1 от 1

Weidmuller 1469520000 PRO ECO 960W 24V 40A Switch-mode Power Supply Unit

Weidmuller 1469520000 PRO ECO 960W 24V 40A Switch-mode Power Supply Unit

Only 10 item(s) left in stock
  • Manufacturer: Weidmuller

  • Product No.: PRO ECO 960W 24V 40A

  • Country of origin:Германия

  • Product Type: DIN Rail Power Supplies

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 160 mm x 125 mm x 120 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Количество
Покажи пълните подробности

Engineered for high-capacity DC power distribution in demanding industrial environments, the Weidmuller 1469520000 (Model: PRO ECO 960W 24V 40A) switch-mode power supply unit delivers a regulated 24 V DC output at up to 40 A. This robust DIN-rail mountable module combines a compact form factor with 93% operational efficiency, minimizing thermal load inside control cabinets and ensuring stable power delivery to PLCs, HMIs, and field actuators.

Key Features

  • High Operational Efficiency: Achieves up to 93% efficiency, significantly reducing energy dissipation and cabinet heat buildup.
  • Wide Input Range: Supports universal AC input from 85 to 264 V AC and DC input from 80 to 370 V DC for global compatibility.
  • Tri-Color LED Diagnostics: Real-time status monitoring via Green (Uoutput > 21.6 V DC), Yellow (Ioutput > 90% rated), and Red (overload, short-circuit, or overtemperature) indicators.
  • Parallel Capability: Supports direct parallel connection of up to 3 units to scale current capacity or establish redundant power architectures.
  • Robust Protection Suite: Integrated varistor surge protection, short-circuit protection, overload protection, and thermal shutdown.

Industrial Applications

  • Factory Automation: Centralized 24 V DC power distribution for PLC racks, I/O drops, and industrial PCs.
  • Process Control Systems: Reliable power source for transmitters, solenoid valves, and safety barriers in continuous process plants.
  • Machine Building: Heavy-duty power supply for packaging, material handling, and CNC machinery control panels.
  • Water and Wastewater: Robust power infrastructure for outdoor telemetry and pump control stations.

Ordering Information

Order Number Type Designation GTIN / EAN Standard Package Qty
1469520000 PRO ECO 960W 24V 40A 4050118275704 1 pc(s).

Technical Specifications

Manufacturer Weidmuller
Series PROeco
Rated Output Voltage 24 V DC ± 1 % (adjustable 22 to 28 V DC via potentiometer)
Continuous Output Current 40 A @ 50 degC / 24 A @ 70 degC
Output Power 960 W
AC Input Voltage Range 85 to 264 V AC (derating required below 100 V AC)
DC Input Voltage Range 80 to 370 V DC (derating required below 120 V DC)
AC Current Consumption 4.6 A @ 230 V AC / 9.9 A @ 110 V AC
Frequency Range AC 47 to 63 Hz
Inrush Current Max. 5 A
Efficiency 93%
Power Loss (Idle / Nominal) 8 W (Idling) / 85 W (Nominal Load)
Connection System Screw connection
Housing Version Metal, corrosion resistant
Operating Temperature -25 degC to 70 degC
Storage Temperature -40 degC to 85 degC
Dimensions (W x H x D) 160 mm x 125 mm x 120 mm
Net Weight 3190 g
Shipping Weight (Calculated) 3.5 kg

Diagnostic LED Status Mapping

LED Color Status / Threshold Operational Meaning
Green Uoutput > 21.6 V DC Normal operation; output voltage within acceptable limits.
Yellow Ioutput > 90% IRated typ. High load warning; output current is approaching maximum capacity.
Red Uoutput < 20.4 V DC Fault condition; overload, overtemperature, short-circuit, or low voltage.

Empirical Engineering Insights

Alternative Models & Compatibility

The PROeco series is designed as a highly space-efficient and cost-effective alternative to Weidmuller's premium PROmax and PROtop series. When replacing older 40 A power supplies, verify the 160 mm width footprint on the TS 35 rail, as high-power units require adequate lateral spacing for heat dissipation.

Application Pitfalls & Engineering Notes

A critical consideration for the PRO ECO 960W is its thermal derating profile. While it delivers a full 40 A at ambient temperatures up to 50 degC, the output capacity derates linearly to 24 A at 70 degC. Operating the unit near its limit in unventilated enclosures will trigger the internal thermal protection, causing output cycling.

