{"product_id":"abb-bailey-imcis02-control-i-o-slave-module","title":"ABB Bailey IMCIS02 Control I\/O Slave Module","description":"\u003cp\u003eThe \u003cstrong\u003eABB Bailey IMCIS02\u003c\/strong\u003e is a Control I\/O Slave (CIS) module designed to interface process field signals with the Infi 90 Process Management System. Occupying a single slot in a Module Mounting Unit (MMU), the \u003cstrong\u003eIMCIS02\u003c\/strong\u003e acts as an input\/output bridge, processing field signals to be monitored and executed by master modules like the Multi-Function Processor (MFP).\u003c\/p\u003e\n\u003cp\u003eThe module conditions four analog inputs and three digital inputs from field equipment, while driving two analog outputs and four digital outputs to control industrial processes. Front-panel switch configurations allow customization of analog output behavior and digital input response times to handle process contact debouncing.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eAccepts up to 4 analog inputs and 3 digital inputs.\u003c\/li\u003e\n\u003cli\u003eProvides 2 analog outputs and 4 digital outputs.\u003c\/li\u003e\n\u003cli\u003eSupports selectable analog output modes (1 to 5 VDC or 4 to 20 mA).\u003c\/li\u003e\n\u003cli\u003eOptically isolated digital I\/O for enhanced field circuit noise isolation.\u003c\/li\u003e\n\u003cli\u003eConfigurable digital input response times (1.5 ms Fast \/ 17 ms Slow) for contact debounce filtering.\u003c\/li\u003e\n\u003cli\u003eAutomatic online analog input calibration utilizing integrated reference voltages.\u003c\/li\u003e\n\u003cli\u003eOnboard bus fault timer for process safety and default output state enforcement upon communication loss.\u003c\/li\u003e\n\u003cli\u003eFront-panel status LED indicator for operational diagnostics and bus fault tracking.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eDistributed Control Systems (DCS) process monitoring and control\u003c\/li\u003e\n\u003cli\u003eAnalog loop field signal interface and conditioning\u003c\/li\u003e\n\u003cli\u003eDiscrete device field status monitoring and control\u003c\/li\u003e\n\u003cli\u003eSystem expansion and signal integration within Infi 90 systems\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eABB \/ Elsag Bailey\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIMCIS02\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModule Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eControl I\/O Slave Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eLogic Power Requirements\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cp\u003e+5 VDC (±5%) @ 332 mA max\u003c\/p\u003e\n\u003cp\u003e+15 VDC (-2.5%, +5%) @ 35 mA max\u003c\/p\u003e\n\u003cp\u003e-15 VDC (-5%, +2.5%) @ 30 mA max\u003c\/p\u003e\n\u003cp\u003e+24 VDC (±10%) @ 50 mA max\u003c\/p\u003e\n\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Dissipation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cp\u003e1.65 W @ +5 VDC\u003c\/p\u003e\n\u003cp\u003e525 mW @ +15 VDC\u003c\/p\u003e\n\u003cp\u003e450 mW @ -15 VDC\u003c\/p\u003e\n\u003cp\u003e1.20 W @ +24 VDC\u003c\/p\u003e\n\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAnalog Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 differential\/single-ended (1-5 VDC, or 4-20 mA via TU\/TM)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eA\/D Resolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAnalog Input Accuracy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e±0.10% of Full Scale Range (FSR)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAnalog Outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2 selectable (1-5 VDC or 4-20 mA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eD\/A Resolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 bits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAnalog Output Accuracy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cp\u003eVoltage: ±0.15% of FSR\u003c\/p\u003e\n\u003cp\u003eCurrent: ±0.25% of FSR\u003c\/p\u003e\n\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDigital Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3 optically isolated (24 VDC, 125 VDC, 120 VAC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDigital Outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 open collector, optically isolated (24 VDC, 250 mA max sink)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMounting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eOccupies 1 slot in standard Infi 90 Module Mounting Unit (MMU)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0 to 70 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelative Humidity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\n\u003cp\u003e0% to 95% up to 55 degC (non-condensing)\u003c\/p\u003e\n\u003cp\u003e0% to 45% up to 70 degC (non-condensing)\u003c\/p\u003e\n\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eAltitude\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSea Level to 3 Km\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eConnector Pin\u003c\/th\u003e\n\u003cth\u003eFunction\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP1-1, P1-2\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e+5 VDC Power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP1-5, P1-6\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePower Common\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP1-7\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e+15 VDC Power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP1-8\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-15 VDC Power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP1-9, P1-10\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePower Fail Interrupt (PFI)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP2 (1-10)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSlave Expander Bus (Data 0-7, Clock, Sync)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-A \/ P3-1\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Output 1 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-B \/ P3-2\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Output 2 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-C \/ P3-3\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Output 3 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-D \/ P3-4\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Output 4 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-F \/ P3-6\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Input 1 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-H \/ P3-7\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Input 2 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-J \/ P3-8\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDigital Input 3 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-K \/ P3-9\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e+24 VDC Power\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-L \/ P3-10\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog Output 1 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-M \/ P3-11\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog Output 2 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-N \/ P3-12\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog Input 1 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-P \/ P3-13\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog Input 2 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-R \/ P3-14\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog Input 3 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eP3-S \/ P3-15\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAnalog Input 4 (+ \/ -)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eESD Handling:\u003c\/strong\u003e Use a static dissipative grounding wrist strap and anti-static field kit when handling or installing the module to prevent electrostatic damage to sensitive components.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMMU Mounting:\u003c\/strong\u003e Align the circuit board with the top and bottom plastic guide rails of the designated MMU slot and slide in until flush with the rack frame. Lock the captive retaining screws by turning them half a turn into the vertical latched position.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eExpander Bus Setup:\u003c\/strong\u003e Ensure a dipshunt is correctly installed in the backplane socket between the master controller and the slave module to establish communication on the slave expander bus.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConfiguration Verification:\u003c\/strong\u003e Set DIP switches S1 (Slave Address), S2 (Analog Output Default), S3 (Analog Output Mode), and jumpers J1 through J6 (Digital Input Voltages\/Speed) prior to sliding the board into the MMU.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eWiring \u0026amp; Cabling:\u003c\/strong\u003e Route field signals using compatible termination devices (NTCS02 Termination Unit or NICS01 Termination Module) connected via standard NKTU or NKTM cables to connector P3.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eCSA:\u003c\/strong\u003e Certified for use as process control equipment in ordinary (non-hazardous) locations.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":52668624601451,"sku":"IMCIS02","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/abb-imcis02-control-i-o-slave-module-vlkm1ib0xjx_b1a6b003-470c-45fd-81e7-979911940124.jpg?v=1765535932","url":"https:\/\/www.plcprotech.com\/products\/abb-bailey-imcis02-control-i-o-slave-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}