| Manufacturer |
Basler Electric |
| Model |
DECS-200-2L |
| Control Power Input Voltage (Style L) |
16 to 60 Vdc |
| Control Power Burden |
30 W |
| AC Operating Power Input (32 Vdc Output) |
60 Vac nominal, 56 to 70 Vac +/-10%, 1 or 3 Phase, 50 to 500 Hz, 780 VA burden |
| AC Operating Power Input (63 Vdc Output) |
120 Vac nominal, 100 to 139 Vac +/-10%, 1 or 3 Phase, 50 to 500 Hz, 1570 VA burden |
| AC Operating Power Input (125 Vdc Output) |
240 Vac nominal, 190 to 277 Vac +/-10%, 1 or 3 Phase, 50 to 500 Hz, 3070 VA burden |
| Minimum Voltage Buildup |
3 Vac |
| Continuous Field Output Current |
15 Adc |
| 10-Second Forcing Output Current |
30 Adc |
| Rated Field Output Voltage (32 Vdc Output) |
32 Vdc continuous, 50 Vdc 10-sec forcing, 2.13 Ohm min field resistance |
| Rated Field Output Voltage (63 Vdc Output) |
63 Vdc continuous, 100 Vdc 10-sec forcing, 4.2 Ohm min field resistance |
| Rated Field Output Voltage (125 Vdc Output) |
125 Vdc continuous, 200 Vdc 10-sec forcing, 8.3 Ohm min field resistance |
| Generator Voltage Sensing Ranges |
100V/50Hz (85 to 127V), 120V/60Hz (94 to 153V), 200V/50Hz (170 to 254V), 240V/60Hz (187 to 305V), 400V/50Hz (340 to 508V), 480V/60Hz (374 to 600V), 500V/50Hz (425 to 625V), 600V/60Hz (510 to 660V) |
| Bus Voltage Sensing Ranges |
100V/50Hz (85 to 127V), 120V/60Hz (94 to 153V), 200V/50Hz (170 to 254V), 240V/60Hz (187 to 305V), 400V/50Hz (340 to 508V), 480V/60Hz (374 to 600V), 500V/50Hz (425 to 625V), 600V/60Hz (510 to 660V) |
| Generator Current Sensing Rating |
1 Aac and 5 Aac for metering/control; 1 Aac and 5 Aac for cross current compensation |
| Sensing Burden |
Voltage: <0.1 VA per phase; Current: <1 VA; Parallel Compensation: <1 VA |
| Contact Switching Inputs |
11 inputs supplied with 24 Vdc for dry contacts |
| Remote Set Point Auxiliary Inputs |
Selectable +10 Vdc or 4 to 20 mA |
| Contact Output Carry Rating |
7.0 A resistive @ 24/48/125 Vdc / 120/240 Vac |
| Contact Output Make/Break Rating |
7.0 A @ 24 Vdc, 0.7 A @ 48 Vdc, 0.2 A @ 125 Vdc, 7.0 A @ 120/240 Vac |
| AVR Regulation Accuracy |
+/-0.25% over load range at rated power factor and constant frequency |
| AVR Steady State Stability |
+/-0.1% at constant load and frequency |
| AVR Temperature Drift |
+/-0.5% for 0 to 50 degC change |
| FCR Regulation Accuracy |
+/-1.0% of nominal value for 10% input voltage or 20% field resistance change |
| var Regulation Accuracy |
+/-2.0% of nominal VA rating at rated frequency |
| PF Regulation Accuracy |
+/-0.02 PF for real power between 10% and 100% at rated frequency |
| Operating Temperature |
-40 degC to +60 degC (-40 degF to +140 degF) |
| Storage Temperature |
-40 degC to +85 degC (-40 degF to +185 degF) |
| Salt Fog Resistance |
Per MIL-STD-810E, Method 509.3 (100 hrs salt fog, 100 hrs drying) |
| Shock Resistance |
15 Gs in each of three mutually perpendicular planes |
| Vibration Resistance |
5-26 Hz: 1.2 Gs; 27-52 Hz: 0.914 mm (.036 in) double amplitude; 53-500 Hz: 5.0 Gs |
| Dimensions (H x W x D) |
12.0 in x 8.08 in x 6.76 in (304 mm x 205 mm x 171 mm) |
| Weight |
14 lbs (6.35 kg) |