{"product_id":"general-electric-is200tvibh2bcc-mark-vi-termination-vibration-board","title":"General Electric IS200TVIBH2BCC Mark VI Termination Vibration Board","description":"\u003ch3\u003eDescription\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong\u003eIS200TVIBH2BCC\u003c\/strong\u003e functions as a dedicated terminal vibration board manufactured by GE Industrial Systems under the General Electric production umbrella for the Mark VI Speedtronic control series. This module serves as a critical connection layer within the greater VVIB vibration and position board assembly, enabling direct interface paths for up to fourteen Bently Nevada proximity probes tasked with mechanical shaft vibration monitoring. Engineered to support robust diagnostic applications, the \u003cstrong\u003eIS200TVIBH2BCC\u003c\/strong\u003e outputs buffered raw signals to facilitate localized parameter collection by portable data gathering hardware without interrupting active machinery protection tracking.\u003c\/p\u003e\n\u003cp\u003eThis customizable terminal hardware modification extends its system compatibility beyond traditional steam and gas utility turbine governance loops, featuring validated integration pathways for industrial wind turbine management systems. Outfitted with multiple configurable hardware jumper pairs, the board establishes accurate sensor signal routing and matching impedance baselines across dynamic rotating machinery diagnostics.\u003c\/p\u003e\n\u003ch3\u003eFeatures\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eMulti-Probe Monitoring Interface:\u003c\/strong\u003e Provisions direct termination lanes for up to fourteen external Bently Nevada probes to execute continuous shaft vibration analysis.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eDedicated Diagnostic Outlets:\u003c\/strong\u003e Incorporates fourteen standalone BNC connectors designed to isolate and distribute buffered sensor wave vectors directly to portable data logging equipment.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHigh-Density Pluggable Blocks:\u003c\/strong\u003e Hosts two screw-secured terminal blocks supporting 24 I\/O connections each, yielding a total of 48 removable field terminal termination points.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHighly Customizable Architecture:\u003c\/strong\u003e Populated with sixteen configurable hardware jumper pairs to modify board layouts and factory-specified tracking configurations.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIndustrial Grade Layer Shielding:\u003c\/strong\u003e Protected by a thin, specialized conformal circuit coating that completely encapsulates board elements against corrosive contamination.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMark VI Speedtronic heavy-duty gas, steam, and wind turbine shaft vibration monitoring\u003c\/li\u003e\n\u003cli\u003eReal-time dynamic machinery diagnostic and predictive maintenance data logging\u003c\/li\u003e\n\u003cli\u003eField proximity probe signal conditioning and terminal block routing\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eTechnical Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003e\u003cstrong\u003eItem\u003c\/strong\u003e\u003c\/th\u003e\n\u003cth\u003e\u003cstrong\u003eDescription \/ Value\u003c\/strong\u003e\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOriginal Manufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGE Industrial Systems\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProduct Series\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eMark VI Speedtronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFunctional Part Number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eIS200TVIBH2BCC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFunctional Acronym\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTVIB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eFunctional Description\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eTermination Vibration Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePCB Coating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eConformal Coating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e1st Functional Revision\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003e2nd Functional Revision\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eArtwork Revision\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eProbe Connections Supported\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUp to 14 Bently Nevada probes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eBuffered Signal Connectors\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e14 BNC interface ports\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eTotal Terminal Block Connections\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e48 I\/O connection points (24 per block)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOnboard Configurable Jumpers\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e16 jumpers\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCountry of Origin\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eInstallation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal Block Fastening:\u003c\/strong\u003e Ensure the two large pluggable terminal blocks are secured onto the base circuit card structure via the four factory-supplied retention screws to maintain physical bridge alignment.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eJumper Map Validation:\u003c\/strong\u003e Verify the position and label alignment of the sixteen hardware jumper pairs match the designated system site specifications prior to applying loop excitation power.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSignal Shield Isolation:\u003c\/strong\u003e Ground external probe transmission shielding leads through the proper terminal common points to mitigate ambient plant electromagnetic disruptions across the BNC outputs.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":52695414505835,"sku":"IS200TVIBH2BCC","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0953\/3227\/0443\/files\/general-electric-is200tvibh2bcc-termination-vibration-board-yq532ygedwb_9bb8bb64-47cb-41bd-983a-78521384dfab.jpg?v=1766135193","url":"https:\/\/www.plcprotech.com\/vi\/products\/general-electric-is200tvibh2bcc-mark-vi-termination-vibration-board","provider":"PLC ProTech Ltd.","version":"1.0","type":"link"}