{"product_id":"bently-nevada-3500-61-05-cn-3500-61-temperature-module-with-recorder-outputs","title":"Bently Nevada 3500\/61-05-CN 3500\/61 Temperature Module with Recorder Outputs","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003e3500\/61-05-CN\u003c\/strong\u003e is a full-height, six-channel instrumentation module designed to provide continuous temperature monitoring and precise proportional analog signaling within the \u003cstrong\u003e3500 Series Machinery Protection System\u003c\/strong\u003e. This specialized monitor accepts raw inputs from Resistance Temperature Detectors (RTD) and Thermocouples (TC), conditions the signals, and evaluates the data against user-programmable alert and danger alarm thresholds. Distinct from its companion module, this component provides independent +4 to +20 mA recorder outputs for each of its six channels, allowing seamless integration with external distributed control systems (DCS), strip chart recorders, or plant-wide data loggers. Operating within a standard 3500 rack frame, it supports field configuration via the 3500 Rack Configuration Software and accommodates non-isolated layouts with internal safety barriers to maintain loop integrity across diverse industrial machinery environments.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSix comprehensive temperature monitoring channels accepting mixed combinations of RTD and Thermocouple sensors.\u003c\/li\u003e\n\u003cli\u003eDedicated +4 to +20 mA analog recorder outputs per channel, proportional to full-scale monitor values and completely unbothered by external short circuits.\u003c\/li\u003e\n\u003cli\u003eIntegrated software-programmable Alert and Danger setpoints covering 0 to 100% of the active sensor scale.\u003c\/li\u003e\n\u003cli\u003eConfigurable alarm time delays adjustable from 1 to 60 seconds to mitigate transient signal trips.\u003c\/li\u003e\n\u003cli\u003eFront-panel diagnostic LEDs providing instant status evaluation for Module OK, Bypass Mode, and active TX\/RX communication bus traffic.\u003c\/li\u003e\n\u003cli\u003eSupport for non-isolated I\/O architectures featuring internal safety barriers to protect delicate processing loops.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eContinuous thermal tracking of industrial motor and generator stator windings.\u003c\/li\u003e\n\u003cli\u003eRadial and thrust bearing temperature monitoring on critical turbomachinery, pumps, and industrial compressors.\u003c\/li\u003e\n\u003cli\u003eExhaust gas temperature logging for gas turbines and heavy processing machinery.\u003c\/li\u003e\n\u003cli\u003eMulti-channel temperature voting logic integration for automated machinery trip systems.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eCategory\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eData\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eElectrical\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e9 watts nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eInput Signal Capacity\u003c\/td\u003e\n\u003ctd\u003e1 to 6 RTD or TC transducer signals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eInput Impedance\u003c\/td\u003e\n\u003ctd\u003e10 MOhm for each lead input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eRTD Current Source Value\u003c\/td\u003e\n\u003ctd\u003e925 +\/-15 microA @ 25 degC per transducer\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eRecorder Output Signal\u003c\/td\u003e\n\u003ctd\u003e+4 to +20 mA DC (proportional to full-scale)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eVoltage Compliance Range\u003c\/td\u003e\n\u003ctd\u003e0 to +12 Vdc across load\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eLoad Resistance Range\u003c\/td\u003e\n\u003ctd\u003e0 to 600 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eRecorder Resolution\u003c\/td\u003e\n\u003ctd\u003e0.3662 microA per bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eRecorder Error\u003c\/td\u003e\n\u003ctd\u003e+\/-0.15% at room temp, +\/-0.4% over temperature range\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePerformance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAlarm Setpoint Range\u003c\/td\u003e\n\u003ctd\u003eAdjustable from 0 to 100% of full-scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eAlarm Setpoint Accuracy\u003c\/td\u003e\n\u003ctd\u003eWithin 0.13% of the desired value\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eAlert Delay Intervals\u003c\/td\u003e\n\u003ctd\u003e1 to 60 seconds in 1 second intervals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eDanger Delay Intervals\u003c\/td\u003e\n\u003ctd\u003e1 to 60 seconds in 0.5 second intervals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eTemperature Resolution\u003c\/td\u003e\n\u003ctd\u003e1 degC or 1 degF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eEnvironmental\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eOperating Temperature (Internal Barriers)\u003c\/td\u003e\n\u003ctd\u003e0 degC