1 от 1

Beckhoff IP2001-B518 Fieldbus Box 8-Channel Digital Output Module

Beckhoff IP2001-B518 Fieldbus Box 8-Channel Digital Output Module

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: IP2001-B518

  • Country of origin:Германия

  • Product Type: Fieldbus I/O Modules

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 30 mm x 210 mm x 26.5 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Количество
Покажи пълните подробности

Description

Engineered for decentralized automation architectures, the Beckhoff IP2001-B518 establishes direct, field-level digital actuation via the CANopen protocol. This high-density, IP67-rated Fieldbus Box permits the direct connection of up to eight digital actuators to a high-speed CAN network, negating the need for protective electrical enclosures. Each of the eight outputs delivers up to 0.5 A at 24 V DC, making it suitable for driving solenoid valves, contactors, indicators, and small DC motors under demanding ambient environments.

Features

  • 8 Digital Outputs: Standard 24 V DC switching logic with individual short-circuit protection.
  • Direct CANopen Integration: Built-in node management supporting life/node guarding, emergency objects, and variable PDO mapping.
  • Integrated T-Connector: Dual M12 fieldbus interfaces simplify daisy-chaining without external junction blocks.
  • Submersible Enclosure: Encapsulated PA6 polyamide housing rated for IP65, IP66, and IP67 protection zones.
  • Compact M8 Actuator Ports: Space-optimized termination for industrial sensors and actuator cables.

Applications

  • Machine-mount control systems omitting local terminal boxes.
  • Material handling systems and modular conveyor networks.
  • Pneumatic valve manifold control in food processing and packaging machinery.
  • Mobile equipment and material transport systems utilizing CANopen system buses.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation GmbH & Co. KG
Model Number IP2001-B518
Fieldbus Protocol CANopen (up to 16 send/receive PDOs)
Baud Rate Detection Automatic: 10 kbaud to 1 Mbaud
Number of Outputs 8 digital outputs
Output Voltage 24 V DC (-15% / +20%)
Maximum Output Current 0.5 A per channel (individually short-circuit proof)
Short-Circuit Current Limit Typical 1.5 A
Bus Interface Connectors 1 x M12 plug (5-pin), 1 x M12 socket (5-pin) integrated T-connector
Power Supply Connection Feed: 1 x M8 male (4-pin); Downstream: 1 x M8 female (4-pin)
Internal Current Consumption 45 mA from Us + sensor load (max 0.5 A)
Isolation Voltage 500 V (Control voltage to fieldbus logic)
Ingress Protection Rating IP65 / IP66 / IP67 (conforming to EN 60529)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Housing Material PA6 Polyamide
Dimensions (W x H x D) 30 mm x 210 mm x 26.5 mm
Country of Origin Germany
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Connector Type Pin Allocation Signal Assignment
M12 CANopen Bus (Plug/Socket) Pin 1 CAN Shield / PE
Pin 2 V+ (CAN Bus Power Supply)
Pin 3 V- (CAN Bus Reference Ground)
Pin 4 CAN_H (Signal High)
Pin 5 CAN_L (Signal Low)
M8 Power Feed (4-Pin Male) Pin 1 +24 V DC Control Voltage (Us)
Pin 2 +24 V DC Load Voltage (Up)
Pin 3 GND Control (GNDs)
Pin 4 GND Load (GNDp)

Alternative Models & Compatibility

The IP2001-B518 is fully compatible with the Beckhoff KS2000 configuration software for parameterization and monitoring. When replacing legacy IP2001-B510 modules, verify standard network address switch settings and register maps, as the B518's integrated T-connector structure limits the need for external network splitting hardware.

Application Pitfalls & Engineering Notes

While the module features a total load-handling capacity of up to 4 A across all 8 channels, total heat dissipation within highly confined non-ventilated spaces must be modeled carefully. Additionally, when switching highly inductive loads, such as large pneumatic solenoid coils, external suppressor circuits or free-wheeling diodes should be placed at the load to protect the internal short-circuit monitoring circuitry from inductive kickback transients.

Commissioning & Wiring Tips

Always ensure that the CANopen network is terminated with 120-Ohm resistors at both physical endpoints of the trunk line. Use high-quality, shielded copper twisted-pair cabling for connection to the integrated M12 T-connector interface to avoid data frame corruption in environments with heavy variable frequency drive (VFD) interference.

