{"product_id":"honeywell-80363975-150-mc-pdoy22-digital-output-module","title":"Honeywell 80363975-150 MC-PDOY22 Digital Output Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp style=\"color: #2d3748; margin-bottom: 1rem;\"\u003eFacilitating robust discrete signal transmission in industrial process control environments, the Honeywell 80363975-150 serves as a high-density MC-PDOY22 digital output card designed for Honeywell TDC 3000 and High-Performance Process Manager (HPM) architectures. This digital output processor controls up to \u003cstrong\u003e32 discrete outputs\u003c\/strong\u003e, interfacing the central control system with field solenoids, relays, indicators, and motor starters. Engineered for high-reliability process automation, the Honeywell 80363975-150 routes logic signals directly to Field Termination Assemblies (FTAs) to manage varying load ranges safely and efficiently.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul style=\"list-style-type: square; color: #2d3748; margin-bottom: 1.5rem; padding-left: 1.5rem;\"\u003e\n  \u003cli\u003e\n\u003cstrong\u003e32-Channel Output Density:\u003c\/strong\u003e Maximizes rack space efficiency within the High-Performance Process Manager card file.\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eDual-FTA Compatibility:\u003c\/strong\u003e Supports low-voltage DC applications as well as high-voltage AC\/DC switching environments using standard FTAs.\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eConformal Coating:\u003c\/strong\u003e Designed to withstand harsh, corrosive industrial atmospheres typical of petrochemical and power generation facilities.\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eHigh-Speed Signal Processing:\u003c\/strong\u003e Delivers rapid response times for critical safety interlocks and discrete control logic.\u003c\/li\u003e\n  \u003cli\u003e\n\u003cstrong\u003eRedundancy Support:\u003c\/strong\u003e Integrates seamlessly with redundant IOP pairs to ensure continuous operation in high-availability environments.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul style=\"list-style-type: square; color: #2d3748; margin-bottom: 1.5rem; padding-left: 1.5rem;\"\u003e\n  \u003cli\u003ePetrochemical and refining control loops.\u003c\/li\u003e\n  \u003cli\u003ePower plant burner management and auxiliary system sequencing.\u003c\/li\u003e\n  \u003cli\u003eDiscrete actuator control in pulp and paper manufacturing lines.\u003c\/li\u003e\n  \u003cli\u003eHazardous-area discrete logic switching and alarm annunciator panels.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eTechnical Specifications Table\u003c\/h3\u003e\n\u003cdiv style=\"overflow-x: auto; width: 100%; margin-bottom: 1.5rem;\"\u003e\n  \u003ctable style=\"border-collapse: collapse; width: 100%; color: #2d3748; border: 1px solid #e2e8f0;\"\u003e\n    \u003cthead\u003e\n      \u003ctr style=\"border-bottom: 2px solid #cbd5e0;\"\u003e\n        \u003cth style=\"padding: 10px; text-align: left; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eSpecification Parameter\u003c\/th\u003e\n        \u003cth style=\"padding: 10px; text-align: left; font-weight: bold;\"\u003eValue \/ Rating\u003c\/th\u003e\n      \u003c\/tr\u003e\n    \u003c\/thead\u003e\n    \u003ctbody\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eManufacturer\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003eHoneywell\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003ePart Number \/ SKU\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003e80363975-150\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eModel Code\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003eMC-PDOY22\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eI\/O Processor Type\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003eDigital Output (DO) 32-Channel Processor\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eLoad Voltage Range (FTA OY22\/62)\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003e15 to 30 Vdc\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eLoad Voltage Max (FTA OY23\/63)\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003e250 Vac \/ 125 Vdc (Requires 2 FTAs for 32 outputs)\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eSystem Compatibility\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003eHoneywell TDC 3000 \/ HPM \/ APM systems\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003eShipping Weight (Calculated)\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003e1.50 kg\u003c\/td\u003e\n      \u003c\/tr\u003e\n      \u003ctr style=\"border-bottom: 1px solid #e2e8f0;\"\u003e\n        \u003ctd style=\"padding: 10px; font-weight: bold; border-right: 1px solid #e2e8f0;\"\u003ePackage Dimensions (Calculated)\u003c\/td\u003e\n        \u003ctd style=\"padding: 10px;\"\u003e31.5 cm x 24.0 cm x 5.5 cm\u003c\/td\u003e\n      \u003c\/tr\u003e\n    \u003c\/tbody\u003e\n  \u003c\/table\u003e\n\u003c\/div\u003e\n\n\u003ch3\u003eEmpirical Engineering Insights\u003c\/h3\u003e\n\n\u003ch3\u003eAlternative Models \u0026amp; Compatibility\u003c\/h3\u003e\n\u003cp style=\"color: #2d3748; margin-bottom: 1rem;\"\u003eThe MC-PDOY22 is the direct conformal-coated alternative to older non-coated MU-PDOY22 modules. It functions seamlessly within any standard PM, APM, or HPM I\/O card file slot. When replacing an older revision, verify that the existing 50-pin control bus cables (MU-KDOYxx) match the physical socket constraints of the updated Honeywell 80363975-150 model.