{"product_id":"1020521","title":"Honeywell 10205\/2\/1 11600 FSC 2-Channel Fail-Safe Analog Output Module","description":"\u003cp\u003e\u003cstrong\u003eHoneywell 10205\/2\/1\u003c\/strong\u003e (ordering code \u003cstrong\u003e11600\u003c\/strong\u003e) is a two-channel fail-safe analog output module for the Honeywell Fail Safe Control (FSC) platform. Each channel delivers a configurable 0–20 mA or 4–20 mA current signal in an active (internally powered) or passive (externally powered) loop arrangement. It is intended for non-redundant FSC I\/O configurations; the output currents cannot be paralleled for redundant operation.\u003c\/p\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eManufacturer\u003c\/th\u003e\n\u003ctd\u003eHoneywell Safety Management Systems\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eProduct \/ order code\u003c\/th\u003e\n\u003ctd\u003e10205\/2\/1 \/ 11600\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003ePlatform\u003c\/th\u003e\n\u003ctd\u003eHoneywell FSC (Fail Safe Control)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eModule function\u003c\/th\u003e\n\u003ctd\u003eFail-safe analog current output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eNumber of outputs\u003c\/th\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eOutput ranges\u003c\/th\u003e\n\u003ctd\u003e0–20 mA or 4–20 mA; active or passive loop modes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eD\/A conversion\u003c\/th\u003e\n\u003ctd\u003e12-bit per output; A\/D output-value monitoring for diagnostics\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003e5 VDC supply requirement\u003c\/th\u003e\n\u003ctd\u003e30 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003e24 VDC supply requirement\u003c\/th\u003e\n\u003ctd\u003e65 mA base load, plus 30 mA for each active output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eOff-state current\u003c\/th\u003e\n\u003ctd\u003eLess than 0.05 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eActive output: maximum loop resistance\u003c\/th\u003e\n\u003ctd\u003e1 kΩ\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eActive output: maximum output voltage\u003c\/th\u003e\n\u003ctd\u003e30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003ePassive output: external supply\u003c\/th\u003e\n\u003ctd\u003e40 VDC maximum; minimum module voltage drop 7.5 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eWatchdog input current\u003c\/th\u003e\n\u003ctd\u003e0.5 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eIsolation\u003c\/th\u003e\n\u003ctd\u003eAnalog outputs isolated from 5 VDC and 24 VDC supplies; output 0 V terminals internally commoned\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eRack space\u003c\/th\u003e\n\u003ctd\u003e4 HP (4 TE), 3U (3 HE)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eModule \/ rack key coding\u003c\/th\u003e\n\u003ctd\u003eA9 and C5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eHistorical software requirement\u003c\/th\u003e\n\u003ctd\u003eFSC software version 3.00 as listed in the Hardware Manual; verify installed system release\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eI\/O redundancy\u003c\/th\u003e\n\u003ctd\u003eNon-redundant I\/O configurations only\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\n\u003ch3\u003eOutput Modes and Termination\u003c\/h3\u003e\n\u003cp\u003eWhen used with FSC I\/O backplanes, each output requires a corresponding \u003cstrong\u003e10205\/A\/.\u003c\/strong\u003e analog output mode module at the backplane programming connector. The \u003cstrong\u003e10205\/A\/1\u003c\/strong\u003e configures internally powered current-source operation for a passive field load; \u003cstrong\u003e10205\/A\/2\u003c\/strong\u003e configures externally powered current regulation for an active field device. The \u003cstrong\u003e10205\/A\/3\u003c\/strong\u003e dummy mode module is used to terminate an unused output channel. Verify which mode card is installed on each channel before replacing the output module.\u003c\/p\u003e\n\u003cp\u003eThe historical FSC manual permits resistive or capacitive loads; inductive loads may trigger module fault reporting. The 24 VDC feed remains necessary even when a loop is configured for external power. On an unused channel, the required dummy or specified shorting arrangement prevents the module's self-test from raising a fault.\u003c\/p\u003e\n\u003ch3\u003eDiagnostics and Commissioning\u003c\/h3\u003e\n\u003cp\u003eEach channel includes D\/A conversion and an A\/D readback path. The FSC system can check output-value agreement, ability to de-energize, and cross-channel effects within the configured process safety time. This diagnostic architecture does not establish that a particular installed application meets a safety integrity level by itself; the configured system and field circuit must be evaluated independently.\u003c\/p\u003e\n\u003cp\u003eDuring replacement, document the original \u003cstrong\u003e10205\/2\/1 11600\u003c\/strong\u003e order code, rack keying, backplane type, installed 10205\/A mode cards, loop wiring, control-system release and process safety configuration. After controlled installation, verify the output ranges, loop current with an appropriate meter, unused-channel termination, watchdog response and fault indication under site-approved commissioning procedures. The module has P2\/P3 calibration potentiometers; do not alter calibration without the FSC procedure and suitable test equipment.\u003c\/p\u003e\n\u003ch3\u003eDimensions, Weight and Air-Freight Planning\u003c\/h3\u003e\n\u003cp\u003eThe Honeywell hardware manual specifies \u003cstrong\u003e4 HP × 3U rack space\u003c\/strong\u003e, not a complete shipping-carton dimension. Historical spare-parts listings report an approximate module envelope of \u003cstrong\u003e175 × 125 × 25 mm\u003c\/strong\u003e, but these measurements and the listed net weights differ between suppliers; confirm the actual stocked unit before treating them as final dimensions or weight.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eEstimated protective package:\u003c\/strong\u003e 240 × 180 × 90 mm. \u003cstrong\u003eEstimated shipping weight:\u003c\/strong\u003e 0.8 kg. These are preliminary courier\/freight-planning estimates, \u003cem\u003enot Honeywell OEM package specifications\u003c\/em\u003e. Final chargeable dimensions and gross weight must come from the warehouse after protective packing. The previous draft's 325 × 150 × 150 mm figure appears in third-party documentation for a separate associated termination\/motherboard assembly and must not be presented as the physical dimensions of the 10205\/2\/1 module.\u003c\/p\u003e\n\u003ch3\u003eOrdering and Replacement Information\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eModule:\u003c\/strong\u003e 10205\/2\/1. \u003cstrong\u003eOrdering code:\u003c\/strong\u003e 11600. Confirm the complete marking on the stocked unit and whether the required 10205\/A\/1, \/A\/2 or \/A\/3 mode cards, termination assembly and cables are supplied separately. Do not assume 10205\/1\/1 is an unconditional plug-in replacement: its rack keying and system implementation differ. Availability and exact package measurements should be reconfirmed before shipment.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52705307951467,"sku":"10205\/2\/1","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/1020521-3e2dw4lezal_6827b221-c719-4dfd-8360-a10e924e06af.jpg?v=1766639423","url":"https:\/\/www.plcprotech.com\/products\/1020521","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}