Configuring RSLinx Drivers for SLC 5/04 DF1, DH-485, and DH+ Communication — figure 1

SLC 5/04 uchun DF1, DH-485 va DH+ aloqa drayverlarini sozlash

SLC 5/04 uchun RSLinx drayverini sozlash: CH.0 ketma-ket porti uchun DF1 drayveridan, DH-485 uchun 1747-PIC/AIC+ qurilmasidan yoki DH+ (CH.1) uchun 1784-PCMK...

Hali ham yangi ControlLogix hujayralari yonida RSLogix 500 mantiqi ishlayotgan zavodlarda SLC 5/04 bilan ishonchli RSLinx Classic aloqasini o‘rnatish asosiy ko‘nikmalardan biri bo‘lib qolmoqda. Kontrollerning ikki kanalli tuzilishi — birinchi tekshiriladigan jihat: 0-kanal DF1 yoki DH-485 bo‘lishi mumkin, 1-kanal esa faqat DH+ uchun mo‘ljallangan. Fizik port uchun noto‘g‘ri RSLinx drayverini tanlash — protsessorning RUN LED indikatori normal yonib turgan bo‘lsa ham, RSWho oynasi bo‘sh qolishining eng keng tarqalgan sababidir.

SLC 5/04 DF1, DH-485 va DH+ aloqalari uchun RSLinx drayverlarini sozlash — 1-rasm Odatdagi DF1, DH-485 va DH+ interfeys qurilmalari bilan SLC 5/04 ning 0-kanal va 1-kanal ulagichlari.

RSLinx’ni ochishdan oldin uzatish muhitini moslang. 0-kanaldagi DF1 Full-Duplex odatda kompyuterning COM porti yoki USB-serial adapteridan 1747-CP3 (yoki ekvivalenti) ketma-ket kabelidan foydalanadi. 0-kanaldagi DH-485 uchun oddiy null-modem kabeli emas, 1747-PIC yoki AIC+ yo‘li kerak. 1-kanaldagi DH+ esa to‘g‘ri magistral tarmoq ulanishi va terminatsiya rezistorlariga ega 1784-PCMK, 1784-PKTX yoki eski KTX turidagi kartani talab qiladi. Har ikki tomondagi uzatish tezligi mutlaqo bir xil bo‘lishi kerak, DH+ tugun manzillari esa 00 dan 77 gacha bo‘lgan sakkizlik qiymatlardir.

RSLogix 500’da protsessor kanali konfiguratsiyasini tekshiring

Onlayn yoki oflayn rejimda SLC 5/04 uchun Channel Configuration oynasini oching va 0-kanalga qaysi protokol biriktirilgani, shuningdek qaysi tugun yoki stansiya raqami belgilanganini qayd eting. Zavod sozlamalari oxirgi OEM yuklashidan keyin saqlanib qolgan deb o‘ylamang. Agar 0-kanal qo‘l siqishsiz, 19200 tezlikdagi DF1 Full-Duplex bo‘lsa, RSLinx DF1 drayveri ham aynan shu sozlamalarni takrorlashi kerak. Agar 0-kanal DH-485 bo‘lsa, stansiya raqami va uzatish tezligi AIC+ tarmog‘i bilan mos kelishi lozim. 1-kanal DH+ tugun manzili magistralda yagona bo‘lishi kerak; bir xil sakkizlik tugunlar drayver xatosiga o‘xshab ko‘rinadigan uzilib-qoluvchi ko‘rish muammolarini keltirib chiqaradi.

Noutbuk aravachasidan ketishdan oldin kanal xulosasini chop eting yoki ekran rasmini oling. Ko‘plab “RSLinx PLC’ni ko‘rmayapti” murojaatlari elektrik 0-kanal bir necha oy oldin PanelView ko‘chirilishi uchun DH-485 ga o‘zgartirilganini, noutbuk esa hali ham DF1 drayver profilini yuklayotganini aniqlagach hal bo‘ladi.

SLC 5/04 DF1, DH-485 va DH+ aloqalari uchun RSLinx drayverlarini sozlash — 2-rasm SLC 5/04 ning 0-kanal DF1 Full-Duplex sozlamalariga moslangan RSLinx Classic drayverini sozlash oynasi.

