1 от 3

Bently Nevada 21504-12-28-10-02 7200 Series 8 mm Standard Mount Proximity Probe

Bently Nevada 21504-12-28-10-02 7200 Series 8 mm Standard Mount Proximity Probe

Only 4 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 21504-12-28-10-02

  • Country of origin:Съединени щати

  • Product Type: 5 mm and 8 mm Standard Mount Probe

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 120g

  • Dimensions: 20.4cm x 22.2cm x 3.7cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Количество
Покажи пълните подробности

Description

21504-12-28-10-02 specifies this 7200 Series 8 mm Standard Mount Proximity Probe configuration, featuring a 3/8-24 UNF-2A thread, 1.2 inches of unthreaded length, 2.8 inches of overall case length, a 1.0-meter integral coaxial cable, and a miniature male coaxial connector.

Unlike the armored 21505 probe series, this 21504 model does not feature stainless steel lead armor, making it suitable for routing inside conduit or protective machinery enclosures where mechanical abrasion risks are minimal. Additionally, its 1.2-inch unthreaded length (Option 12) combined with the 2.8-inch case length (Option 28) leaves a threaded length of 1.6 inches for bracket depth adjustment, supporting proper gap calibration with the target surface.

Features

  • 8 mm tip diameter constructed of polyphenylene sulfide (PPS) plastic to withstand harsh, wet, or chemical environments.
  • 3/8-24 UNF-2A English thread configuration for robust standard-mount installations.
  • 1.2 inches (30.5 mm) unthreaded length (Option 12) to accommodate specific bracket recess depths.
  • 2.8 inches (71.1 mm) overall case length (Option 28) providing 1.6 inches of threaded casing.
  • 1.0-meter (39 inches) integral 95-ohm coaxial cable length (Option 10) for direct connection to an extension cable.
  • Miniature male coaxial connector (Option 02) designed for low-impedance signal transmission.
  • Non-armored design for installations where external conduit protection is already provided.

Applications

  • Radial shaft vibration measurement for evaluating fluid-film bearing condition, rotor imbalance, and misalignment.
  • Axial shaft position monitoring to detect thrust bearing wear or potential machine failure.
  • Shaft average radial position determination for indicating attitude angle and rotor stability.
  • Vibration amplitude and phase angle acquisition for Polar and Bode diagnostic plots.
  • Rotor eccentricity measurement to evaluate shaft bow prior to machine startup.

Ordering Information

Option Segment Code on This SKU Description
Orderable Part Number 21504-12-28-10-02 7200 Series 8 mm Standard Mount Proximity Probe, 3/8-24 UNF thread, non-armored
A - Unthreaded Length 12 1.2 inches (30.5 mm) unthreaded length
B - Overall Case Length 28 2.8 inches (71.1 mm) overall case length
C - Total Cable Length 10 1.0 meter (39 inches) total cable length
D - Connector Option 02 With miniature male coaxial connector

Technical Specifications

Parameter Specification Value
Manufacturer Bently Nevada (Baker Hughes)
Part Number 21504-12-28-10-02
Transducer Type 7200 Series 8 mm Proximity Probe
Tip Diameter 8 mm
Thread Type 3/8-24 UNF-2A
Unthreaded Length 1.2 inches (30.5 mm)
Overall Case Length 2.8 inches (71.1 mm)
Total Lead Cable Length 1.0 meter (39 inches)
Connector Type Miniature male coaxial connector
Lead Armor No (unarmored)
Calibrated Linear Range 80 mils (2.0 mm), begins at approx 10 mils (0.25 mm) from probe face
Scale Factor 200 mV/mil (7.87 V/mm)
System Compatibility Bently Nevada 3300 and 9000 Monitoring Systems
Frequency Response 0 Hz to 10 kHz; -5% at 10 kHz
Probe Tip Material Polyphenylene sulfide (PPS)
Probe Case Material Stainless steel
Operating Temperature -30 to +350 degF (-34 to +177 degC)
Humidity Limit To 95%, noncondensing
Cable Impedance 95 ohm

Connections and Interfaces

This proximity probe is equipped with an integral 1.0-meter 95-ohm coaxial cable terminated with a miniature male coaxial connector. It connects directly to a 7200 Series extension cable to establish a total system length of either 5 or 9 meters back to the Proximitor Sensor.

