{"product_id":"hima-f6217-8-channel-analog-input-module","title":"HIMA F6217 8-Channel Analog Input Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eHIMA F 6217 (F6217)\u003c\/strong\u003e is a safety-related 8-channel analog input module designed for safety-critical industrial applications up to SIL 3 according to IEC 61508. The \u003cstrong\u003eHIMA F 6217\u003c\/strong\u003e features a redundant, safety-related processor system containing microcontrollers uC1, uC2, and uC3 to execute integrated self-tests directly on the module. Built with safe isolation, the module processes standard current inputs (0\/4...20 mA) and voltage inputs (0...5\/10 V) with a 12-bit resolution. Internal test routines continuously evaluate A\/D converter linearity, A\/D converter overflow, channel crosstalk, input filter functionality, and I\/O bus communication. Recognized errors generate individual channel bit faults that are interpreted and evaluated within the user program in ELOP II.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e8 analog input channels with safe isolation\u003c\/li\u003e\n\u003cli\u003eRedundant, safety-related microcontroller structure (uC1, uC2, and uC3)\u003c\/li\u003e\n\u003cli\u003eContinuous internal self-testing of A\/D converters, memories, input filters, and I\/O bus communication\u003c\/li\u003e\n\u003cli\u003eApplicable in safety-related systems up to SIL 3 in accordance with IEC 61508\u003c\/li\u003e\n\u003cli\u003eSupport for redundant current or voltage connections and transmitter supplies\u003c\/li\u003e\n\u003cli\u003eTime constant input filter of approximately 10 ms for signal processing\u003c\/li\u003e\n\u003cli\u003eIndividual channel bit fault detection for safety program evaluation in ELOP II\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSafety Instrumented Systems (SIS) requiring up to SIL 3 certification\u003c\/li\u003e\n\u003cli\u003eEmergency Shutdown Systems (ESD)\u003c\/li\u003e\n\u003cli\u003eIndustrial process control and monitoring\u003c\/li\u003e\n\u003cli\u003eCurrent loop and voltage transmitter signal acquisition\u003c\/li\u003e\n\u003cli\u003eHigh-availability redundant analog measurement loops\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eHIMA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eF 6217 (F6217)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Channels\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e8 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSafety Standard\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eApplicable up to SIL 3 according to IEC 61508\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eResolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e12 bits (0 mV = 0, 5.5 V = 4095)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Voltage Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0...5.5 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum Input Voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e7.5 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Current Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0...22 mA (via shunt), 22 mA = 4095\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum Input Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e30 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eShunt Resistor (Current Input)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e250 Ohm; 0.05%; 0.25 W; T \u0026lt; 10 ppm\/K; Part No.: 00 0710251\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMeasurand Update\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e50 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSafety Time\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u0026lt; 450 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Resistance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100 kOhm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTime Constant Input Filter\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eapprox. 10 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBasic Error\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.1% at 25 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Error\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.3% at 0...+60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eError Limit Related on Safety\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1%\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eElectric Strength\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e200 V against GND\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSpace Requirement\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 SU\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating Data\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e5 VDC \/ 80 mA, 24 VDC \/ 50 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003ch4\u003eLead Marking for Cable Plug Z 7127\/6217\/C..\/I (U5V) \u0026amp; Z 7127\/6217\/C..