RSLinx drayverini sozlang

  1. RSLinx Classic’ni ishga tushiring va Configure Drivers bo‘limini oching.
  2. 0-kanaldagi DF1 uchun “RS-232 DF1 devices” bandini qo‘shing, to‘g‘ri COM portni tanlang, Device parametrini SLC-CH0 / 1747-CP3 turiga o‘rnating, uzatish tezligi, parity, xatolarni tekshirish va Full-Duplex sozlamalarini moslang.
  3. DH-485 uchun 1747-PIC/AIC+ drayverini (yoki mos USB o‘rnini bosuvchi stekni) qo‘shing, stansiya raqamini protsessornikidan farqli qilib belgilang va uzatish tezligini moslang.
  4. 1-kanaldagi DH+ uchun 1784-PCMK/PKTX/KTX drayverini sozlang, kompyuter tugunini foydalanilmayotgan sakkizlik manzilga o‘rnating va tarmoq turi hamda tezligini tekshiring (o‘rnatilgan tizimga qarab odatda 57.6K yoki 230.4K).
  5. Drayverni ishga tushiring va port bandligi bilan bog‘liq xatolarsiz Running holatini ko‘rsatayotganini tasdiqlang.

RSWho orqali ko‘rib chiqing va ulanishni tasdiqlang

RSWho’ni oching, yangi drayverni kengaytiring va SLC 5/04 stansiyasi kutilgan tugun bilan paydo bo‘lishini kuting. RSLogix 500 orqali shu yo‘l bilan kontrollerga onlayn ulaning va ma’lumotlar jadvalidan kichik hajmdagi monitoring o‘qishini bajaring. Agar stansiya paydo bo‘lib, keyin yo‘qolsa, kabel ekranlamasi, AIC+ bias sozlamasi, DH+ terminatsiyalari va USB-serial kechikishini qayta tekshiring. Uzoq davom etadigan yuklashlar vaqtida USB COM portlarini to‘xtatib qo‘yadigan noutbuk quvvat boshqaruvi DF1 uzilishlarining keng tarqalgan sababidir.

Yo‘l Kanal Odatdagi uskuna RSLinx drayverining asosiy sozlamasi
DF1 Full-Duplex CH.0 1747-CP3 RS-232 DF1, uzatish tezligi/parity mosligi
DH-485 CH.0 1747-PIC / AIC+ PIC/AIC drayveri, yagona stansiya
DH+ CH.1 only 1784-PCMK / PKTX / KTX DH+ karta drayveri, 00–77 sakkizlik tugunlar
Tarmoqni “ishlamayapti” deb atashdan oldingi tekshiruv ro‘yxati:
1. RSLogix 500 Channel Config protokoli = mo‘ljallangan uzatish muhiti
2. PLC va RSLinx’dagi uzatish tezligi bir xil
3. Kabel/adapter modeli protokolga mos
4. DH+ tuguni yagona va sakkizlik formatda
5. Drayver holati = Running; RSWho stansiyani ko‘rsatadi
6. RSLogix 500 vaqt tugashi xatolarisiz onlayn ulanadi

Bir smenani behuda sarflaydigan xatolar

DH+ drayverini 0-kanalga yo‘naltirmang. DH-485 portida CP3 kabelidan foydalanib, avtomatik kelishuvni kutmang. Windows drayverining quvvat tejash rejimida belgilangan uzatish tezligini e’tiborsiz qoldiradigan USB-RS232 adapterlari dastlabki ko‘rishdan o‘tib, yuklash vaqtida ishlamay qolishi mumkin. DH+ tizimida sakkizlik manzillarni shkafda qayd eting, shunda o‘nlik sanoq tizimiga odatlangan texniklar siferblat 10 sakkizlikni ko‘rsatib turganda 8-tugunni o‘rnatmaydi. Zavoddagi RSLinx zaxira papkasida kamida bitta soz, ishonchli CP3 va bitta soz, ishonchli PCMK profilini saqlang.

RSWho SLC 5/04’ni izchil ko‘rsata boshlagach, RSLinx konfiguratsiyasini saqlang va drayverlar to‘plamini texnik xizmat tasviri uchun eksport qiling. Bu kichik tartib qarib borayotgan PLC & PAC tizimlarida oflayn tahrirlar, force jadvallari va trend vositalaridan foydalanishni saqlab qoladi hamda har bir to‘xtash vaqtida ketma-ket ulanish yo‘lini qaytadan yaratish zaruratini bartaraf etadi.

Muallif haqida

Mark Townsend | Katta avtomatlashtirish muhandisi – Allen-Bradley tizimlari

Mark Townsend ControlLogix, CompactLogix va eski SLC-500 platformalarini qamrab olgan Allen-Bradley tizimlarida 18 yildan ortiq tajribaga ega katta avtomatlashtirish muhandisidir. Uning kundalik ishi qarib borayotgan va aralash parklar uchun RSLogix / Studio 5000 mantiqi hamda FactoryTalk View HMI tizimlarini ishga tushirishdan iborat.