\u003c\/p\u003e\n\n\u003ch3\u003eApplication Pitfalls \u0026amp; Engineering Notes\u003c\/h3\u003e\n\u003cp style=\"color: #2d3748; margin-bottom: 1rem;\"\u003eWhen deploying the MC-PDOY22 with high-voltage AC\/DC loads via FTA OY23 or OY63, plant engineers must note that two discrete FTAs are required to fully implement all 32 output channels. Utilizing a single FTA limits addressable outputs to 16. Ensure that the total current draw per output group does not violate the thermal and backplane constraints of the HPM node power supply, especially inside sealed, non-ventilated cabinets.\u003c\/p\u003e\n\n\u003ch3\u003eCommissioning \u0026amp; Wiring Tips\u003c\/h3\u003e\n\u003cp style=\"color: #2d3748; margin-bottom: 1.5rem;\"\u003eDuring commissioning, verify the structural integrity of the field cable shielding. Run discrete DO signal lines away from high-power variable frequency drives (VFDs) and motor supply cables to prevent inductive noise injection. Always execute an I\/O loop check from the control system console to confirm exact contact-state transitions on the corresponding FTA terminals before putting the loops into auto-control mode.\u003c\/p\u003e\n\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cdiv style=\"background-color: #fff5f5; border-left: 4px solid #c53030; padding: 1rem; margin-bottom: 1.5rem; color: #9b2c2c;\"\u003e\n  \u003cstrong\u003eCRITICAL WARNING:\u003c\/strong\u003e Hazardous voltages may be present on the field termination assemblies linked to this module. Disconnect all primary process power and field-side load voltages before attempting to extract or insert the MC-PDOY22 card. Strictly adhere to standard electrostatic discharge (ESD) safety protocols to prevent catastrophic gate driver damage.\n\u003c\/div\u003e\n\n\u003cdiv style=\"display: flex; flex-direction: column; gap: 1rem; margin-bottom: 1.5rem;\"\u003e\n  \u003cdiv style=\"display: flex; align-items: flex-start; gap: 1rem;\"\u003e\n    \u003cdiv style=\"background-color: #2b6cb0; color: #ffffff; border-radius: 50%; min-width: 28px; min-height: 28px; display: flex; align-items: center; justify-content: center; font-weight: bold;\"\u003e1\u003c\/div\u003e\n    \u003cdiv style=\"color: #2d3748; padding-top: 2px;\"\u003eEnsure the HPM card file slot matches the address configured in the control system database. Verify that the plastic physical keying pins on the card chassis align with the card file.\u003c\/div\u003e\n  \u003c\/div\u003e\n  \u003cdiv style=\"display: flex; align-items: flex-start; gap: 1rem;\"\u003e\n    \u003cdiv style=\"background-color: #2b6cb0; color: #ffffff; border-radius: 50%; min-width: 28px; min-height: 28px; display: flex; align-items: center; justify-content: center; font-weight: bold;\"\u003e2\u003c\/div\u003e\n    \u003cdiv style=\"color: #2d3748; padding-top: 2px;\"\u003eCarefully slide the MC-PDOY22 module into the card guide tracks until the rear edge connectors are firmly engaged with the chassis backplane.\u003c\/div\u003e\n  \u003c\/div\u003e\n  \u003cdiv style=\"display: flex; align-items: flex-start; gap: 1rem;\"\u003e\n    \u003cdiv style=\"background-color: #2b6cb0; color: #ffffff; border-radius: 50%; min-width: 28px; min-height: 28px; display: flex; align-items: center; justify-content: center; font-weight: bold;\"\u003e3\u003c\/div\u003e\n    \u003cdiv style=\"color: #2d3748; padding-top: 2px;\"\u003eDepress the top and bottom extraction levers to secure the card in place. Screw in any retention hardware if applicable to prevent movement caused by plant floor vibration.\u003c\/div\u003e\n  \u003c\/div\u003e\n  \u003cdiv style=\"display: flex; align-items: flex-start; gap: 1rem;\"\u003e\n    \u003cdiv style=\"background-color: #2b6cb0; color: #ffffff; border-radius: 50%; min-width: 28px; min-height: 28px; display: flex; align-items: center; justify-content: center; font-weight: bold;\"\u003e4\u003c\/div\u003e\n    \u003cdiv style=\"color: #2d3748; padding-top: 2px;\"\u003eConnect the 50-pin I\/O link cable extending from the matching FTA, ensuring the latching clips lock firmly onto the header of the MC-PDOY22 card.\u003c\/div\u003e\n  \u003c\/div\u003e\n\u003c\/div\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52705556169067,"sku":"80363975-150","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/80363975-150-tkts5xsiuol_85a3047f-f4d7-42f1-a50e-b5c647f1b896.jpg?v=1766649633","url":"https:\/\/www.plcprotech.com\/products\/honeywell-80363975-150-mc-pdoy22-digital-output-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}