1 of 1

Beckhoff ER3314-0002 EtherCAT Box 4-Channel Thermocouple Input Module

Beckhoff ER3314-0002 EtherCAT Box 4-Channel Thermocouple Input Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: ER3314-0002

  • Country of origin:Germany

  • Product Type: EtherCAT Box Modules

  • Payment: T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Direct processing of up to four thermocouple sensors in harsh industrial environments is enabled by the Beckhoff ER3314-0002, an IP67-rated EtherCAT Box designed for decentralized temperature acquisition. Operating directly in the field, this space-saving module converts thermoelectric voltages from various sensor types (J, K, L, B, E, N, R, S, T, and U) into high-resolution temperature values, routing them straight to the controller without requiring a local electrical cabinet. System integrators benefit from native TwinCAT compatibility, configurable input filters, and robust electrical isolation, ensuring precise thermal profiling even under severe electromagnetic and environmental stress.

Features

  • Multi-Sensor Support: Built-in compatibility with ten distinct thermocouple classifications and direct millivolt (mV) voltage measurements.
  • Decentralized IP67 Housing: Fully encapsulated zinc die-cast housing provides extreme protection against moisture, dust, and mechanical impact.
  • M12 Connection Technology: Secure 2-wire thermocouple connections via standardized M12 screw sockets to resist high-vibration applications.
  • Advanced Diagnostics: Built-in open-circuit recognition and sensor failure detection reported directly over the EtherCAT process data image.
  • Configurable Filtering: Five software-configurable input filter variations to eliminate high-frequency electrical noise and line interference.

Applications

  • Decentralized temperature measurement on plastic injection molding and extrusion machinery.
  • Multi-zone thermal tracking in industrial glass, ceramic, and metallurgical kilns.
  • Field-level environmental testing and climatic chamber monitoring.
  • Exhaust gas and cooling system measurement in heavy-duty engine testing beds.

Technical Specifications

Parameter Specification
Manufacturer Beckhoff Automation GmbH & Co. KG
Model / Part Number ER3314-0002
Number of Inputs 4 channels
Sensor Types Supported Types J, K, L, B, E, N, R, S, T, U (default: Type K), mV measurement
Measuring Range Sensor-dependent (Type K: -100 to +1370 degC)
Resolution 0.1 degC per digit
Measurement Error Less than +/-0.3% of full-scale value (Type K)
Conversion Time 2.5 s down to 20 ms (configurable; default: ~250 ms)
Bus Interface 2 x M8 socket, shielded, screw-type (EtherCAT)
Nominal Supply Voltage 24 V DC (-15% / +20%)
Current Consumption from US 120 mA
Electrical Isolation 500 V RMS
Protection Rating IP65 / IP66 / IP67 (conforms to EN 60529)
Operating / Storage Temp -25 to +60 degC / -40 to +85 degC
Approvals CE, UL
Country of Origin Germany
Net Weight 0.265 kg
Shipping Weight (Calculated) 2.0 kg (with protective commercial packaging)

Connections and Interfaces

Connector Pin / Terminal Function / Circuit Assignment
M12 Sockets (Channels 1 to 4) Thermocouple Connection (2-wire input: TC+ and TC-)
M8 Male Socket (Feed) Power Supply IN (24 V DC Control Voltage US / Sensor Supply UP)
M8 Female Socket (Downstream) Power Supply OUT (Looping power to downstream EtherCAT boxes)
M8 Sockets (EtherCAT Link) EtherCAT IN / EtherCAT OUT (100 Mbps communication lines)

Alternative Models & Compatibility

The ER3314-0002 features a zinc die-cast housing designed to offer superior mechanical protection compared to the plastic-housed EP3314-0002 variant, though they remain functionally and programmatically identical. For setups requiring higher channel density in a control cabinet rather than field mounting, standard EtherCAT Terminals such as the EL3314 can be utilized within an E-bus segment. Both systems map to the exact same process image, allowing seamless code translation and direct parameter reuse in TwinCAT PLC configurations.

Application Pitfalls & Engineering Notes

Due to the high thermal mass of the zinc die-cast chassis, sudden environmental temperature changes near the module can cause temporary localized gradients across the cold junction. To prevent measurement errors during rapid ambient fluctuations, avoid mounting the box directly adjacent to heat sources or in areas experiencing severe draft currents. Unshielded thermocouple wires are highly susceptible to electromagnetic coupling; always maintain proper isolation from high-voltage variable frequency drive (VFD) cabling and use shielded thermocouple cables where possible.