to +65 degC (32 degF to +150 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eStorage Temperature Range\u003c\/td\u003e\n\u003ctd\u003e-40 degC to +85 degC (-40 degF to +185 degF)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eAmbient Operating Humidity\u003c\/td\u003e\n\u003ctd\u003e95%, non-condensing maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMechanical\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMonitor Module Dimensions (H x W x D)\u003c\/td\u003e\n\u003ctd\u003e241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x 9.52 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eMonitor Module Weight\u003c\/td\u003e\n\u003ctd\u003e0.91 kg (2.0 lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eI\/O Module with Internal Barriers (H x W x D)\u003c\/td\u003e\n\u003ctd\u003e241.3 mm x 24.4 mm x 163.1 mm (9.50 in x 0.96 in x 6.42 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eI\/O Module with Internal Barriers Weight\u003c\/td\u003e\n\u003ctd\u003e0.46 kg (1.01 lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eFront Rack Space Requirements\u003c\/td\u003e\n\u003ctd\u003e1 full-height front slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eRear Rack Space Requirements\u003c\/td\u003e\n\u003ctd\u003e1 full-height rear slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eBently Nevada\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eTerminal \/ Component Interface\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eFunction\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFront Panel OK LED\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIndicates when the Temperature Monitor is operating properly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFront Panel TX\/RX LED\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eFlashes to indicate active communication with other modules in the rack\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFront Panel Bypass LED\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIlluminates when the channel or monitor is placed into Bypass Mode\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRear I\/O Terminals\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDirect termination points for physical RTD and Thermocouple field wiring\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRecorder Output Interface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eParallel connections providing independent +4 to +20 mA diagnostic loops\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMain Card Insertion:\u003c\/strong\u003e Mount the primary monitor module into any available full-height slot positioned to the right of the Rack Interface Module.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eI\/O Module Positioning:\u003c\/strong\u003e Install the matching RTD\/TC non-isolated internal barrier I\/O module into the corresponding full-height rear slot directly behind the main front monitor.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCable Strain Relief:\u003c\/strong\u003e Route external sensor leads separately from noisy high-voltage distribution lines to eliminate electromotive interference across non-isolated circuits.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConfiguration Verification:\u003c\/strong\u003e Prior to plant operation, define precise sensor curves (alpha values) and scaling attributes within the 3500 Configuration Software utility.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eEMC Directives:\u003c\/strong\u003e 2014\/30\/EU.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEMC Standards:\u003c\/strong\u003e EN 61000-6-2 (Immunity for Industrial Environments), EN 61000-6-4 (Emissions for Industrial Environments), EN 55011 Class A.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eElectrical Safety:\u003c\/strong\u003e 2014\/35\/EU Low Voltage Directive; EN 61010-1.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHazardous Area Approvals (with Internal Barriers):\u003c\/strong\u003e CSA\/NRTL\/C Class I, Division 2, Groups A, B, C, and D (with IS Output for Division 1); Class I, Zone 2: AEx\/Ex nA nC ic [ia Ga] IIC T4 Gc or AEx\/Ex ec nC ic [ia Ga] IIC T4 Gc.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eATEX\/IECEx (with Internal Barriers):\u003c\/strong\u003e Ex II 3(1) G; Ex nA nC ic [ia Ga] IIC T4 Gc or Ex ec nC ic [ia Ga] IIC T4 Gc at Ta = -20 degC to +65 degC.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFunctional Safety:\u003c\/strong\u003e Designed to meet SIL 2 requirements.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Bently Nevada","offers":[{"title":"Default Title","offer_id":52668299379051,"sku":"3500\/61-05-CN","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/3500-61-05-CN-cfhoqahh0w4_028b5b49-848f-4c41-80b1-1f94bb49297c.jpg?v=1765520500","url":"https:\/\/www.plcprotech.com\/products\/bently-nevada-3500-61-05-cn-3500-61-temperature-module-with-recorder-outputs","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}