{"product_id":"honeywell-tk-oah061-c200-analog-output-module","title":"Honeywell TK-OAH061 C200 Analog Output Module","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eTK-OAH061\u003c\/strong\u003e functions as a high-density analog signal routing interface within the \u003cstrong\u003eHoneywell\u003c\/strong\u003e Experion PKS C200 controller chassis. This module provides six galvanically isolated current channels to drive external field components based on internal processing logic from the controller. It converts digital controller values into standard current loops to precisely modulate regulatory hardware such as control valve positioners, variable speed drive references, actuators, and industrial dosing pumps.\u003c\/p\u003e\n\u003cp\u003eOperating across a flexible current span, the hardware maintains distinct signal isolation to prevent ground loops and shield processing logic from field-side electrical interference. Each output loop incorporates embedded overload protection and current limiting mechanisms to ensure high continuous loop uptime. The module's engineering structure facilitates real-time deterministic updates across all active loops, supporting stable closed-loop control applications across critical process manufacturing facilities.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eGalvanically Isolated Channels:\u003c\/strong\u003e Protects internal backplane electronics and microprocessors by eliminating ground loop noise between channels and system components.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOnboard Overvoltage Protection:\u003c\/strong\u003e Safely handles continuous voltage faults at room temperature without compromising the integrity of adjacent signal loops.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eElectronically Limited Output:\u003c\/strong\u003e Automatically restricts output current during short-circuit faults to safeguard field wiring and terminations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHigh-Resolution Conversion:\u003c\/strong\u003e Delivers fine granularity over the operational current band to ensure precise process valve modulating capabilities.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eVariable frequency drive speed reference modulation and remote setpoint transmission.\u003c\/li\u003e\n\u003cli\u003eProportional control for electronic valve actuators, dampers, and positioners.\u003c\/li\u003e\n\u003cli\u003eInterface connections to strip chart recorders, local panel indicators, and continuous dosing sub-systems.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cp\u003eThe specifications listed below are derived from official engineering reference documentation for the \u003cstrong\u003eHoneywell\u003c\/strong\u003e module family, including image_3bb1ec.png:\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eCategory\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eParameter\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eSpecification\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput\/Output\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNumber of Points\u003c\/td\u003e\n\u003ctd\u003e6 galvanically isolated channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eOutput Current Range\u003c\/td\u003e\n\u003ctd\u003e0 to 21.0 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eCurrent Resolution\u003c\/td\u003e\n\u003ctd\u003e13 bits across 21 mA (2.7 uA)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eOpen Circuit Detection\u003c\/td\u003e\n\u003ctd\u003eNone\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eDrive Capability\u003c\/td\u003e\n\u003ctd\u003e20.0 mA max. into loads of 500 ohms or less. Loads of 1000 ohms or less may be achieved with alternate field terminations.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePerformance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eCalibrated Accuracy @ 25 degC\u003c\/td\u003e\n\u003ctd\u003eBetter than 0.1% of range from 4.0 mA to 21.0 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eModule Update Rate for All Channels\u003c\/td\u003e\n\u003ctd\u003e25 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eOutput Settling Time\u003c\/td\u003e\n\u003ctd\u003eLess than 2 ms to 95% of final value with resistive loads\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eOutput Offset Drift with Temperature\u003c\/td\u003e\n\u003ctd\u003e1 uA\/degC typical\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eOutput Gain Drift with Temperature\u003c\/td\u003e\n\u003ctd\u003e60 ppm\/degC typical\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProtection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eOutput Overvoltage Protection\u003c\/td\u003e\n\u003ctd\u003e24 VAC\/VDC continuous at room temperature\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eOpen Short Circuit Protection\u003c\/td\u003e\n\u003ctd\u003eElectronically current limited to 21 mA or less\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eIsolation Voltage: Channel to channel\u003c\/td\u003e\n\u003ctd\u003e100% tested at 2546 VDC for 1 second\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eIsolation Voltage: User to system\u003c\/td\u003e\n\u003ctd\u003e100% tested at 2546 VDC for 1 second\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePower \u0026amp; Interface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003ePower Dissipation\u003c\/td\u003e\n\u003ctd\u003e6.7 W max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eBackplane Current\u003c\/td\u003e\n\u003ctd\u003eSee Module Power Consumption Data, page 46.\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eConnection Terminal Blocks\u003c\/td\u003e\n\u003ctd\u003eTC-TBNH, 20-position terminal block\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eMechanical\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eManufacturer\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.4 kg (Typical for C200 I\/O cards)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e \u003c\/td\u003e\n\u003ctd\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eChassis Alignment:\u003c\/strong\u003e Match the module circuit board with the top and bottom tracking guides of the designated C200 chassis slot, pressing firmly until the retention latches snap engaged.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Block Attachment:\u003c\/strong\u003e Use the specified TC-TBNH 20-position terminal block for field wiring terminations, ensuring screws are fully tightened to eliminate intermittent resistive contacts.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLoop Load Verifications:\u003c\/strong\u003e Confirm total loop resistance does not exceed 500 ohms under standard operating layouts, or implement alternate approved field terminations if driving up to 1000 ohm loads.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSignal Cable Routing:\u003c\/strong\u003e Run low-voltage current loop wiring in dedicated conduits isolated from high-voltage motor starters, switchgear, and power lines to reduce RFI\/EMI interference.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eFAQ\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eWhat is the update rate for the output channels on this module?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eThe module updates all six analog output channels simultaneously within a fixed update interval of 25 milliseconds.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eHow does the card protect its internal circuits if a field wire shorts out?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eThe module features integrated short-circuit protection that electronically limits the output current to 21 mA or less, preventing component damage.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eIs an external terminal base needed to connect field instrumentation wires?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eYes, field instrumentation wires terminate directly into a compatible TC-TBNH 20-position terminal block assembly mapped to the module front interface.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eCan this module drive a 4-20 mA control loop device?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eYes, the hardware delivers an output current range of 0 to 21.0 mA, making it fully compatible with standard industrial 4-20 mA control devices.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52705311654251,"sku":"TK-OAH061","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/tk-oah061-w3dgjozrnpl_1d94e4a0-ea6c-4f1e-ac2e-a4d6bbc0547e.jpg?v=1766639525","url":"https:\/\/www.plcprotech.com\/products\/honeywell-tk-oah061-c200-analog-output-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}