{"product_id":"general-electric-ic693mdl310-series-90-30-120-vac-0-5-a-12-point-ac-output-module","title":"General Electric IC693MDL310 Series 90-30 120 VAC 0.5 A 12-Point AC Output Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe General Electric IC693MDL310 is a 120 VAC, 0.5 Amp discrete solid-state AC output module designed for the GE Fanuc Series 90-30 programmable logic controller system. It provides 12 output circuits organized into two isolated groups of six points each. Because each group incorporates an independent common connection that is electrically separated from the other inside the module, the groups can operate on distinct phases of an AC power source or draw from a single shared supply.\u003c\/p\u003e\n\u003cp\u003eEach output circuit integrates an RC snubber network to suppress power line transient noise and voltage spikes. The module provides high inrush current tolerance rated at up to 10 times continuous load current (5 Amps peak for one AC cycle), allowing direct operation of inductive and incandescent loads such as contactors, motor starters, indicator lamps, and solenoids. Field power to energize output loads must be provided externally by the user.\u003c\/p\u003e\n\u003cp\u003eThe IC693MDL310 installs into any standard I\/O slot of a 5-slot or 10-slot Series 90-30 baseplate, including CPU baseplates, expansion baseplates, and remote baseplates. The hinged faceplate door contains an insert card that provides internal terminal wiring diagrams on the reverse side and user identification labeling on the outer surface, bordered by a red edge to designate high-voltage AC field wiring.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003e12 solid-state AC outputs partitioned into two isolated groups of 6 circuits each.\u003c\/li\u003e\n  \u003cli\u003eIndependent common terminals per group allowing connection to separate AC supply phases.\u003c\/li\u003e\n  \u003cli\u003eIndividual RC snubber suppression on each output point for transient protection.\u003c\/li\u003e\n  \u003cli\u003eHigh inrush capability rated at 5 Amps for one line cycle to drive inductive loads.\u003c\/li\u003e\n  \u003cli\u003eIndividual 3 Amp protection fuse per group.\u003c\/li\u003e\n  \u003cli\u003eFront-panel LED diagnostics featuring 12 green status indicators and 1 red blown-fuse indicator.\u003c\/li\u003e\n  \u003cli\u003eHinged front door with high-voltage red color code and terminal assignment reference.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003cthead\u003e\n    \u003ctr\u003e\n      \u003cth\u003eParameter\u003c\/th\u003e\n      \u003cth\u003eSpecification\u003c\/th\u003e\n    \u003c\/tr\u003e\n  \u003c\/thead\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eModule Type\u003c\/td\u003e\n      \u003ctd\u003eDiscrete AC Output Module\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003ePLC Platform\u003c\/td\u003e\n      \u003ctd\u003eSeries 90-30\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eNumber of Output Points\u003c\/td\u003e\n      \u003ctd\u003e12 points (2 isolated groups of 6 points)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eRated Voltage\u003c\/td\u003e\n      \u003ctd\u003e120 VAC\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eOutput Voltage Range\u003c\/td\u003e\n      \u003ctd\u003e85 to 132 VAC, 50\/60 Hz\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eOutput Current per Point\u003c\/td\u003e\n      \u003ctd\u003e0.5 A maximum\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eOutput Current per Group\u003c\/td\u003e\n      \u003ctd\u003e1.0 A maximum at 60 degC (140 degF); 2.0 A maximum at 50 degC (122 degF)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMaximum Inrush Current\u003c\/td\u003e\n      \u003ctd\u003e5.0 A for one cycle\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMinimum Load Current\u003c\/td\u003e\n      \u003ctd\u003e50 mA\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMaximum Voltage Drop\u003c\/td\u003e\n      \u003ctd\u003e1.5 V at 0.5 A load\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMaximum Output Leakage Current\u003c\/td\u003e\n      \u003ctd\u003e3 mA at 120 VAC\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eTurn-On Response Time\u003c\/td\u003e\n      \u003ctd\u003e1 ms maximum\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eTurn-Off Response Time\u003c\/td\u003e\n      \u003ctd\u003e1\/2 cycle maximum\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eIsolation: Field to Logic\u003c\/td\u003e\n      \u003ctd\u003e1500 VAC\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eIsolation: Group to Group\u003c\/td\u003e\n      \u003ctd\u003e500 VAC\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eInternal Bus Current Draw\u003c\/td\u003e\n      \u003ctd\u003e210 mA from +5 VDC bus (all outputs ON)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eInternal Group Fusing\u003c\/td\u003e\n      \u003ctd\u003e3 A fuse per group (2 fuses total)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eStatus Indicators\u003c\/td\u003e\n      \u003ctd\u003e12 green logic LEDs (A1-A6, B1-B6); 1 red fuse blown LED (F)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eFaceplate Color Band\u003c\/td\u003e\n      \u003ctd\u003eRed (High Voltage)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eBaseplate Compatibility\u003c\/td\u003e\n      \u003ctd\u003eAny I\/O slot in Series 90-30 5-slot or 10-slot baseplates\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003ctr\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eInstallation and Wiring Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eTurn off power to the baseplate and field circuits prior to inserting or removing the module or servicing fuses.\u003c\/li\u003e\n  \u003cli\u003eEnsure field AC power is routed through appropriate external disconnects, as the module does not supply output power from the backplane.\u003c\/li\u003e\n  \u003cli\u003eGroup 1 uses points A1 through A6, while Group 2 uses points B1 through B6; do not bridge the respective commons if groups operate on differing AC phases.\u003c\/li\u003e\n  \u003cli\u003eRoute high-voltage AC field wiring separately from low-voltage DC communication and analog signal cables to minimize inductive coupling.\u003c\/li\u003e\n  \u003cli\u003eInspect the red \"F\" LED indicator during runtime to quickly identify an open fuse condition in either group.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":53770186817899,"sku":"IC693MDL310","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/ic693mdl310_1200x1200_3a383da0-a7a0-4c7c-87e6-6139e2bbc648.jpg?v=1787737936","url":"https:\/\/www.plcprotech.com\/products\/general-electric-ic693mdl310-series-90-30-120-vac-0-5-a-12-point-ac-output-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}