{"product_id":"bently-nevada-330103-00-10-10-11-05-3300-xl-8-mm-proximity-probe","title":"Bently Nevada 330103-00-10-10-11-05 3300 XL 8 mm Proximity Probe","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003e330103-00-10-10-11-05\u003c\/strong\u003e: 3300 XL 8 mm armored proximity probe, 3\/8-24 UNF thread, 0.0 in unthreaded length (Option 00), 1.0 m total length (Option 10), and CSA\/ATEX\/IECEx approval (Option 05). This component operates within 3300 XL 8 mm monitoring chains to deliver non-contact eddy-current displacement measurements for critical machinery, such as shaft vibration and axial position monitoring on turbines and compressors.\u003c\/p\u003e\n\u003cp\u003eThe 330103 series probe differs from standard 330101 series probes by incorporating a protective stainless steel armor over the coaxial cable, providing additional mechanical protection against abrasion and physical damage in industrial environments. This specific configuration includes a FluidLoc cable to prevent liquid migration along the cable assembly, ensuring operational integrity in high-moisture or oil-exposed installations.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eOption 00: 0.0 in (0 mm) unthreaded length (fully threaded body)\u003c\/li\u003e\n\u003cli\u003eOption 10: 1.0 in (25.4 mm) case length\u003c\/li\u003e\n\u003cli\u003eOption 10: 1.0 m (3.3 ft) total system length\u003c\/li\u003e\n\u003cli\u003eOption 11: Miniature ClickLoc coaxial connector with FluidLoc cable\u003c\/li\u003e\n\u003cli\u003eOption 05: CSA, ATEX, and IECEx hazardous area agency approvals\u003c\/li\u003e\n\u003cli\u003eArmored cable construction for mechanical durability\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eTurbine and compressor shaft vibration monitoring\u003c\/li\u003e\n\u003cli\u003eRotor axial position measurement\u003c\/li\u003e\n\u003cli\u003eCritical rotating machinery protection\u003c\/li\u003e\n\u003cli\u003eFluid-exposed or abrasive industrial environments\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003ctable\u003e\n\u003ctr\u003e\n\u003cth\u003eOption\u003c\/th\u003e\n\u003cth\u003eCode on This SKU\u003c\/th\u003e\n\u003cth\u003eDescription\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrderable Part Number\u003c\/td\u003e\n\u003ctd\u003e330103-00-10-10-11-05\u003c\/td\u003e\n\u003ctd\u003e3300 XL 8 mm Proximity Probe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA - Unthreaded Length\u003c\/td\u003e\n\u003ctd\u003e00\u003c\/td\u003e\n\u003ctd\u003e0.0 in\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eB - Case Length\u003c\/td\u003e\n\u003ctd\u003e10\u003c\/td\u003e\n\u003ctd\u003e1.0 in\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eC - Total Length\u003c\/td\u003e\n\u003ctd\u003e10\u003c\/td\u003e\n\u003ctd\u003e1.0 m\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eD - Connector\/Cable\u003c\/td\u003e\n\u003ctd\u003e11\u003c\/td\u003e\n\u003ctd\u003eMiniature ClickLoc \/ FluidLoc cable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eE - Agency Approval\u003c\/td\u003e\n\u003ctd\u003e05\u003c\/td\u003e\n\u003ctd\u003eCSA, ATEX, IECEx\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003ctr\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eBently Nevada\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e330103-00-10-10-11-05\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProbe Diameter\u003c\/td\u003e\n\u003ctd\u003e8 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eThread Size\u003c\/td\u003e\n\u003ctd\u003e3\/8-24 UNF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCable Type\u003c\/td\u003e\n\u003ctd\u003eArmored coaxial with FluidLoc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnector Type\u003c\/td\u003e\n\u003ctd\u003eMiniature ClickLoc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd\u003e-51 degC to +177 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCase Material\u003c\/td\u003e\n\u003ctd\u003eAISI 303 or 304 stainless steel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCSA, ATEX, IECEx (Option 05)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cp\u003eEnsure the probe is mounted in a rigid bracket to prevent vibration interference. The probe gap should be set according to the Proximitor sensor calibration (typically 1.27 mm gap). When routing the armored cable, maintain the minimum bend radius to avoid damaging the internal coaxial core. Ensure all connector interfaces are clean and free of moisture or oil before mating. Consult the 3300 XL system manual for specific hazardous area installation requirements regarding zener barriers or galvanic isolators.\u003c\/p\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":52666545930603,"sku":"330103-00-10-10-11-05","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/bently-nevada-330103-00-10-10-11-05-8-mm-proximity-probe-vfhugduk0gl_dc879637-2acf-4ce7-8681-1f17fa9d2870.jpg?v=1765440528","url":"https:\/\/www.plcprotech.com\/products\/bently-nevada-330103-00-10-10-11-05-3300-xl-8-mm-proximity-probe","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}