SLC 5/04 uchun DF1, DH-485 va DH+ aloqa drayverlarini sozlash

SLC 5/04 uchun RSLinx drayverini sozlash: CH.0 ketma-ket porti uchun DF1 drayveridan, DH-485 uchun 1747-PIC/AIC+ qurilmasidan yoki DH+ (CH.1) uchun 1784-PCMK/PKTX kartalaridan foydalaning. Kabel va...

Hali ham yangi ControlLogix hujayralari yonida RSLogix 500 mantiqi ishlayotgan zavodlarda SLC 5/04 bilan ishonchli RSLinx Classic aloqasini o‘rnatish asosiy ko‘nikmalardan biri bo‘lib qolmoqda. Kontrollerning ikki kanalli tuzilishi — birinchi tekshiriladigan jihat: 0-kanal DF1 yoki DH-485 bo‘lishi mumkin, 1-kanal esa faqat DH+ uchun mo‘ljallangan. Fizik port uchun noto‘g‘ri RSLinx drayverini tanlash — protsessorning RUN LED indikatori normal yonib turgan bo‘lsa ham, RSWho oynasi bo‘sh qolishining eng keng tarqalgan sababidir.

SLC 5/04 DF1, DH-485 va DH+ aloqalari uchun RSLinx drayverlarini sozlash — 1-rasm Odatdagi DF1, DH-485 va DH+ interfeys qurilmalari bilan SLC 5/04 ning 0-kanal va 1-kanal ulagichlari.

RSLinx’ni ochishdan oldin uzatish muhitini moslang. 0-kanaldagi DF1 Full-Duplex odatda kompyuterning COM porti yoki USB-serial adapteridan 1747-CP3 (yoki ekvivalenti) ketma-ket kabelidan foydalanadi. 0-kanaldagi DH-485 uchun oddiy null-modem kabeli emas, 1747-PIC yoki AIC+ yo‘li kerak. 1-kanaldagi DH+ esa to‘g‘ri magistral tarmoq ulanishi va terminatsiya rezistorlariga ega 1784-PCMK, 1784-PKTX yoki eski KTX turidagi kartani talab qiladi. Har ikki tomondagi uzatish tezligi mutlaqo bir xil bo‘lishi kerak, DH+ tugun manzillari esa 00 dan 77 gacha bo‘lgan sakkizlik qiymatlardir.

RSLogix 500’da protsessor kanali konfiguratsiyasini tekshiring

Onlayn yoki oflayn rejimda SLC 5/04 uchun Channel Configuration oynasini oching va 0-kanalga qaysi protokol biriktirilgani, shuningdek qaysi tugun yoki stansiya raqami belgilanganini qayd eting. Zavod sozlamalari oxirgi OEM yuklashidan keyin saqlanib qolgan deb o‘ylamang. Agar 0-kanal qo‘l siqishsiz, 19200 tezlikdagi DF1 Full-Duplex bo‘lsa, RSLinx DF1 drayveri ham aynan shu sozlamalarni takrorlashi kerak. Agar 0-kanal DH-485 bo‘lsa, stansiya raqami va uzatish tezligi AIC+ tarmog‘i bilan mos kelishi lozim. 1-kanal DH+ tugun manzili magistralda yagona bo‘lishi kerak; bir xil sakkizlik tugunlar drayver xatosiga o‘xshab ko‘rinadigan uzilib-qoluvchi ko‘rish muammolarini keltirib chiqaradi.

Noutbuk aravachasidan ketishdan oldin kanal xulosasini chop eting yoki ekran rasmini oling. Ko‘plab “RSLinx PLC’ni ko‘rmayapti” murojaatlari elektrik 0-kanal bir necha oy oldin PanelView ko‘chirilishi uchun DH-485 ga o‘zgartirilganini, noutbuk esa hali ham DF1 drayver profilini yuklayotganini aniqlagach hal bo‘ladi.

SLC 5/04 DF1, DH-485 va DH+ aloqalari uchun RSLinx drayverlarini sozlash — 2-rasm SLC 5/04 ning 0-kanal DF1 Full-Duplex sozlamalariga moslangan RSLinx Classic drayverini sozlash oynasi.

