{"product_id":"general-electric-is200vvibh1cac-mark-vi-vibration-monitor-board","title":"General Electric IS200VVIBH1CAC Mark VI Vibration Monitor Board","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIS200VVIBH1CAC\u003c\/strong\u003e is a dedicated vibration monitor board engineered for the Mark VI control system. This module processes incoming analog signals received from up to 14 Bently Nevada proximity probes connected via the TVIB terminal board, enabling precise shaft vibration monitoring in critical machinery. The board digitizes these vibration signatures using high-resolution analog-to-digital conversion and transmits the processed data directly across a VME bus to the main controller for continuous diagnostics and system logic execution. Built using surface mount technology, it supports expandable architectures where multiple terminal boards or redundant pairs can interface with a single processing unit, ensuring uninterrupted signal availability. Additionally, the \u003cstrong\u003eIS200VVIBH1CAC\u003c\/strong\u003e features a dedicated generator breaker coil output rated at 5A at 125 V dc to facilitate protective tripping sequences.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInterfaces with up to 14 Bently Nevada proximity probes for full shaft vibration diagnostics.\u003c\/li\u003e\n\u003cli\u003eConverts incoming analog signals using a high-precision 16-bit analog-to-digital converter.\u003c\/li\u003e\n\u003cli\u003eTransmits real-time digitized parameters over a high-speed VME bus architecture.\u003c\/li\u003e\n\u003cli\u003eSupports dual terminal board configurations to ensure system redundancy and fallback capability.\u003c\/li\u003e\n\u003cli\u003eOffers dual-rate sampling configurations automatically adjusted based on machine RPM thresholds.\u003c\/li\u003e\n\u003cli\u003eOutputs buffered signals with high amplitude accuracy to external machinery analysis systems.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eGas turbine shaft vibration monitoring\u003c\/li\u003e\n\u003cli\u003eSteam turbine proximity and position measurement\u003c\/li\u003e\n\u003cli\u003eGenerator breaker control systems\u003c\/li\u003e\n\u003cli\u003eIndustrial rotating machinery protection\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eValue\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePart Number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIS200VVIBH1CAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMark VI\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eVibration Monitor Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTechnology\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eSurface mount\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-30 to 65 Celsius\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eDimensions\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e33.0 cm high x 17.8 cm wide\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 Generator breaker coil\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Rating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5A at 125 V dc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Supply Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNominal 125 V dc to breaker coil\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMPU Pulse Rate Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2 Hz to 20 kHz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMPU Pulse Rate Accuracy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.05 percent of reading\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTransducer Supply Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e-24 V dc (derived from -28 V dc bus)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTransducer Current Limit\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 mA maximum load per transducer\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eA\/D Conversion Resolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16-bit converter with 14-bit resolution\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSampling Rate (RPM \u0026gt;= 4000)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4,600 samples per second (Fast scan mode)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSampling Rate (RPM \u0026lt; 4000)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e2,586 samples per second (with 9 or more probes)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSimultaneous Sampling Window\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e160 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBuffered Output Accuracy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1 percent amplitude accuracy\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCountry of Manufacture\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUnited States of America (USA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003ePower down the VME processor rack completely before attempting insertion or removal to prevent electrical hazards.\u003c\/li\u003e\n\u003cli\u003eAlign the module with the designated guide rails and carefully slide the board into the slot within the VME rack.\u003c\/li\u003e\n\u003cli\u003eSeat the edge connectors firmly by pushing the top and bottom front panel levers inward simultaneously.\u003c\/li\u003e\n\u003cli\u003eTighten the captive screws located at the top and bottom of the front faceplate to fix the module securely in place.\u003c\/li\u003e\n\u003cli\u003eVerify all cable connections and visually inspect alignment before re-powering the VME processor rack.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":52695413227883,"sku":"IS200VVIBH1CAC","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/general-electric-is200vvibh1cac-vibration-monitor-board-ll45mxst1xr_2a3b7651-aff4-40f7-84ce-445b50eee79d.jpg?v=1766135142","url":"https:\/\/www.plcprotech.com\/products\/general-electric-is200vvibh1cac-mark-vi-vibration-monitor-board","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}