{"product_id":"beckhoff-el3413-ethercat-terminal-3-phase-power-measurement","title":"BECKHOFF EL3413 EtherCAT Terminal: 3-Phase Power Measurement","description":"\u003cp\u003eThe \u003cstrong\u003eEL3413\u003c\/strong\u003e is a high-precision, 3-phase \u003cstrong\u003eEtherCAT Terminal\u003c\/strong\u003e designed for comprehensive power measurement of alternating voltages up to 690 V AC. It is engineered to monitor energy consumption and power quality directly within the EtherCAT system. With its ability to perform harmonic analysis and measure effective, reactive, and apparent power, the EL3413 is an essential component for energy management and grid monitoring applications.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003e3-Phase Power Measurement:\u003c\/strong\u003e Capable of monitoring 3-phase systems, with optional single-phase operation.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eExtensive Measured Values:\u003c\/strong\u003e Provides data for current (I1, I2, I3, In), voltage, effective\/reactive\/apparent power, energy, cos φ, frequency, and harmonic analysis.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGalvanic Isolation:\u003c\/strong\u003e High electrical isolation (4500 V) and galvanically isolated current inputs ensure safety and measurement accuracy.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFlexible Current Input:\u003c\/strong\u003e Adjustable range for current measurement: 100 mA, 1 A (default), and 5 A.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCompact Design:\u003c\/strong\u003e 12 mm wide housing for high-density DIN rail mounting in control cabinets.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eIndustrial energy monitoring and cost optimization\u003c\/li\u003e\n\u003cli\u003ePower quality analysis in electrical grids\u003c\/li\u003e\n\u003cli\u003eMonitoring of machinery energy efficiency\u003c\/li\u003e\n\u003cli\u003ePreventive maintenance for motor-driven systems\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eCategory\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eBECKHOFF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eEL3413\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasuring Voltage\u003c\/td\u003e\n\u003ctd\u003eMax. 690 V AC (3-phase)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasuring Current\u003c\/td\u003e\n\u003ctd\u003eAdjustable (100 mA, 1 A, 5 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Isolation\u003c\/td\u003e\n\u003ctd\u003e4500 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e1 μA, 0.1 mV, 10 mW\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMeasuring Error\u003c\/td\u003e\n\u003ctd\u003e0.5 % (U\/I), 1 % (calculated values)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption (E-bus)\u003c\/td\u003e\n\u003ctd\u003etyp. 160 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-25 to +60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProtection Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions (W x H x D)\u003c\/td\u003e\n\u003ctd\u003e12 mm x 100 mm x 68 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMount on a 35 mm DIN rail (EN 60715) using the integrated lock mechanism.\u003c\/li\u003e\n\u003cli\u003eEnsure proper wiring for 3-phase voltage and current inputs, utilizing the spring-actuated terminals for solid or flexible conductors (stripping length 8–9 mm).\u003c\/li\u003e\n\u003cli\u003eAdhere to all local electrical safety regulations when connecting high-voltage (up to 690 V AC) circuits.\u003c\/li\u003e\n\u003cli\u003eFollow EMC immunity standards (EN 61000-6-2\/EN 61000-6-4) for cabinet wiring to prevent electromagnetic interference with power data.\u003c\/li\u003e\n\u003cli\u003eEnsure consistent ambient conditions between -25 and +60 degC.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"BECKHOFF","offers":[{"title":"Default Title","offer_id":53106595201387,"sku":"EL3413","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/el3413-f3ewckbyot0.png?v=1776244486","url":"https:\/\/www.plcprotech.com\/products\/beckhoff-el3413-ethercat-terminal-3-phase-power-measurement","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}