{"product_id":"honeywell-tc-odd321-experion-dc-output-module","title":"Honeywell TC-ODD321 Experion DC Output Module","description":"\u003cp\u003eThe \u003cstrong\u003eHoneywell TC-ODD321\u003c\/strong\u003e is a 24 VDC digital output module for the Experion chassis I\/O platform. It features 32 non-isolated output channels configured into two groups with 16 points per common ground. Designed to drive field devices such as solenoids, relays, and indicators, the device processes digital control signals from Experion C200\/C200E controllers with fast, solid-state response.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003e32 Output Points\u003c\/strong\u003e: Arranged into 2 distinct groups with 16 points per common connection.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLinear Derating\u003c\/strong\u003e: Supports full current loads up to 50 degC with controlled linear thermal derating up to 60 degC.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFast Switching Response\u003c\/strong\u003e: On\/off signal delay times are capped at 1.0 ms maximum.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConfigurable Channel States\u003c\/strong\u003e: Individual channels can be configured to hold their last state or default to ON or OFF during fault conditions or program mode.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHot-Swappable Operation\u003c\/strong\u003e: Supports Removal and Insertion Under Power (RIUP) in non-hazardous area installations.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eDriving 24 VDC industrial solenoids and actuator coils\u003c\/li\u003e\n\u003cli\u003eOperating interposing control relays and contactors\u003c\/li\u003e\n\u003cli\u003eControlling field indicator lights and annunciator panels\u003c\/li\u003e\n\u003cli\u003eInterface automation outputs to external subsystem logic\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTC-ODD321\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eDiscrete Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eNumber of Outputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e32 (16 points\/common)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Voltage Range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e10 to 31.2 VDC @ 50 degC (Linear derating), 10 to 28 VDC @ 60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Current Rating (Per Point)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.5 A max @ 50 degC (Linear derating), 0.35 A max @ 60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Current Rating (Per Module)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16 A max @ 50 degC (Linear derating), 10 A max @ 60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSurge Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 A for 10 ms each, repeatable every 2 s @ 60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMinimum On-State Load Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.0 mA per output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum On-State Voltage Drop\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1 VDC @ rated current per point (3 VDC for IEC 1131-2)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMaximum Off-State Leakage Current\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e0.5 mA per point (1 mA per point IEC 1131-2 for 0.25 A output)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOutput Delay Time (Off-to-On \/ On-to-Off)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e1.0 ms maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower Dissipation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e6.1 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFusing Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNot protected (Fused terminal block\/IFM recommended)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eReverse Polarity Protection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNone (Wiring incorrectly may damage module)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIsolation Voltage (Group to Group)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100% tested at 2546 VDC for 1 s (250 VAC max continuous)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIsolation Voltage (User to System)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e100% tested at 2546 VDC for 1 s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTerminal Block Connector\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTC-TBCH (36-position terminal block)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003ch3\u003eConnections\/Interfaces\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eTerminal Connection\u003c\/th\u003e\n\u003cth\u003eFunction\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnection Type\u003c\/td\u003e\n\u003ctd\u003eTC-TBCH 36-Position Removable Terminal Block\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCable Assembly Option\u003c\/td\u003e\n\u003ctd\u003ePre-wired 1492-HWCAB or 1492-CABLE system\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRemote Interface Option\u003c\/td\u003e\n\u003ctd\u003eCompatible with Allen-Bradley 1492-IFM \/ 1492-XIM series RTPs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003cp\u003e \u003c\/p\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003ePolarity Warning\u003c\/strong\u003e: The module does not feature reverse polarity protection; ensure correct wiring polarity to avoid damaging internal output circuits.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eExternal Circuit Protection\u003c\/strong\u003e: Outputs are not internally fused. Use fused Remote Terminal Panels (RTPs) or interface modules to guard individual channels against overcurrent conditions.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eThermal Management\u003c\/strong\u003e: Maintain appropriate chassis clearance inside enclosures to ensure proper natural convection cooling across specified operating temperature limits.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHazardous Location RIUP\u003c\/strong\u003e: Do not remove or insert modules under power if the surrounding atmosphere is classified as a hazardous location.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eCompliance and Certifications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eUL\u003c\/strong\u003e: UL 508 Industrial Control Equipment\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHazardous Locations\u003c\/strong\u003e: Class I, Div 2, Groups A, B, C \u0026amp; D Hazardous and Ordinary locations\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEMC Directives\u003c\/strong\u003e: 89\/336\/EEC EMC Directive, EN 50081-2 (Emissions), EN 50082-2 (Immunity)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eC-Tick\u003c\/strong\u003e: Compliant with Australian Radiocommunications Act of 1992\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52705777811819,"sku":"TK-ODD321","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/TC-ODD321_005_1200x1200_20f93688-c6ea-46c8-912e-91b9922db054.jpg?v=1785990770","url":"https:\/\/www.plcprotech.com\/products\/honeywell-tc-odd321-experion-dc-output-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}