{"product_id":"general-electric-is200tvbah2acc-mark-vie-vibration-input-terminal-board","title":"General Electric IS200TVBAH2ACC Mark VIe Vibration Input Terminal Board","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIS200TVBAH2ACC\u003c\/strong\u003e operates as a high-performance vibration input terminal board developed by General Electric for deployment within the Mark VIe Speedtronic turbine control platform. This terminal board acquires real-time seismic, proximitor, velomiter, and accelerometer sensor feedback from dynamic gas, steam, and wind turbine drive assemblies. Optimized for machinery protection loops, the \u003cstrong\u003eIS200TVBAH2ACC\u003c\/strong\u003e implements individual channel signal suppression and electromagnetic interference (EMI) filtering parameters to isolate sensitive processing elements from transient field disruptions.\u003c\/p\u003e\n\u003cp\u003eRather than relying on common instrumentation power supplies, the \u003cstrong\u003eIS200TVBAH2ACC\u003c\/strong\u003e obtains operational stability directly from external +28 V sources, leveraging three onboard removable daughterboards to achieve critical +28 V to -28 V voltage conversion locally. The circuit card hosts standard terminal blocks paired alongside a dedicated high-density cable connector network to streamline the delivery of buffered dynamic vibration wave vectors directly into the downstream I\/O processor framework.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eFlexible Transducer Interfacing:\u003c\/strong\u003e Accommodates multiple industrial measurement elements, specifically accepting proximitor, seismic, velomiter, and accelerometer transducer variations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOnboard Negative Voltage Inversion:\u003c\/strong\u003e Integrates three modular, field-removable daughterboards that internally convert +28 V to -28 V to fully sustain transducer power requirements.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTransient Signal Filtering:\u003c\/strong\u003e Delivers dedicated surge suppression and EMI noise defense boundaries uniquely matched across each sensor channel track.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHigh-Density Monitoring Interface:\u003c\/strong\u003e Features dual integrated terminal blocks, supporting 14 dynamic sensor inputs through a total of 24 independent field terminals.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBuffered Diagnostic Outputs:\u003c\/strong\u003e Provisions 14 individual N24 buffered sensor outputs alongside specialized multi-pin output plugs for Bently-Nevada analytical machinery instruments.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConformal Coating Insulation:\u003c\/strong\u003e Protected by a precise, thin conformal coating formulation that comprehensively seals traces against corrosive ambient plant humidity.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMark VIe Speedtronic dynamic turbine vibration monitoring systems\u003c\/li\u003e\n\u003cli\u003eCritical turbo-machinery shaft displacement and overspeed safety loops\u003c\/li\u003e\n\u003cli\u003eReal-time predictive maintenance tracking within automated wind, steam, and gas turbine drive assemblies\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eItem\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eDescription \/ Value\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eSeries\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMark VIe Speedtronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePart Number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIS200TVBAH2ACC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFunctional Acronym\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTVBA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eVibration Input Terminal Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePCB Coating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eConformal Coating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFunctional Revision 1\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTotal Sensor Inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e14 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTotal Block Terminals\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e24 points\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBuffered Signal Paths\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e14 N24 buffered outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBently-Nevada Data Plugs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e11 ports\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePrimary Interface Connector\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e37-pin connector plug\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput Voltage Framework\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAcquired +28 V source inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWeight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e3.2 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eShield Termination Grounding:\u003c\/strong\u003e Fasten the primary field cables firmly to the dedicated shield termination attachment point on the board frame to suppress induced electromagnetic or radio frequency noise.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003ePower Loop Configuration:\u003c\/strong\u003e Verify that the primary external +28 V source supplies remain functional and stable to power the voltage inversion daughterboard cards, maintaining regular TVIB board interaction profiles.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eElectrostatic Grounding Measures:\u003c\/strong\u003e Ensure the system service engineer wears a path-to-ground ESD wrist strap during the removal or replacement of the negative voltage daughterboard modules to avoid circuit overstress.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":52695412572523,"sku":"IS200TVBAH2ACC","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/general-electric-is200tvbah2acc-vibration-input-terminal-board-sia41nm4ek5_df2b7401-a132-41ab-a49c-63b46e6e1861.jpg?v=1766135116","url":"https:\/\/www.plcprotech.com\/tr\/products\/general-electric-is200tvbah2acc-mark-vie-vibration-input-terminal-board","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}