{"product_id":"bently-nevada-3300-35-12-01-01-00-00-six-channel-temperature-rtd-input-monitor","title":"Bently Nevada 3300\/35-12-01-01-00-00 Six-Channel Temperature RTD Input Monitor","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eBently Nevada 3300\/35-12-01-01-00-00\u003c\/strong\u003e is a \u003cstrong\u003e3300 Series Six-Channel Temperature RTD Input Monitor\u003c\/strong\u003e engineered to provide continuous, on-line temperature monitoring for industrial machinery. This specific configuration accepts input signals from six 3-wire 100 ohm platinum RTD sensors across a full-scale range of 0 to 150 degC. It performs continuous signal conditioning, drives individual channel recorder outputs, and includes epoxy-sealed alarm relays for machine protection. Operating within the Bently Nevada 3300 system rack, the unit displays monitored temperatures on a 4-digit LCD screen and provides status indication via front-panel LEDs.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMonitors six independent temperature channels using resistance temperature detector (RTD) inputs.\u003c\/li\u003e\n\u003cli\u003ePre-configured for 3-wire 100 ohm platinum RTD sensors with an alpha coefficient of 0.00392.\u003c\/li\u003e\n\u003cli\u003eFactory calibrated for a 0 to 150 degC full-scale operating range.\u003c\/li\u003e\n\u003cli\u003eEquipped with an epoxy-sealed dual alarm relay module for Alarm 1 and Alarm 2 contact outputs.\u003c\/li\u003e\n\u003cli\u003eProvides individual proportional recorder outputs (+4 to +20 mA default) for each channel.\u003c\/li\u003e\n\u003cli\u003eFeatures a front-panel 4-digit LCD display alongside OK, Alarm 1, Alarm 2, and Bypass status LEDs.\u003c\/li\u003e\n\u003cli\u003eSupports internal plug-in jumpers for configuring alarm delays, reset logic, and recorder output types.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eContinuous temperature monitoring of machinery bearings, windings, and stator temperatures.\u003c\/li\u003e\n\u003cli\u003eOn-line RTD signal conditioning and alarm protection in Bently Nevada 3300 rack systems.\u003c\/li\u003e\n\u003cli\u003eIndustrial monitoring applications requiring localized digital readout and dedicated relay outputs.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eOrdering Code Component\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSelected Option\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eTechnical Specification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003e3300\/35\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSix-Channel Temperature RTD Input Monitor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eA: Full-scale Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003e12\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0 to 150 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eB: Transducer Input\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003e01\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 ohm platinum (a = 0.00392) (3-wire)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eC: Alarm Relay\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003e01\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eEpoxy-sealed relays\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eD: Agency Approval\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003e00\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNot required\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eE: Safety Barriers\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003e00\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNone\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eBently Nevada\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e3300\/35-12-01-01-00-00\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSix-Channel Temperature RTD Input Monitor\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eBently Nevada 3300 System\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e6 independent channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTransducer Type\u003c\/td\u003e\n\u003ctd\u003e3-wire 100 ohm platinum RTD (a = 0.00392)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFull-Scale Range\u003c\/td\u003e\n\u003ctd\u003e0 to 150 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAlarm Relay Module\u003c\/td\u003e\n\u003ctd\u003eEpoxy-sealed relays\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAgency Approval Option\u003c\/td\u003e\n\u003ctd\u003eNot required\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSafety Barrier Option\u003c\/td\u003e\n\u003ctd\u003eNone\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNominal 4 watts\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay\u003c\/td\u003e\n\u003ctd\u003e4-digit 7-segment non-multiplexing LCD with decimal point\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay Accuracy (+25 degC)\u003c\/td\u003e\n\u003ctd\u003eWithin +\/-1 degC (+\/-1.8 degF) with tenths digit; +\/-1.5 degC (+\/-2.7 degF) without tenths digit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDisplay Resolution\u003c\/td\u003e\n\u003ctd\u003e0.1 or 1 (user-programmable)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLED Status Indicators\u003c\/td\u003e\n\u003ctd\u003eOK (green), Alarm 1 (red), Alarm 2 (red), Bypass (red)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRecorder Output Signal\u003c\/td\u003e\n\u003ctd\u003eUser-programmable: +4 to +20 mA, 0 to -10 Vdc, or +1 to +5 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRecorder Accuracy (+4 to +20 mA)\u003c\/td\u003e\n\u003ctd\u003e+\/-1.8% of signal, +\/-0.09 mA offset (at +25 degC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Output Impedance\u003c\/td\u003e\n\u003ctd\u003e100 ohm (minimum load resistance 10 k ohm)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Output Compliance\u003c\/td\u003e\n\u003ctd\u003e0 to +12 Vdc across load (0 to 600 ohm load for +4 to +20 mA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAlarm Setpoint Adjustment\u003c\/td\u003e\n\u003ctd\u003eDigitally adjustable 0 to +500 degC (0 to +1000 degF), repeatability +\/-1 degC (+\/-1.8 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e0 degC to +65 degC (+32 degF to +150 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 degC to +85 degC (-40 degF to +185 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003eUp to 95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpace Requirements\u003c\/td\u003e\n\u003ctd\u003eTwo rack positions (positions 3 through 12 in 3300 rack)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e2.8 kg (6.2 lbs.)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eInterface \/ Connector\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eFunction\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eRTD Input Connector\u003c\/td\u003e\n\u003ctd\u003eTerminal connections for 3-wire RTD sensor inputs (Channels 1 to 6)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRecorder Output Connector\u003c\/td\u003e\n\u003ctd\u003eTerminal outputs for individual channel recorder signals (CH1-CH6: +, -S, COM)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAlarm Contact Connector\u003c\/td\u003e\n\u003ctd\u003eRelay output contacts for Alarm 1 and Alarm 2 (NC, ARM, NO)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMount the module into two vacant positions of a 3300 rack (positions 3 through 12; positions 1 and 2 are reserved for Power Supply and System Monitor).\u003c\/li\u003e\n\u003cli\u003eLand 3-wire RTD sensor wiring directly onto the channel terminal connectors on the rear input assembly.\u003c\/li\u003e\n\u003cli\u003eConfigure internal plug-in jumpers behind the front panel to adjust settings such as Alarm Delays (1, 3, or 6 seconds), Latching\/Nonlatching reset modes, and Recorder Output types.\u003c\/li\u003e\n\u003cli\u003eUse the front-panel MODE, CHANNEL STEP, ALARM 1, and ALARM 2 pushbuttons to review monitored values and setpoint levels without interrupting monitoring operations.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eCE EMC Directive (Certificate of Conformity: 158710)\u003c\/li\u003e\n\u003cli\u003eCE Low Voltage Directive (Certificate of Conformity: 135300)\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":53698364965227,"sku":"3300\/35-12-01-01-00-00","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/3300-35-12-01-01-00-00_003_1200x1200_0c20321e-8fb5-48fd-bf9e-6502c3dc2bff.jpg?v=1786368783","url":"https:\/\/www.plcprotech.com\/products\/bently-nevada-3300-35-12-01-01-00-00-six-channel-temperature-rtd-input-monitor","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}