{"product_id":"mx213-bachmann-m1-automation-system-processor-module","title":"MX213 Bachmann M1 Automation System Processor Module","description":"\u003ch3\u003eHardware Overview\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eMX213 (MX213\/512 CF)\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eprocessor module functions as the high-performance central processing unit for the Bachmann M1 automation platform, engineered specifically for high-demand industrial sectors like wind energy turbine control, maritime propulsion, and large-scale power generation infrastructure. This control unit interfaces directly with modular backplane networks to deliver deterministic program execution under rigorous field conditions. By consolidating a 266 MHz low-voltage industrial x86 processor with comprehensive communication options and an integrated 17 W power supply, the unit coordinates real-time data acquisition and complex logic control. Its solid-state hardware framework minimizes moving parts, which dramatically improves mean time between failures (MTBF) and eliminates unplanned plant downtime in continuous-process operations.\u003c\/p\u003e\n\u003ch3\u003eComprehensive Technical Configuration\u003c\/h3\u003e\n\u003cp\u003eThe architectural integrity of this processor core relies on an optimized x86\/AMD LX execution model that delivers sub-millisecond task cycle times. Data retention relies on a split-memory structure: 256 MB of volatile DRAM manages active runtime processes, while a 512 kB NVRAM system permanently captures critical retain variables and system states without requiring battery backup.\u003c\/p\u003e\n\u003cp\u003eFor horizontal and vertical network integration, the hardware features multiple dedicated onboard communication interfaces:\u003c\/p\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eDual 100 Base-TX Ethernet Ports:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eProvides separate IP channels for deterministic machine-to-machine interlocking and SCADA data transmission.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eOnboard CAN\/CANopen Channel:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eFacilitates native fieldbus master\/slave integration for remote I\/O sub-assemblies.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e\u003cstrong\u003eDual RS232\/422\/485 Serial Interfaces:\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003eSupports point-to-point industrial telemetry and legacy device connections.\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eStorage expansion uses a heavy-duty CompactFlash slot that supports industrial CF cards up to 2 GB for extensive event logging, system recipes, and local application backups.\u003c\/p\u003e\n\u003ch3\u003eCore Parameter Specifications\u003c\/h3\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr class=\"firstRow\"\u003e\n\u003ctd\u003e\u003cstrong\u003eTechnical Parameter\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cstrong\u003eEngineering Value\u003c\/strong\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eModel\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eMX213 (Spare Model: MX 213\/512 CF)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eBrand\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eBachmann Electronic\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eOrigin\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eAustria\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eWeight\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e0.7 kg\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eDimensions\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e11.0 x 6.0 x 11.8 cm\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eOperating Temperature\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e-30 to 60 deg C\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003ePower Consumption\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e33.6 W (Maximum with fully loaded I\/O modules)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eProcessor Type\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003eAMD LX x86, 266 MHz\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eSystem Memory\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e256 MB DRAM \/ 16 MB File-Flash\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eRetentive Memory\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e512 kB NVRAM\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eInput Supply Voltage\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e24 VDC (Acceptable tolerance band: 18 to 34 V)\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eIntegrated Power Supply\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e17 W output capacity\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cspan\u003e\u003cstrong\u003eTariff Code\u003c\/strong\u003e\u003c\/span\u003e\u003c\/td\u003e\n\u003ctd\u003e\u003cspan\u003e8537101190\u003c\/span\u003e\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eProduct FAQs\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eHow does the module manage critical variable storage during an abrupt 24 VDC power disruption?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eThe unit features an onboard hardware monitoring circuit that detects supply voltage drops below acceptable limits. Upon detection, the system uses the residual energy stored in the internal power supply capacitors to write all designated retain data directly into the 512 kB non-volatile NVRAM. This architecture ensures complete data preservation without the failure risks of traditional lithium batteries.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eCan the dual Ethernet interfaces on this control unit be configured on independent subnets?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eYes. The two physical Ethernet ports (2x ETH100) are assigned separate MAC addresses and link layers. Engineers can configure them with distinct IP addresses on independent subnets to isolate deterministic machine network traffic from standard corporate plant networks.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eWhat are the direct drop-in replacement procedures if updating an older MX200 processor variant?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eThe MX213 maintains complete downward compatibility with previous Bachmann M1 software deployments. When replacing an older variant, the application code compiled for the x86 architecture can be transferred via the CompactFlash card. However, you must verify that the target firmware version supports the integrated communication controllers on the newer hardware.\u003c\/p\u003e\n\u003chr\u003e\n\u003ch3\u003eEngineering \u0026amp; Installation Guide\u003c\/h3\u003e\n\u003ch4\u003eThermal Management \u0026amp; Airflow Clearances\u003c\/h4\u003e\n\u003cp\u003eTo maintain structural stability up to the maximum 60 deg C rating, you must install the controller chassis vertically on a standard DIN rail. Maintain a minimum clear boundary space of 80 mm above and below the module housing. This spatial clearance generates natural convective airflow, preventing localized heat pockets inside the enclosure and protecting the low-voltage internal silicon components from premature thermal breakdown.\u003c\/p\u003e\n\u003ch4\u003eGrounding and Shielding Protocols\u003c\/h4\u003e\n\u003cp\u003eAll fieldbus communication links (specifically CANopen and RS485 lines) must use shielded twisted-pair cabling. Terminate the cable shields directly at the entry point of the electrical cabinet using low-impedance ground clamps. The DIN rail itself must connect to the central plant functional earth via a copper conductor with a minimum cross-section of 10 square millimeters to neutralize high-frequency electromagnetic noise.\u003c\/p\u003e\n\u003ch4\u003ePower Distribution Protection\u003c\/h4\u003e\n\u003cp\u003eThe 24 VDC input supply line requires protection via a fast-acting circuit breaker or fuse rated at a maximum of 4.0 A. To prevent ground loops and common-mode voltage fluctuations from destabilizing the x86 processor core, do not share the primary 24 VDC automation power bus with inductive switching elements, such as heavy-duty motor contactors or hydraulic solenoids.\u003c\/p\u003e\n\u003ch3\u003e\u003c\/h3\u003e","brand":"Bachmann","offers":[{"title":"Default Title","offer_id":53240196333931,"sku":"MX213","price":88.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/MX213.png?v=1778943594","url":"https:\/\/www.plcprotech.com\/products\/mx213-bachmann-m1-automation-system-processor-module","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}