{"product_id":"bently-nevada-330103-03-10-10-11-00-3300-xl-8-mm-proximity-probe","title":"Bently Nevada 330103-03-10-10-11-00 3300 XL 8 mm Proximity Probe","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eOption 03 (30 mm unthreaded length), Option 10 (100 mm case length), and Option 11 (ClickLoc connector with protector, FluidLoc cable) specify this metric \u003cstrong\u003e3300 XL 8 mm proximity probe\u003c\/strong\u003e configuration — \u003cstrong\u003e330103-03-10-10-11-00\u003c\/strong\u003e.\u003c\/p\u003e\n\u003cp\u003eThis metric configuration features an unarmored cable design with M10 x 1 threads, distinguishing it from standard-threaded (3\/8-24 UNF) probe configurations like the 330101 or armored options like the 330104. The integration of FluidLoc cable technology prevents oil or other process fluids from leaking through the cable interior, making it well-suited for applications where pressure differentials or fluid containment are critical, while the connector protector adds environmental protection at the probe-to-extension cable junction.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eOption 03 specifies a 30 mm unthreaded body segment.\u003c\/li\u003e\n  \u003cli\u003eOption 10 provides a 100 mm overall stainless steel case length with M10 x 1 threads.\u003c\/li\u003e\n  \u003cli\u003eOption 11 integrates a FluidLoc cable to prevent fluid and oil migration through the cable core.\u003c\/li\u003e\n  \u003cli\u003ePre-installed fluorosilicone connector protector shields the miniature coaxial ClickLoc connection.\u003c\/li\u003e\n  \u003cli\u003eStandard 1.0 meter (3.3 feet) total cable length.\u003c\/li\u003e\n  \u003cli\u003eOption 00 indicates that agency approvals are not required for this configuration.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eEddy-current non-contacting machinery vibration and position monitoring\u003c\/li\u003e\n  \u003cli\u003eThrust position and radial shaft vibration measurements\u003c\/li\u003e\n  \u003cli\u003eFluid-film bearing performance evaluation in rotating machinery\u003c\/li\u003e\n  \u003cli\u003ePetrochemical, refining, oil and gas, and power generation turbomachinery applications\u003c\/li\u003e\n  \u003cli\u003eDirect replacement in M10 threaded configurations requiring fluid-blocking cable properties\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eOrdering Information\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003cthead\u003e\n    \u003ctr\u003e\n      \u003cth\u003eOption\u003c\/th\u003e\n      \u003cth\u003eCode on This SKU\u003c\/th\u003e\n      \u003cth\u003eDescription\u003c\/th\u003e\n    \u003c\/tr\u003e\n  \u003c\/thead\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eOrderable Part Number\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e\u003cstrong\u003e330103-03-10-10-11-00\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e3300 XL 8 mm Proximity Probe, M10 x 1 thread, without armor\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eA - Unthreaded Length\u003c\/td\u003e\n      \u003ctd\u003e03\u003c\/td\u003e\n      \u003ctd\u003e30 mm unthreaded length\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eB - Overall Case Length\u003c\/td\u003e\n      \u003ctd\u003e10\u003c\/td\u003e\n      \u003ctd\u003e100 mm case length\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eC - Total Length\u003c\/td\u003e\n      \u003ctd\u003e10\u003c\/td\u003e\n      \u003ctd\u003e1.0 meter (3.3 feet) total length\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eD - Connector\/Cable Option\u003c\/td\u003e\n      \u003ctd\u003e11\u003c\/td\u003e\n      \u003ctd\u003eMiniature coaxial ClickLoc connector with connector protector, FluidLoc cable\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eE - Agency Approval Option\u003c\/td\u003e\n      \u003ctd\u003e00\u003c\/td\u003e\n      \u003ctd\u003eNot required\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003eBently Nevada (Baker Hughes)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003ePart Number\/Model\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e330103-03-10-10-11-00\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eProbe Tip Material\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003ePolyphenylene sulfide (PPS)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eProbe Case Material\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003eAISI 303 or 304 stainless steel (SST)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eThread Size\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003eM10 x 1\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eUnthreaded Length\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e30 mm\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eCase Length\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e100 mm\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eTotal Cable Length\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e1.0 meter (3.3 feet)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eCable Type\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e75 ohm triaxial fluoroethylene propylene (FEP) insulated, FluidLoc style\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eConnector Type\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003eMiniature coaxial ClickLoc\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eConnector Protector\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003ePre-installed fluorosilicone protector\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eCalibration Target\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003eAISI 4140 steel\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eTemperature Range\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e-52 degC to +177 degC (-62 degF to +350 degF) operating\/storage\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003ePressure Seal Limit\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003eSeals differential pressure between tip and case with Viton O-ring\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eRecommended Torque\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e7.5 N-m (66 in-lbf) standard, 22.6 N-m (200 in-lbf) maximum\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eTensile Strength Limit\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e330 N (75 lbf) probe case to lead\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eDimensions\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e10 mm x 10 mm x 100 mm (H x W x D)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003e\u003cstrong\u003eWeight\u003c\/strong\u003e\u003c\/td\u003e\n      \u003ctd\u003e0.32 kg\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eConnections and Interfaces\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003cthead\u003e\n    \u003ctr\u003e\n      \u003cth\u003eConnection Type\u003c\/th\u003e\n      \u003cth\u003eDescription\u003c\/th\u003e\n    \u003c\/tr\u003e\n  \u003c\/thead\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMiniature male coaxial ClickLoc\u003c\/td\u003e\n      \u003ctd\u003eGold-plated brass\/beryllium copper connector, finger-tight click interface\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eConnector Protector\u003c\/td\u003e\n      \u003ctd\u003ePre-installed fluorosilicone protector over the coaxial connection\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cp\u003eMaintain standard thread engagement limits for metric M10 x 1 threads, keeping engagement to 15 mm or less. Tighten the probe case using M10 wrench flats to the recommended 7.5 N-m torque. Inspect and clean miniature coaxial ClickLoc connector faces before connecting. Secure them finger-tight until the lock clicks. Always ensure the minimum cable bend radius of 25.4 mm (1.0 inch) is observed during routing to prevent insulation or shielding fatigue.\u003c\/p\u003e\n\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cp\u003eCompliance and standards achieved by standard 3300 XL transducer systems include standard European Union EMC Directive (2014\/30\/EU), RoHS Directive (2011\/65\/EU), and Functional Safety certification up to SIL 2 (HFT = 0) and SIL 3 (HFT = 1).\u003c\/p\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":52666749649259,"sku":"330103-03-10-10-11-00","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/bently-nevada-330103-03-10-10-11-00-3300-xl-8-mm-probe-shh02c2akgb_9f205918-7c50-476d-9c38-22b229a356f6.jpg?v=1765446990","url":"https:\/\/www.plcprotech.com\/products\/bently-nevada-330103-03-10-10-11-00-3300-xl-8-mm-proximity-probe","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}