Installation Guidelines

CRITICAL WARNING:

De-energize all primary system power loops (Us and Up) before inserting, removing, or wiring the Fieldbus Box. Failure to remove supply lines can trigger catastrophic bus controller faults or damage the short-circuit protection profiles of the outputs.

1

Mount the housing to a rigid surface using the two integrated 3.5 mm diameter fixing holes designed for M3 screws.

2

Route the CANopen bus topology through the integrated M12 T-connector, confirming secure hand-tightening of mating connectors to preserve the IP67 seal rating.

3

Connect the 4-pin M8 power feed cable. Ensure separation of control logic voltage (Us) and output load voltage (Up) lines if diagnostic separation is required.

Can the outputs of the IP2001-B518 be connected in parallel to increase drive current?

No, connecting output channels in parallel to drive larger loads is not supported. The internal short-circuit and overload protection algorithms monitor individual channel profiles and will trip due to unequal load balancing.

What is the purpose of the integrated T-connector on the CANopen interface?

The integrated M12 T-connector allows fieldbus cabling to daisy-chain directly into and out of the module without requiring external multi-port junctions, maintaining physical topology continuity even if a drop cable is disconnected.

Does this module require a separate configuration file for deployment?

Yes, network integration inside a CANopen master configuration tool requires the matching EDS (Electronic Data Sheet) file provided by Beckhoff for the IP2001-B518 series.

How does the short-circuit protection operate on the outputs?

Each output is individually protected. If a short-circuit occurs, the output current is limited to approximately 1.5 A. The module logs the diagnostic event and safely disables the faulted channel while other outputs remain operational.

Глобална експресна доставка

  • Стандартна доставка: 4-6 работни дни чрез DHL, FedEx и UPS.
  • Експресна изпращане: Изпращане в същия ден за налични поръчки, направени преди 14:00 ч. (GMT+8).
  • Глобално покритие: Обслужваме над 150 държави, включително бърза доставка до Саудитска Арабия и ОАЕ.

Връщания и гаранция

  • 30-дневна гаранция: Връщания се приемат за налични продукти в оригинална, фабрично запечатана опаковка.
  • 12-месечна гаранция: Всеки индустриален компонент е подкрепен с нашата професионална техническа гаранция.

Поръчките се обработват и доставят от понеделник до петък (с изключение на официалните празници).


За пълна информация относно допустимост, такси за презареждане и международни връщания, моля, разгледайте нашия официален Политика за възстановяване и връщане .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Наскоро разгледани продукти

Технически знания

Електрически задвижващи механизми, проектирани да заменят хидравлични и пневматични системи: Практическо ръководство за индустриална автоматизация

Тази статия обяснява как интегрираните електрически задвижвания, като серията e-Actuator на SMC, трансформират индустриалното управление на движението, като заменят традиционните пневматични и...

Математически операции с OpenPLC за индустриални автоматизационни приложения

Тази статия обяснява как PLC системите изпълняват основни математически операции като събиране, изваждане, умножение, деление, модуло и степенуване в индустриалната автоматизация. Показва как тези...

Разширена булева логика с FBD PLC програмиране: Практически индустриални приложения отвъд основната логика

Статията обяснява няколко усъвършенствани булеви логически функции, използвани в програмирането на PLC, извън основните операции AND, OR и NOT. Тя разглежда как инструменти като таблици на...

Булева логика в програмирането на PLC: Разбиране на логическите врати в FBD

Булевата логика е основата на всяка програма за PLC. От прости машинни управления до сложни индустриални автоматизационни системи, логическите врати определят как контролерите реагират на променящите...

Подробно ръководство за индустриални защитни стени и сегментиране на OT мрежи

Индустриалните защитни стени играят ключова роля в киберсигурността на OT, като защитават мрежите PLC, DCS и SCADA чрез сегментация, контрол на входящия/изходящия трафик и интеграция на IDS/IPS в...

Ръководство за роботизирани захвати: от деликатно боравене до тежка автоматизация

Съвременните роботизирани захвати се развиват отвъд традиционните механични челюсти. От системи с лепкави повърхности, вдъхновени от геконите, и меки захвати за хранителни продукти до инструменти за...