RSLinx drayverini sozlang

  1. RSLinx Classic’ni ishga tushiring va Configure Drivers bo‘limini oching.
  2. 0-kanaldagi DF1 uchun “RS-232 DF1 devices” bandini qo‘shing, to‘g‘ri COM portni tanlang, Device parametrini SLC-CH0 / 1747-CP3 turiga o‘rnating, uzatish tezligi, parity, xatolarni tekshirish va Full-Duplex sozlamalarini moslang.
  3. DH-485 uchun 1747-PIC/AIC+ drayverini (yoki mos USB o‘rnini bosuvchi stekni) qo‘shing, stansiya raqamini protsessornikidan farqli qilib belgilang va uzatish tezligini moslang.
  4. 1-kanaldagi DH+ uchun 1784-PCMK/PKTX/KTX drayverini sozlang, kompyuter tugunini foydalanilmayotgan sakkizlik manzilga o‘rnating va tarmoq turi hamda tezligini tekshiring (o‘rnatilgan tizimga qarab odatda 57.6K yoki 230.4K).
  5. Drayverni ishga tushiring va port bandligi bilan bog‘liq xatolarsiz Running holatini ko‘rsatayotganini tasdiqlang.

RSWho orqali ko‘rib chiqing va ulanishni tasdiqlang

RSWho’ni oching, yangi drayverni kengaytiring va SLC 5/04 stansiyasi kutilgan tugun bilan paydo bo‘lishini kuting. RSLogix 500 orqali shu yo‘l bilan kontrollerga onlayn ulaning va ma’lumotlar jadvalidan kichik hajmdagi monitoring o‘qishini bajaring. Agar stansiya paydo bo‘lib, keyin yo‘qolsa, kabel ekranlamasi, AIC+ bias sozlamasi, DH+ terminatsiyalari va USB-serial kechikishini qayta tekshiring. Uzoq davom etadigan yuklashlar vaqtida USB COM portlarini to‘xtatib qo‘yadigan noutbuk quvvat boshqaruvi DF1 uzilishlarining keng tarqalgan sababidir.

Yo‘l Kanal Odatdagi uskuna RSLinx drayverining asosiy sozlamasi
DF1 Full-Duplex CH.0 1747-CP3 RS-232 DF1, uzatish tezligi/parity mosligi
DH-485 CH.0 1747-PIC / AIC+ PIC/AIC drayveri, yagona stansiya
DH+ CH.1 only 1784-PCMK / PKTX / KTX DH+ karta drayveri, 00–77 sakkizlik tugunlar
Tarmoqni “ishlamayapti” deb atashdan oldingi tekshiruv ro‘yxati:
1. RSLogix 500 Channel Config protokoli = mo‘ljallangan uzatish muhiti
2. PLC va RSLinx’dagi uzatish tezligi bir xil
3. Kabel/adapter modeli protokolga mos
4. DH+ tuguni yagona va sakkizlik formatda
5. Drayver holati = Running; RSWho stansiyani ko‘rsatadi
6. RSLogix 500 vaqt tugashi xatolarisiz onlayn ulanadi

Bir smenani behuda sarflaydigan xatolar

DH+ drayverini 0-kanalga yo‘naltirmang. DH-485 portida CP3 kabelidan foydalanib, avtomatik kelishuvni kutmang. Windows drayverining quvvat tejash rejimida belgilangan uzatish tezligini e’tiborsiz qoldiradigan USB-RS232 adapterlari dastlabki ko‘rishdan o‘tib, yuklash vaqtida ishlamay qolishi mumkin. DH+ tizimida sakkizlik manzillarni shkafda qayd eting, shunda o‘nlik sanoq tizimiga odatlangan texniklar siferblat 10 sakkizlikni ko‘rsatib turganda 8-tugunni o‘rnatmaydi. Zavoddagi RSLinx zaxira papkasida kamida bitta soz, ishonchli CP3 va bitta soz, ishonchli PCMK profilini saqlang.

RSWho SLC 5/04’ni izchil ko‘rsata boshlagach, RSLinx konfiguratsiyasini saqlang va drayverlar to‘plamini texnik xizmat tasviri uchun eksport qiling. Bu kichik tartib qarib borayotgan PLC & PAC tizimlarida oflayn tahrirlar, force jadvallari va trend vositalaridan foydalanishni saqlab qoladi hamda har bir to‘xtash vaqtida ketma-ket ulanish yo‘lini qaytadan yaratish zaruratini bartaraf etadi.

Muallif haqida

Mark Townsend | Katta avtomatlashtirish muhandisi – Allen-Bradley tizimlari

Mark Townsend ControlLogix, CompactLogix va eski SLC-500 platformalarini qamrab olgan Allen-Bradley tizimlarida 18 yildan ortiq tajribaga ega katta avtomatlashtirish muhandisidir. Uning kundalik ishi qarib borayotgan va aralash parklar uchun RSLogix / Studio 5000 mantiqi hamda FactoryTalk View HMI tizimlarini ishga tushirishdan iborat.