Installation Guidelines

  • Ensure the unthreaded length (1.2 inches) is at least 0.8 inches less than the overall case length (2.8 inches). This configuration provides a threaded length of 1.6 inches, meeting the clearance requirement.
  • Use a standard thread jam nut to secure the standard-mount probe in place once final gapping is achieved.
  • Adjust the gap to the center of the calibrated linear range (typically 50 mils or 1.27 mm) to achieve optimal vibration and position measurement.
  • Ensure connection points are clean and dry. Use protective sleeves where connections are exposed to industrial fluids.
  • Do not exceed the minimum bend radius of the coaxial cable during routing.

Compliance and Certifications

Most Bently Nevada 7200 Series proximity transducers are certified by major regulatory bodies (including CSA, BASEEFA, and FM) for use in hazardous environments. For detailed installation wiring diagrams and intrinsic safety parameters, consult the official Bently Nevada systems for hazardous locations documentation.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 21504-12-28-10-02 7200 Series 8 mm Standard Mount Proximity Probe

What are the specific case dimensions of the Bently Nevada 21504-12-28-10-02 probe?

This probe features a 3/8-24 UNF-2A thread, an unthreaded length of 1.2 inches (Option 12), and an overall case length of 2.8 inches (Option 28).

Does this 21504 probe configuration include stainless steel lead armor?

No, this configuration has an unarmored coaxial cable (Option 10). If stainless steel armor is required, the 21505 series should be selected instead.

What cable length and connector are provided on this model?

This probe has a 1.0-meter (39 inches) integral coaxial cable (Option 10) terminated with a miniature male coaxial connector (Option 02).

What is the linear range and scale factor of this 7200 Series 8 mm probe?

The probe offers an 80 mil (2.0 mm) calibrated linear range with a nominal scale factor of 200 mV/mil (7.87 V/mm) when used as a system.

Глобална експресна доставка

  • Стандартна доставка: 4-6 работни дни чрез DHL, FedEx и UPS.
  • Експресна изпращане: Изпращане в същия ден за налични поръчки, направени преди 14:00 ч. (GMT+8).
  • Глобално покритие: Обслужваме над 150 държави, включително бърза доставка до Саудитска Арабия и ОАЕ.

Връщания и гаранция

  • 30-дневна гаранция: Връщания се приемат за налични продукти в оригинална, фабрично запечатана опаковка.
  • 12-месечна гаранция: Всеки индустриален компонент е подкрепен с нашата професионална техническа гаранция.

Поръчките се обработват и доставят от понеделник до петък (с изключение на официалните празници).


За пълна информация относно допустимост, такси за презареждане и международни връщания, моля, разгледайте нашия официален Политика за възстановяване и връщане .

TECHNICAL SPECIFICATIONS

Country of origin
Съединени щати

Наскоро разгледани продукти

Технически знания

Електрически задвижващи механизми, проектирани да заменят хидравлични и пневматични системи: Практическо ръководство за индустриална автоматизация

Тази статия обяснява как интегрираните електрически задвижвания, като серията e-Actuator на SMC, трансформират индустриалното управление на движението, като заменят традиционните пневматични и...

Математически операции с OpenPLC за индустриални автоматизационни приложения

Тази статия обяснява как PLC системите изпълняват основни математически операции като събиране, изваждане, умножение, деление, модуло и степенуване в индустриалната автоматизация. Показва как тези...

Разширена булева логика с FBD PLC програмиране: Практически индустриални приложения отвъд основната логика

Статията обяснява няколко усъвършенствани булеви логически функции, използвани в програмирането на PLC, извън основните операции AND, OR и NOT. Тя разглежда как инструменти като таблици на...

Булева логика в програмирането на PLC: Разбиране на логическите врати в FBD

Булевата логика е основата на всяка програма за PLC. От прости машинни управления до сложни индустриални автоматизационни системи, логическите врати определят как контролерите реагират на променящите...

Подробно ръководство за индустриални защитни стени и сегментиране на OT мрежи

Индустриалните защитни стени играят ключова роля в киберсигурността на OT, като защитават мрежите PLC, DCS и SCADA чрез сегментация, контрол на входящия/изходящия трафик и интеграция на IDS/IPS в...

Ръководство за роботизирани захвати: от деликатно боравене до тежка автоматизация

Съвременните роботизирани захвати се развиват отвъд традиционните механични челюсти. От системи с лепкави повърхности, вдъхновени от геконите, и меки захвати за хранителни продукти до инструменти за...