{"product_id":"honeywell-cc-paoh51-51410070-275-experion-pks-analog-output-module","title":"Honeywell CC-PAOH51 51410070-275 Experion PKS Analog Output Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe Honeywell CC-PAOH51 (part number 51410070-275) is a high-performance analog output module engineered specifically for the Honeywell Experion Process Knowledge System (PKS) platform. Operating as part of the Series C hardware architecture, this module provides reliable conversion of controller digital values into precise analog control signals for industrial actuators, control valves, and positioners. It is deployed in continuous process industries to maintain closed-loop control integrity across critical plant units.\u003c\/p\u003e\n\u003cp\u003eThis 16-channel analog output module features built-in HART communication protocol support, enabling bi-directional digital communication with smart field instruments simultaneously with the 4 to 20 mA analog signal. The module incorporates extensive diagnostic capabilities, channel-to-channel isolation, and output readback verification to ensure uninterrupted process operation and rapid fault detection within safety and regulatory frameworks.\u003c\/p\u003e\n\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eProvides 16 isolated analog output channels supporting standard 4 to 20 mA control signals.\u003c\/li\u003e\n  \u003cli\u003eIntegrated HART protocol multiplexing for digital configuration, calibration, and diagnostics of smart field devices.\u003c\/li\u003e\n  \u003cli\u003eDirectly settable output current ranges from 0 mA or 2.9 mA up to 21.1 mA to support custom fail-safe states.\u003c\/li\u003e\n  \u003cli\u003eHigh-accuracy output readback of plus or minus 0.04 percent of full scale with a resolution of plus or minus 0.005 percent.\u003c\/li\u003e\n  \u003cli\u003eLow temperature drift coefficient ensuring long-term operational stability in harsh industrial environments.\u003c\/li\u003e\n  \u003cli\u003eSeries C form factor designed for direct DIN-rail mounting and simplified I\/O termination assembly.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n  \u003cli\u003eOil and gas upstream production and downstream refining process loops.\u003c\/li\u003e\n  \u003cli\u003eChemical and petrochemical distillation, reaction, and blending control.\u003c\/li\u003e\n  \u003cli\u003ePower generation boiler control and feedwater regulation systems.\u003c\/li\u003e\n  \u003cli\u003eWater and wastewater treatment plant flow and chemical dosing control.\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003cthead\u003e\n    \u003ctr\u003e\n      \u003cth\u003eParameter\u003c\/th\u003e\n      \u003cth\u003eSpecification\u003c\/th\u003e\n    \u003c\/tr\u003e\n  \u003c\/thead\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eManufacturer\u003c\/td\u003e\n      \u003ctd\u003eHoneywell\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eProduct Series\u003c\/td\u003e\n      \u003ctd\u003eExperion PKS (Series C)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eModel \/ Part Number\u003c\/td\u003e\n      \u003ctd\u003eCC-PAOH51 \/ 51410070-275\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eModule Type\u003c\/td\u003e\n      \u003ctd\u003eAnalog Output Module with HART\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eNumber of Channels\u003c\/td\u003e\n      \u003ctd\u003e16 channels\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eOutput Signal Range\u003c\/td\u003e\n      \u003ctd\u003e4 to 20 mA standard (configurable 0 to 21.1 mA)\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eHART Compatibility\u003c\/td\u003e\n      \u003ctd\u003eHART protocol supported on all channels\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eMaximum Resistive Load\u003c\/td\u003e\n      \u003ctd\u003e800 ohms at 20 mA\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eOpen Circuit Voltage\u003c\/td\u003e\n      \u003ctd\u003e22 V maximum\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eResolution\u003c\/td\u003e\n      \u003ctd\u003eplus or minus 0.005 percent of full scale\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eReadback Accuracy\u003c\/td\u003e\n      \u003ctd\u003eplus or minus 0.04 percent of full scale\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eCountry of Origin\u003c\/td\u003e\n      \u003ctd\u003eUnited States\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eDimensions\u003c\/td\u003e\n      \u003ctd\u003e5.5 x 16.2 x 14.5 cm\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eNet Weight\u003c\/td\u003e\n      \u003ctd\u003e0.3 kg\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eConnections \/ Interfaces\u003c\/h3\u003e\n\u003ctable\u003e\n  \u003cthead\u003e\n    \u003ctr\u003e\n      \u003cth\u003eInterface\u003c\/th\u003e\n      \u003cth\u003eFunction\u003c\/th\u003e\n    \u003c\/tr\u003e\n  \u003c\/thead\u003e\n  \u003ctbody\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eSeries C I\/O Terminal Block\u003c\/td\u003e\n      \u003ctd\u003eField wiring connection for 16 analog output loops and HART communication.\u003c\/td\u003e\n    \u003c\/tr\u003e\n    \u003ctr\u003e\n      \u003ctd\u003eI\/O Module Backplane Connector\u003c\/td\u003e\n      \u003ctd\u003ePower distribution and high-speed data communication with the Series C controller or I\/O Gateway.\u003c\/td\u003e\n    \u003c\/tr\u003e\n  \u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003col\u003e\n  \u003cli\u003eVerify that the part number CC-PAOH51 (51410070-275) matches system engineering documentation before installation.\u003c\/li\u003e\n  \u003cli\u003eEnsure all power to the target Series C I\/O slot and associated field wiring terminal blocks is de-energized.\u003c\/li\u003e\n  \u003cli\u003eInspect the module and terminal base for any transit damage or bent connector pins.\u003c\/li\u003e\n  \u003cli\u003eMount the Series C I\/O module securely onto the designated DIN rail or carrier assembly.\u003c\/li\u003e\n  \u003cli\u003eConnect the field loop wiring to the corresponding terminal blocks according to the loop diagrams.\u003c\/li\u003e\n  \u003cli\u003eApply system power and configure the channel parameters using the Experion PKS Control Builder software.\u003c\/li\u003e\n\u003c\/ol\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52667989688683,"sku":"CC-PAOH51 51410070-275","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/honeywell-cc-paoh51-51410070-275-analog-output-module-ua2gv4vttda_b4d90f4a-6d2f-4671-956b-afa60acdad3f.jpg?v=1765504882","url":"https:\/\/www.plcprotech.com\/products\/honeywell-cc-paoh51-51410070-275-experion-pks-analog-output-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}