current Compensation Sensing Channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA5, B3, A4, B1\u003c\/td\u003e\n\u003ctd\u003eBus Voltage Matching Inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eF+ (C5), F- (C6)\u003c\/td\u003e\n\u003ctd\u003eExciter Field Power Output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA6, A7\u003c\/td\u003e\n\u003ctd\u003e4-20 mAdc Auxiliary Analog Input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA8, A9, A10\u003c\/td\u003e\n\u003ctd\u003e+\/-10 Vdc Auxiliary Analog Input (GND, V+, V-)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA11, A12\u003c\/td\u003e\n\u003ctd\u003eStop\/Start Relay Contacts\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA13, A14\u003c\/td\u003e\n\u003ctd\u003eWatchdog Relay Contacts\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA15, A16\u003c\/td\u003e\n\u003ctd\u003eProgrammable Output Relay #1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA17, A18\u003c\/td\u003e\n\u003ctd\u003eProgrammable Output Relay #2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA19, A20\u003c\/td\u003e\n\u003ctd\u003eProgrammable Output Relay #3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA21, A22\u003c\/td\u003e\n\u003ctd\u003eStart Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA23, A24\u003c\/td\u003e\n\u003ctd\u003eStop Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA25, A26\u003c\/td\u003e\n\u003ctd\u003eAVR Mode Select Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA27, A28\u003c\/td\u003e\n\u003ctd\u003eFCR Mode Select Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA29, A30\u003c\/td\u003e\n\u003ctd\u003eRaise Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA31, A32\u003c\/td\u003e\n\u003ctd\u003eLower Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA33, A34\u003c\/td\u003e\n\u003ctd\u003ePre-position Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA35, A36\u003c\/td\u003e\n\u003ctd\u003eUnit\/Parallel Operation Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA37, A38\u003c\/td\u003e\n\u003ctd\u003eVar\/PF Control Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA39, A40\u003c\/td\u003e\n\u003ctd\u003eSecondary Unit Enable Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA41, A42\u003c\/td\u003e\n\u003ctd\u003eAlarm Reset Contact Input and Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA43, A44, A45\u003c\/td\u003e\n\u003ctd\u003eRS-485 Communication Output Port COM2 (A, B, C)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCOM0 (Front Panel)\u003c\/td\u003e\n\u003ctd\u003eRS-232 9-pin Sub-D Serial Port for local PC interface\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCOM1 (Side Panel)\u003c\/td\u003e\n\u003ctd\u003eRS-232 9-pin Sub-D Serial Port for dual unit autotracking\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eGrounding:\u003c\/strong\u003e Connect terminal C1 (GND) securely to the system chassis ground to ensure proper grounding and noise immunity.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eControl Power Isolation:\u003c\/strong\u003e If dual control power sources are utilized, install an AC Control Power Isolation Transformer (Basler P\/N BE31449-001) on the AC power input.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInrush Current Mitigation:\u003c\/strong\u003e When powering from a source already at rated voltage levels, install an Inrush Current Reduction Module (ICRM-15) to limit startup inrush current.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDual Unit Configurations:\u003c\/strong\u003e For redundant DECS-200 arrangements, connect units using interconnection cable P\/N 9310300032 and install a DECS Freewheeling Diode Module P\/N 9293600101.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCommunication Wiring:\u003c\/strong\u003e Maintain RS-485 network cables within a maximum distance of 4,000 feet using recommended shielded twisted-pair cabling.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eVoltage Sensing:\u003c\/strong\u003e Ensure potential transformers are installed if the line voltage exceeding 600 Vac is connected to the sensing terminals.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eUL Recognized per Standard 508 (File E97035)\u003c\/li\u003e\n\u003cli\u003eCSA Certified per Standard CAN\/CSA-C22.2 No. 14 (File LR23131)\u003c\/li\u003e\n\u003cli\u003eCE Compliant (EMC and LVD directives)\u003c\/li\u003e\n\u003cli\u003eDNV Certified per Standard 2.4\u003c\/li\u003e\n\u003cli\u003eGOST-R Certified\u003c\/li\u003e\n\u003cli\u003eByelorussian Certified\u003c\/li\u003e\n\u003cli\u003eIEEE C37.90.1-1989 (Surge Withstand Capability and Fast Transient)\u003c\/li\u003e\n\u003cli\u003eIEEE 421.3 (High Pot testing)\u003c\/li\u003e\n\u003cli\u003eISO 9001:2000 Registered\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Basler Electric","offers":[{"title":"Default Title","offer_id":53644055511403,"sku":"DECS-200-1L","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/DECS-200-1L_1.jpg?v=1785590957","url":"https:\/\/www.plcprotech.com\/kk\/products\/basler-electric-decs-200-1l-digital-excitation-control-system","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}