Commissioning & Wiring Tips

Due to the high 40 A output current, ensure that output wiring is sized appropriately (minimum 10 AWG / 6 mm² copper wire recommended) to prevent significant voltage drop across the run. When configuring parallel operation for up to 3 units, use a precise digital multimeter to adjust the output voltage of each unit via the front potentiometer to within ±50 mV of each other before tying the outputs together.

Installation Guidelines

CRITICAL WARNING

De-energize all AC and DC power sources before attempting installation, wiring, or maintenance. Ensure the input circuit breaker is locked out. Do not open the metal housing; high residual voltage may remain stored in internal capacitors even after power is disconnected.

1

Snap the unit securely onto a standard TS 35 DIN rail. Ensure the mounting orientation is vertical, with the input terminals at the bottom and output terminals at the top to facilitate natural convection cooling.

2

Maintain a minimum clearance of 50 mm above and below the unit, and 20 mm of lateral clearance from adjacent active heat-producing components.

3

Connect the protective earth (PE) ground terminal first. Wire the AC input (L, N) or DC input terminals using the integrated screw connections, tightening to the manufacturer-specified torque.

4

Connect the 24 V DC load lines to the output terminals, ensuring correct polarity. Energize the input source and verify that the green LED illuminates.

What is the thermal derating behavior of the PRO ECO 960W power supply?

The unit delivers its full rated output of 40 A at ambient temperatures up to 50 degC. Above 50 degC, the output current derates linearly down to 24 A at 70 degC.

Can multiple 1469520000 units be connected in parallel for higher current output?

Yes, up to three units can be connected in parallel to increase current capacity. Ensure the output voltages of all units are calibrated within 50 mV of each other before connection.

What do the three diagnostic LEDs on the front panel indicate?

The Green LED indicates output voltage is above 21.6 V DC. The Yellow LED indicates output current is above 90% of the rated current. The Red LED indicates a fault such as overload, overtemperature, short-circuit, or output voltage below 20.4 V DC.

What are the recommended backup fuses for the input side?

Recommended backup fuses include a 16 A DI safety fuse, a 20 A Character B circuit breaker, or a 16 A Character C circuit breaker.

Глобална експресна доставка

  • Стандартна доставка: 4-6 работни дни чрез DHL, FedEx и UPS.
  • Експресна изпращане: Изпращане в същия ден за налични поръчки, направени преди 14:00 ч. (GMT+8).
  • Глобално покритие: Обслужваме над 150 държави, включително бърза доставка до Саудитска Арабия и ОАЕ.

Връщания и гаранция

  • 30-дневна гаранция: Връщания се приемат за налични продукти в оригинална, фабрично запечатана опаковка.
  • 12-месечна гаранция: Всеки индустриален компонент е подкрепен с нашата професионална техническа гаранция.

Поръчките се обработват и доставят от понеделник до петък (с изключение на официалните празници).


За пълна информация относно допустимост, такси за презареждане и международни връщания, моля, разгледайте нашия официален Политика за възстановяване и връщане .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Наскоро разгледани продукти

Технически знания

Електрически задвижващи механизми, проектирани да заменят хидравлични и пневматични системи: Практическо ръководство за индустриална автоматизация

Тази статия обяснява как интегрираните електрически задвижвания, като серията e-Actuator на SMC, трансформират индустриалното управление на движението, като заменят традиционните пневматични и...

Математически операции с OpenPLC за индустриални автоматизационни приложения

Тази статия обяснява как PLC системите изпълняват основни математически операции като събиране, изваждане, умножение, деление, модуло и степенуване в индустриалната автоматизация. Показва как тези...

Разширена булева логика с FBD PLC програмиране: Практически индустриални приложения отвъд основната логика

Статията обяснява няколко усъвършенствани булеви логически функции, използвани в програмирането на PLC, извън основните операции AND, OR и NOT. Тя разглежда как инструменти като таблици на...

Булева логика в програмирането на PLC: Разбиране на логическите врати в FBD

Булевата логика е основата на всяка програма за PLC. От прости машинни управления до сложни индустриални автоматизационни системи, логическите врати определят как контролерите реагират на променящите...

Подробно ръководство за индустриални защитни стени и сегментиране на OT мрежи

Индустриалните защитни стени играят ключова роля в киберсигурността на OT, като защитават мрежите PLC, DCS и SCADA чрез сегментация, контрол на входящия/изходящия трафик и интеграция на IDS/IPS в...

Ръководство за роботизирани захвати: от деликатно боравене до тежка автоматизация

Съвременните роботизирани захвати се развиват отвъд традиционните механични челюсти. От системи с лепкави повърхности, вдъхновени от геконите, и меки захвати за хранителни продукти до инструменти за...