{"product_id":"omron-nx-tc3407-nx-series-temperature-control-unit","title":"Omron NX-TC3407 NX Series Temperature Control Unit","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eDesigned for precise thermal management within the Sysmac automation platform, the \u003cstrong\u003eNX-TC3407\u003c\/strong\u003e temperature control unit provides multi-channel regulation and high-speed PID control. This module facilitates 4 separate control loops, supporting versatile input configurations including both thermocouple and resistance thermometer (Pt100) sensors. Configured with 8 digital PNP outputs designed for pulse width modulation (PWM) control, it enables direct integration into heat and cool control loops.\u003c\/p\u003e\n\n\u003cp\u003eOperating directly on the high-speed NX I\/O Bus, the module guarantees rapid signal processing with a conversion time of 50 ms per unit. The \u003cstrong\u003eNX-TC3407\u003c\/strong\u003e features a space-saving 24 mm form factor and utilizes detachable Push-in Plus terminal blocks to streamline wiring, reduce maintenance down-time, and resist vibration-induced loosening in harsh environments.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003e4-loop PID control supporting independent heat and cool regulation.\u003c\/li\u003e\n  \u003cli\u003eUniversal inputs compatible with multiple thermocouple types and Pt100\/JPt100 RTD sensors.\u003c\/li\u003e\n  \u003cli\u003e8 PNP digital outputs designed for PWM control tasks (24 VDC, 21 mA per point).\u003c\/li\u003e\n  \u003cli\u003eFast conversion rate of 50 ms per unit for dynamic thermal processes.\u003c\/li\u003e\n  \u003cli\u003eVibration-resistant Push-in Plus connection terminals for quick toolless wiring.\u003c\/li\u003e\n  \u003cli\u003eCompact 24 mm width design for dense DIN rail mounting configurations.\u003c\/li\u003e\n  \u003cli\u003eSeamless integration with Sysmac Studio software for unified programming and diagnostics.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003ePackaging machinery heat-sealing bars and shrink tunnels.\u003c\/li\u003e\n  \u003cli\u003ePlastic injection molding and extrusion barrel zones.\u003c\/li\u003e\n  \u003cli\u003eSemiconductor manufacturing wafer heating systems.\u003c\/li\u003e\n  \u003cli\u003eFood processing and baking ovens.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eManufacturer\u003c\/strong\u003e\n      \u003ctd\u003eOmron\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003ePart Number \/ Model\u003c\/strong\u003e\n      \u003ctd\u003eNX-TC3407\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eProduct Series\u003c\/strong\u003e\n      \u003ctd\u003eNX Series\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eModule Type\u003c\/strong\u003e\n      \u003ctd\u003eTemperature Control Unit (4-Loop Type)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eNumber of Control Loops\u003c\/strong\u003e\n      \u003ctd\u003e4 loops\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eTemperature Input Types\u003c\/strong\u003e\n      \u003ctd\u003eThermocouple (B, C WRe5-26, E, J, JPt100, K, L, N, P PLII, R, S, T, U), Pt100 RTD\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eNumber of Digital Outputs\u003c\/strong\u003e\n      \u003ctd\u003e8 PNP outputs (PWM compatible)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eOutput Rating\u003c\/strong\u003e\n      \u003ctd\u003e24 VDC, 21 mA per point\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eConversion Time\u003c\/strong\u003e\n      \u003ctd\u003e50 ms per unit\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eControl Modes\u003c\/strong\u003e\n      \u003ctd\u003eHeat or cool control\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eI\/O Bus Type\u003c\/strong\u003e\n      \u003ctd\u003eNX I\/O Bus\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eConnection Type\u003c\/strong\u003e\n      \u003ctd\u003ePush-in Plus terminal block (Detachable, 2 connectors)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eDegree of Protection\u003c\/strong\u003e\n      \u003ctd\u003eIP20\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eDimensions (W x H x D)\u003c\/strong\u003e\n      \u003ctd\u003e24 mm x 100 mm x 80 mm\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003cstrong\u003eWeight\u003c\/strong\u003e\n      \u003ctd\u003e140 g\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eMount the module on a standard 35 mm DIN rail within a clean, dry, IP54-rated control enclosure.\u003c\/li\u003e\n  \u003cli\u003eEnsure that power to the NX-series I\/O system is fully disconnected before inserting or removing the terminal block.\u003c\/li\u003e\n  \u003cli\u003eMaintain adequate clearance above and below the module to facilitate natural thermal dissipation.\u003c\/li\u003e\n  \u003cli\u003eRoute analog sensor and digital output wiring in separate conduits to prevent electrical noise interference.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Omron","offers":[{"title":"Default Title","offer_id":53077936013675,"sku":"NX-TC3407","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/nx-tc3407-mas3aqxkpvp.png?v=1775734014","url":"https:\/\/www.plcprotech.com\/ms\/products\/omron-nx-tc3407-nx-series-temperature-control-unit","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}