1 of 1

Omron NS5-SQ00B-V2 NS Series Interactive Display Panel

Omron NS5-SQ00B-V2 NS Series Interactive Display Panel

Only 3 item(s) left in stock
  • Manufacturer: Omron

  • Product No.: NS5-SQ00B-V2

  • Country of origin:Japan

  • Product Type: HMI Operator Panels

  • Payment: T/T, Western Union

  • Weight: 1000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Designed for industrial machine-level visualization, the Omron NS5-SQ00B-V2 serves as a high-reliability interactive human-machine interface (HMI) within modern automation architectures. This panel bridges the communication gap between operators and PLCs, providing responsive touch control and reliable diagnostic displays. Configured with an energy-efficient display system, it operates seamlessly under demanding factory conditions while maintaining a low thermal signature inside electrical control panels.

Key Features

  • Stable Input Power: Optimised for 24 VDC standard industrial distribution networks.
  • Low Power Footprint: Consumes a maximum of 15 W, reducing heat dissipation within sealed enclosures.
  • Long-Term Data Integrity: Integrated memory backup battery features a nominal 5-year service life.
  • Environmental Protection: Built to withstand standard operational wear in environments clear of corrosive gases.

Applications

  • Automated assembly and packaging machinery interfaces.
  • Local control stations in water treatment and material handling facilities.
  • Process visualization terminals in food processing and manufacturing environments.

Technical Specifications

Parameter Specification
Manufacturer Omron
Model Number NS5-SQ00B-V2
Device Type Interactive Display Panel (HMI)
Rated Voltage 24 VDC
Power Consumption 15 W maximum
Operating Environment No corrosive gases
Memory Backup Battery Life 5 years
Net Weight 1.0 kg
Shipping Weight 8.0 kg (including protective packaging)

Empirical Engineering Insights

Alternative Models & Compatibility

The -V2 designation marks a hardware revision that expands screen transfer capabilities and improves direct communication driver support for newer CJ2 and NJ/NX controllers compared to legacy V1 or non-suffix NS5 hardware. Screen files developed in CX-Designer can be easily converted and downloaded, but ensure the target system's system program (firmware) is updated to the matching runtime version of the project.

Application Pitfalls & Engineering Notes

Sustained operation in environments exceeding 40 degC significantly shortens the lifespan of both the screen backlight and the internal backup battery. If mounting within airtight enclosures alongside heat-generating components like active variable speed drives, install supplementary panel cooling or fan systems to prevent localized thermal degradation.

Commissioning & Wiring Tips

When wiring serial communications, use high-quality, individually shielded twisted-pair cables for the RS-232C connections to prevent noise coupling. Avoid routing communication lines parallel to high-current motor leads or power supply distribution cables within the wire ducts to ensure reliable high-speed data transmission.

Installation Guidelines

CRITICAL WARNING: ELECTRICAL SHOCK HAZARD

Isolate and lock out all incoming 24 VDC power sources before mounting, wiring, or replacing the backup battery on this unit. Verify the complete absence of voltage with a calibrated instrument before beginning manual tasks to prevent personal injury or hardware destruction.

1

Prepare a precise panel cutout matching the specified mounting dimensions for the 5.7-inch NS5 chassis.

2

Insert the HMI unit into the cutout, ensuring the integrated waterproof rubber sealing gasket is seated uniformly flat against the front surface of the panel.

3

Secure the panel in position using the provided mounting brackets, tightening them evenly to the specified torque to maintain environmental sealing ratings without warping the front bezel.

4

Connect the dedicated functional ground terminal on the rear of the device to a verified low-impedance facility grounding bar using a minimum 2.0 sq mm copper wire.

What is the expected backup battery lifespan for this HMI and how is it replaced?

The integrated memory backup battery has a typical service life of 5 years when operated under standard conditions. It can be replaced from the rear compartment of the panel while the system is powered down, though a quick swap is recommended to prevent the loss of internal system settings.

Does the NS5-SQ00B-V2 support direct EtherNet/IP communications?

This model relies on serial RS-232C interfaces for its primary communication channels. To utilize Ethernet-based networking protocols, a compatible expansion network board or an external adapter must be integrated.

What software is required to program and transfer screens to this display panel?

The panel is programmed using CX-Designer, which is a core utility included within Omron's CX-One automation software suite. Screens can be transferred via a standard USB connection or the serial ports.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Maye Güc Sistemlərini Əvəz Etmək Üçün Dizayn Edilmiş Elektrik Aktuatorları: Praktik Sənaye Avtomatlaşdırma Bələdçisi

Bu məqalə SMC-nin e-Actuator seriyası kimi inteqrasiya olunmuş elektrik aktuatorlarının ənənəvi pnevmatik və hidravlik sistemləri əvəz etməklə sənaye hərəkət nəzarətini necə dəyişdirdiyini izah edir....

Sənaye Avtomatlaşdırma Tətbiqləri üçün OpenPLC ilə Riyazi Əməliyyatlar

Bu məqalə PLC sistemlərinin sənaye avtomatlaşdırmasında toplama, çıxma, vurma, bölmə, modulo və qüvvətə qaldırma kimi əsas riyazi əməliyyatları necə yerinə yetirdiyini izah edir. Məqalədə bu...

FBD PLC Proqramlaşdırmada Təkmil Boolean Məntiqi: Əsas Məntiqdən Kənar Praktiki Sənaye Tətbiqləri

Məqalə, PLC proqramlaşdırmada əsas AND, OR və NOT əməliyyatlarından kənar istifadə olunan bir neçə inkişaf etmiş Boolean məntiq funksiyalarını izah edir. O, Həqiqət cədvəlləri, çoxlayıcılar, impuls...

PLC Proqramlaşdırmada Boolean Məntiqi: FBD Məntiq Qapılarını Anlamaq

Boolean məntiqi hər bir PLC proqramının əsasını təşkil edir. Sadə maşın idarəetmələrindən mürəkkəb sənaye avtomatlaşdırma sistemlərinə qədər, məntiq qapıları nəzarətçilərin dəyişən girişlərə və...