1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

The Allen-Bradley 1746-OA8 and 1746-OA16 are SLC 500 AC output modules. Both switch 85–265 V AC loads, but their point count and current limits differ.

Technical comparison

Specification 1746-OA8 1746-OA16
Outputs 8 16
Points per common 4 8
Operating voltage 85–265 V AC, 47–63 Hz 85–265 V AC, 47–63 Hz
Backplane current at 5 V DC 0.185 A 0.370 A
Maximum continuous current per point at 30 °C 1.0 A 0.50 A
Maximum continuous current per point at 60 °C 0.50 A 0.25 A
Maximum continuous current per module at 30 °C 8.0 A 8.0 A
Maximum continuous current per module at 60 °C 4.0 A 4.0 A
Maximum signal delay, resistive load 1 ms on; 11 ms off 1 ms on; 11 ms off
Maximum off-state leakage 2 mA 2 mA
Minimum load current 10 mA 10 mA

Check point current before increasing density

The 1746-OA8 permits twice the per-point current of the 1746-OA16 at the same ambient temperature.

The module-level limit is the same for both catalog numbers. A 16-point replacement therefore needs a load-by-load current check, not only a total-current calculation.

Backplane and wiring checks

  • Allow 0.370 A at 5 V DC for the 1746-OA16, compared with 0.185 A for the 1746-OA8.
  • Confirm the common grouping: four points per common on the OA8 and eight on the OA16.
  • Check each load against the temperature-derated point limit.
  • Verify minimum load current and off-state leakage for small relays or indicators.
  • Retain the original terminal schedule before moving conductors.

Primary source

Rockwell Automation publication 1746-IN027D-EN-P, “SLC 500 Digital I/O Modules Installation Instructions,” December 2012, pages 36–37.