{"product_id":"beckhoff-ks3362-bus-terminal","title":"BECKHOFF KS3362 Bus Terminal","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eBECKHOFF KS3362\u003c\/strong\u003e is a 2-channel analog input Bus Terminal designed for high-speed data logging and analysis of voltage signals in the range of -10 to +10 V. As part of the Beckhoff K-bus system, this terminal integrates high-speed data logger capabilities directly into standard I\/O stations, enabling rapid transient capture and analog signal processing without requiring external specialized measuring hardware.\u003c\/p\u003e\n\n\u003cp\u003eFeaturing an integrated trigger input and 32 kbytes of internal memory, the \u003cstrong\u003eBECKHOFF KS3362\u003c\/strong\u003e allows for precise, event-controlled measurement cycles. This terminal distinguishes itself from standard Bus Terminals by incorporating a pluggable wiring level (KS housing), which simplifies installation, commissioning, and physical maintenance workflows by allowing pre-wired terminal blocks to be detached without disturbing the field wiring.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eTwo high-speed analog input channels supporting -10 to +10 V voltage signals\u003c\/li\u003e\n  \u003cli\u003eIntegrated, configurable trigger input for precise measurement initiation\u003c\/li\u003e\n  \u003cli\u003e32 kbytes of internal memory dedicated to high-speed data logging\u003c\/li\u003e\n  \u003cli\u003eConfigurable conversion times down to 10 microseconds in fast sampling mode\u003c\/li\u003e\n  \u003cli\u003ePluggable connection level (KS-series housing) for rapid, tool-free physical replacement\u003c\/li\u003e\n  \u003cli\u003ePower supplied completely via the internal K-bus, eliminating the need for power contact routing\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eHigh-speed transient voltage capturing and waveform analysis\u003c\/li\u003e\n  \u003cli\u003eDynamic machine monitoring and diagnostic recording\u003c\/li\u003e\n  \u003cli\u003eEvent-triggered signal sampling in quality assurance and test bench systems\u003c\/li\u003e\n  \u003cli\u003eFast process loop feedback in synchronized industrial automation environments\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ch4\u003eGeneral\u003c\/h4\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eParameter\u003c\/td\u003e\n      \u003ctd\u003eSpecification\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eManufacturer\u003c\/td\u003e\n      \u003ctd\u003eBECKHOFF\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eModel\u003c\/td\u003e\n      \u003ctd\u003eKS3362\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eProduct Type\u003c\/td\u003e\n      \u003ctd\u003eBus Terminal (High-Speed Data Logger)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eHousing Type\u003c\/td\u003e\n      \u003ctd\u003ePluggable wiring level\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMaterial\u003c\/td\u003e\n      \u003ctd\u003ePolycarbonate\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch4\u003eSignal and I\/O\u003c\/h4\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eNumber of Inputs\u003c\/td\u003e\n      \u003ctd\u003e2 analog inputs, 1 trigger input\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eSignal Voltage Range\u003c\/td\u003e\n      \u003ctd\u003e-10 to +10 V\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eInternal Memory\u003c\/td\u003e\n      \u003ctd\u003e32 kbytes\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eResolution\u003c\/td\u003e\n      \u003ctd\u003e14 bit + sign\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMeasuring Error\u003c\/td\u003e\n      \u003ctd\u003e\u0026lt; ±0.5% (relative to full scale value)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eInternal Resistance\u003c\/td\u003e\n      \u003ctd\u003e\u0026gt; 500 kΩ (E1-GND, E2-GND)\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch4\u003eElectrical and Communication\u003c\/h4\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003ePower Supply\u003c\/td\u003e\n      \u003ctd\u003eVia the K-bus\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eCurrent Consumption K-bus\u003c\/td\u003e\n      \u003ctd\u003eTypically 120 mA\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eCurrent Consumption Power Contacts\u003c\/td\u003e\n      \u003ctd\u003eNone (no power contacts present)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eBit Width in Process Image\u003c\/td\u003e\n      \u003ctd\u003eInput\/Output: 2 x 16 bit data (2 x 8 bit control\/status per channel)\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch4\u003ePerformance\u003c\/h4\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eConversion Time\u003c\/td\u003e\n      \u003ctd\u003e\u0026lt; 100 microseconds (configurable down to 10 microseconds in fast sampling mode)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eTrigger Function\u003c\/td\u003e\n      \u003ctd\u003eConfigurable\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch4\u003eConnection and Mechanical\u003c\/h4\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eConnection Technology\u003c\/td\u003e\n      \u003ctd\u003ePluggable spring-force actuation\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eSolid Conductor Cross-Section\u003c\/td\u003e\n      \u003ctd\u003e0.08 to 1.5 mm² (AWG 28 to 16)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eStranded Conductor Cross-Section\u003c\/td\u003e\n      \u003ctd\u003e0.08 to 1.5 mm² (AWG 28 to 16)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eFine-Stranded Conductor Cross-Section\u003c\/td\u003e\n      \u003ctd\u003e0.14 to 1.5 mm² (AWG 26 to 16)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eStripping Length\u003c\/td\u003e\n      \u003ctd\u003e9 to 10 mm\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eDimensions (W x H x D)\u003c\/td\u003e\n      \u003ctd\u003e12 mm x 100 mm x 68 mm\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMounting\u003c\/td\u003e\n      \u003ctd\u003e35 mm DIN rail conforming to EN 60715 with lock\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch4\u003eEnvironmental and Compliance\u003c\/h4\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eOperating Temperature\u003c\/td\u003e\n      \u003ctd\u003e0 to +55 degC\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eStorage Temperature\u003c\/td\u003e\n      \u003ctd\u003e-25 to +85 degC\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eRelative Humidity\u003c\/td\u003e\n      \u003ctd\u003e95%, non-condensing\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eIP Rating\u003c\/td\u003e\n      \u003ctd\u003eIP20\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eApprovals and Markings\u003c\/td\u003e\n      \u003ctd\u003eCE, UL, ATEX (II 3 G Ex nA IIC T4 Gc)\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n  \u003cli\u003eEnsure all electrical components and power sources to the K-bus system are fully de-energized before mounting or servicing.\u003c\/li\u003e\n  \u003cli\u003eMount the terminal onto a standard 35 mm DIN rail conforming to EN 60715, securing the lock to prevent mechanical drift.\u003c\/li\u003e\n  \u003cli\u003eTo perform wiring, utilize a small flat-blade screwdriver to actuate the spring-force terminals on the pluggable connector block.\u003c\/li\u003e\n  \u003cli\u003eEnsure field wiring conductor insulation is stripped to the designated length of 9 to 10 mm before insertion.\u003c\/li\u003e\n  \u003cli\u003eVerify K-bus power configuration. Because this terminal does not pass power contacts, ensure subsequent power-contact-dependent terminals on the same rail are supplied through a separate power supply terminal if required.\u003c\/li\u003e\n\u003c\/ol\u003e\n\n\u003ch3\u003eReplacement Recommendations\u003c\/h3\u003e\n\u003cp\u003eThe pluggable wiring design of the \u003cstrong\u003eBECKHOFF KS3362\u003c\/strong\u003e simplifies replacement routines. Field-side wiring remains permanently clamped in the removable terminal block. To replace a faulty terminal, gently disconnect the pre-wired connector block from the housing, release the mechanical lock to slide the module off the DIN rail, install the replacement module, and securely re-plug the pre-wired connector. This eliminates manual rewiring and reduces potential commissioning wiring errors.\u003c\/p\u003e","brand":"BECKHOFF","offers":[{"title":"Default Title","offer_id":53106459214187,"sku":"KS3362","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/ks3362-ui5nkx02oc0.png?v=1776245303","url":"https:\/\/www.plcprotech.com\/products\/beckhoff-ks3362-bus-terminal","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}