Commissioning & Wiring Tips

When configuring the module within TwinCAT System Manager, navigate to the CoE (CAN over EtherCAT) online directory (specifically index 0x80n0) to select the correct thermocouple curve matching your physical sensor. By default, the module is configured for Type K thermocouples. Ensure the shield wire of the thermocouple cable is correctly terminated at the M12 connector casing to establish a continuous path to local ground, minimizing common-mode interference on the low-signal mV inputs.

Installation Guidelines

CRITICAL WARNING

Ensure all power sources (US and UP) are completely de-energized before mounting, grounding, or connecting signal lines to the device. Failing to disable live power lines can cause permanent transceiver failure or damage the sensitive analog conversion circuitry on the thermocouple input channels.

1
Securely mount the EtherCAT Box onto a flat, vibration-resistant surface using two M3 bolts through the pre-drilled integrated mounting holes.
2
Connect the local functional earth grounding wire to the ground lug on the module casing to ensure proper shielding performance.
3
Attach shielded M8 EtherCAT communication cables and M12 thermocouple sensors, tightening all connectors to their designated torque spec to preserve the IP67 integrity.

Which thermocouple sensor types are compatible with this module?

This module supports thermocouple types J, K, L, B, E, N, R, S, T, and U. It can also be configured to measure raw millivolt (mV) voltages directly.

What is the differences between the ER3314-0002 and the EP3314-0002?

The ER series features a rugged zinc die-cast housing designed for high-stress mechanical environments, while the EP series uses a light-weight plastic housing. Their electrical specifications and TwinCAT configurations are identical.

How do I change the default sensor type from Type K to Type J?

You can change the sensor type by writing to the corresponding CoE (CAN over EtherCAT) directory index (0x80n0) via the TwinCAT System Manager software.

What is the default conversion rate of the thermocouple inputs?

The default conversion time is approximately 250 ms, but it is software-configurable within a range of 2.5 seconds down to 20 ms depending on your filtering needs.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

OpenVMS Alpha üzərində işləyən Bailey INFI 90 Symphony HMI-lərinin müasirləşdirilməsi

OpenVMS Alpha üzərində işləyən köhnəlmiş Bailey Symphony operator stansiyalarını əvəz etmək üçün praktik bələdçi. Bu, Alpha emulyasiyasını, OpenVMS x86 miqrasiyasını, OPC yenidən...

Sənaye Etibarlılığı üçün Baxım Məlumatının Əhəmiyyəti

Texniki xidmət məlumatları iş sifarişlərini, sensor siqnallarını, aktivlərin tarixçəsini, xərcləri və texniklərin biliklərini birləşdirir. Düzgün istifadə edildikdə, planlaşdırmanı, etibarlılığı,...

Maye Güc Sistemlərini Əvəz Etmək Üçün Dizayn Edilmiş Elektrik Aktuatorları: Praktik Sənaye Avtomatlaşdırma Bələdçisi

Bu məqalə SMC-nin e-Actuator seriyası kimi inteqrasiya olunmuş elektrik aktuatorlarının ənənəvi pnevmatik və hidravlik sistemləri əvəz etməklə sənaye hərəkət nəzarətini necə dəyişdirdiyini izah edir....

Sənaye Avtomatlaşdırma Tətbiqləri üçün OpenPLC ilə Riyazi Əməliyyatlar

Bu məqalə PLC sistemlərinin sənaye avtomatlaşdırmasında toplama, çıxma, vurma, bölmə, modulo və qüvvətə qaldırma kimi əsas riyazi əməliyyatları necə yerinə yetirdiyini izah edir. Məqalədə bu...

FBD PLC Proqramlaşdırmada Təkmil Boolean Məntiqi: Əsas Məntiqdən Kənar Praktiki Sənaye Tətbiqləri

Məqalə, PLC proqramlaşdırmada əsas AND, OR və NOT əməliyyatlarından kənar istifadə olunan bir neçə inkişaf etmiş Boolean məntiq funksiyalarını izah edir. O, Həqiqət cədvəlləri, çoxlayıcılar, impuls...

PLC Proqramlaşdırmada Boolean Məntiqi: FBD Məntiq Qapılarını Anlamaq

Boolean məntiqi hər bir PLC proqramının əsasını təşkil edir. Sadə maşın idarəetmələrindən mürəkkəb sənaye avtomatlaşdırma sistemlərinə qədər, məntiq qapıları nəzarətçilərin dəyişən girişlərə və...