\/U10V\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eChannel\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eConnection\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eColor\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e1\u003c\/td\u003e\n\u003ctd\u003ez4, x4, d4\u003c\/td\u003e\n\u003ctd\u003eBN, WH\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003ctd\u003ez8, x8, d8\u003c\/td\u003e\n\u003ctd\u003eYE, GN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3\u003c\/td\u003e\n\u003ctd\u003ez12, x12, d12\u003c\/td\u003e\n\u003ctd\u003ePK, GY\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003ctd\u003ez16, x16, d16\u003c\/td\u003e\n\u003ctd\u003eRD, BU\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5\u003c\/td\u003e\n\u003ctd\u003ez20, x20, d20\u003c\/td\u003e\n\u003ctd\u003eVT, BK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e6\u003c\/td\u003e\n\u003ctd\u003ez24, x24, d24\u003c\/td\u003e\n\u003ctd\u003eWHGN, WHBN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e7\u003c\/td\u003e\n\u003ctd\u003ez28, x28, d28\u003c\/td\u003e\n\u003ctd\u003eWHGY, WHYE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003ctd\u003ez32, x32, d32\u003c\/td\u003e\n\u003ctd\u003eWHBU, WHPK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eL-\u003c\/td\u003e\n\u003ctd\u003ed26\u003c\/td\u003e\n\u003ctd\u003eBK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eL+\u003c\/td\u003e\n\u003ctd\u003ed30\u003c\/td\u003e\n\u003ctd\u003eRD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCable Screen\u003c\/td\u003e\n\u003ctd\u003e-\u003c\/td\u003e\n\u003ctd\u003eYEGN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch4\u003eLead Marking for Cable Plug with Transmitter Supply Z 7128\/6217\/C..\/ITI\u003c\/h4\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eChannel\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eConnection\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eColor\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e1\u003c\/td\u003e\n\u003ctd\u003ez4, x4, d4\u003c\/td\u003e\n\u003ctd\u003eBN, WH, GN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003ctd\u003ez8, x8, d8\u003c\/td\u003e\n\u003ctd\u003eGY, YE, PK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e3\u003c\/td\u003e\n\u003ctd\u003ez12, x12, d12\u003c\/td\u003e\n\u003ctd\u003eRD, BU, BK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003ctd\u003ez16, x16, d16\u003c\/td\u003e\n\u003ctd\u003eWHBN, VT, WHGN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e5\u003c\/td\u003e\n\u003ctd\u003ez20, x20, d20\u003c\/td\u003e\n\u003ctd\u003eWHGY, WHYE, WHPK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e6\u003c\/td\u003e\n\u003ctd\u003ez24, x24, d24\u003c\/td\u003e\n\u003ctd\u003eWHRD, WHBU, WHBK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e7\u003c\/td\u003e\n\u003ctd\u003ez28, x28, d28\u003c\/td\u003e\n\u003ctd\u003eBNYE, BNGN, BNGY\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003ctd\u003ez32, x32, d32\u003c\/td\u003e\n\u003ctd\u003eBNBU, BNPK, BNRD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eL-\u003c\/td\u003e\n\u003ctd\u003ed26\u003c\/td\u003e\n\u003ctd\u003eBK\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eL+\u003c\/td\u003e\n\u003ctd\u003ed30\u003c\/td\u003e\n\u003ctd\u003eRD\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCable Screen\u003c\/td\u003e\n\u003ctd\u003e-\u003c\/td\u003e\n\u003ctd\u003eYEGN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eShielding \u0026amp; Cabling:\u003c\/strong\u003e Screened cables must be used for field input circuits, and twisted cables are recommended to achieve full interference immunity. Cabling without screening is only acceptable if the transmitter environment is free from interference and distances are relatively short (e.g., inside a cabinet).\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Supply Separation:\u003c\/strong\u003e Cables for the power supply must be locally separated from field input circuits.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eGrounding:\u003c\/strong\u003e Suitable earthing measures must be strictly applied. Flat pin plug 6.3 x 0.8 mm2 on cable screen connections must be attached to the earth bar located under the slot.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCooling \u0026amp; Temperature:\u003c\/strong\u003e External measures against temperature rises inside cabinets (e.g., installing cabinet cooling fans) must be provided.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eUnused Inputs:\u003c\/strong\u003e Terminate unused 0...5 V voltage inputs using jumpers. Terminate unused current inputs with the shunt, and unused 0...10 V voltage inputs with the voltage divider in the cable connector.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLow-Frequency Interference:\u003c\/strong\u003e In environments subject to ~10 Hz external pressure pulses (such as near piston pumps), enable sensor digital filtering or implement an optional H 7017 low-pass filter to prevent temporary channel bit faults.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSpecial Transmitter Isolation:\u003c\/strong\u003e If using transmitters with internal Zener diodes (e.g., Saab\/Rosemount 3300 GWR), galvanic isolation (e.g., HIMA H 6200 HART isolator) must be implemented in the signal line. Note that cable plug Z 7128 must not be used with Zener barriers.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaintenance:\u003c\/strong\u003e No routine maintenance is required. In the event of a module failure, the device de-energizes and must be replaced.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eIEC 61508 SIL 3\u003c\/li\u003e\n\u003cli\u003eCE\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"HIMA","offers":[{"title":"Default Title","offer_id":52695382720875,"sku":"F6217","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/hima-f6217-8-channel-analog-input-module-ggskgxjo5aj_1c524ed8-2e1a-4ce2-8900-42d1f4256580.jpg?v=1766132500","url":"https:\/\/www.plcprotech.com\/products\/hima-f6217-8-channel-analog-input-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}