Description

This primary switch-mode power supply is designed to provide regulated DC power for heavy-duty industrial control and automation architecture. The ABB CP-C.1 24/20.0 (Product ID: 1SVR360763R1001) delivers a stable 24 V DC output at 20 A from a versatile single-phase input grid. Engineered with a built-in power reserve of up to 30%, this power supply module effectively accommodates high transient starter currents and fluctuating dynamic loads without disrupting overall system operation. This device integrates smoothly with standard PLC and DCS automation networks requiring continuous duty cycles and precise voltage stability.

Features

  • High-efficiency primary switch-mode design 
  • Wide input voltage range accepting 85-264 V AC and 90-300 V DC 
  • Continuous rated output power of 480 W 
  • U/I output characteristic curve featuring a power reserve up to 30% 
  • Adjustable output voltage range from 22.5 to 28.5 V DC 
  • Active power factor correction complying with EN 61000-3-2 
  • Support for parallel operation to safely extend total capacity or establish a redundant system layout 

Applications

  • Distributed Control Systems (DCS) and Programmable Logic Controllers (PLC) power cabinets 
  • Factory machine automation and critical control loops
  • Power infrastructure for manufacturing plant automation instrumentation

Technical Specifications

Parameter Specification
Manufacturer ABB 
Model Designation CP-C.1 24/20.0 
Product ID 1SVR360763R1001 
EAN 4013614503832 
Function Switch mode power supply 
Number of Phases 1-phase 
Rated Input Voltage (Uin) 100 - 240 V AC / 100... 270 V DC 
Input Voltage Range (Uin boundaries) 85... 264 V AC / 90... 300 V DC 
Typical Input Current 4.6 A at 115 V AC / 2.3 A at 230 V AC 
Rated Frequency (f) 50/60 Hz 
Rated Frequency Limits 45... 65 Hz 
Hold-up Time min. 40 ms at 230 V AC 
Rated Output Power 480 W 
Rated Output Voltage 24 V DC 
Output Voltage Adjustment Range 22.5 ... 28.5 V DC 
Rated Output Current 20 A (at -25 Celsius ... +60 Celsius) / 26 A (at -25 Celsius ... +40 Celsius) 
Output Characteristic U/I characteristic curve with power reserve 
Rated Insulation Voltage (Ui)

Input Circuit / Output Circuit: 300 V


 

Input Circuit / PE: 300 V


 

Input Circuit / Relay Contact: 300 V


 

Output Circuit / PE: 50 V 

Rated Impulse Withstand Voltage (Uimp)

Input Circuit/Output Circuit: 4 kV


 

Input Circuit/PE: 4 kV


 

Input Circuit / Relay Contact: 4 kV


 

Output Circuit / PE: 0.5 kV


 

Output Circuit: 0.5 kV 

Degree of Protection Housing: IP20 / Terminals: IP20 
Pollution Degree
Tightening Torque Input Circuit: 0.5 N-m / Output Circuit: 1.2 N-m / Auxiliary Circuit: 0.5 N-m 
Wire Stripping Length Input Circuit: 8 mm / Output Circuit: 10 mm / Auxiliary Circuit: 8 mm 
Product Net Width 82 mm 
Product Net Height 129.4 mm 
Product Net Depth / Length 136 mm 
Product Net Weight 1.57 kg 
Ambient Air Temperature

Operation: -25 ... +70 Celsius


 

Storage: -40 ... +85 Celsius 

Maximum Operating Altitude Permissible 5000 m 

Connections/Interfaces

Terminal Connection Type Wire Size Connecting Capacity
Connecting Capacity Input Circuit

Flexible with Ferrule: 0.5... 2.5 mm²


 

Flexible: 0.5 ... 2.5 mm²


 

Rigid: 0.5 ... 4 mm² 

Connecting Capacity Output Circuit

Flexible with Ferrule: 2.5... 10 mm²


 

Flexible: 2.5... 10 mm²


 

Rigid: 2.5... 16 mm² 

Connecting Capacity Input Circuit UL/CSA

Flexible/Flexible with Ferrule: 20-12 AWG


 

Rigid: 20-10 AWG 

Connecting Capacity Output Circuit UL/CSA

Flexible: 12-8 AWG


 

Rigid: 12-6 AWG 

Installation Guidelines

DIN Rail Mounting

Install onto standard 35 mm mounting rails (TH35-15 or TH35-7.5) in accordance with IEC 60715. Snap the module firmly into place using mounting positions 1 through 7 to guarantee stability under mechanical vibration.

Minimum Mounting Clearances

To maintain adequate vertical air circulation and minimize physical thermal load transfers, leave a minimum clearance of 25 mm horizontally and vertically from any adjacent electrically conductive board or equivalent equipment of the same unit type.

Wire Termination Requirements

Ensure input connections conform to a tightening torque of 0.5 N-m (4.4 in-lb). Output connections must be tightened securely to 1.2 N-m (10.5 in-lb) to minimize contact resistance and overheating at higher current thresholds.

Compliance and Certifications

  • CAN/CSA C22.2 No.107.1 
  • IEC/EN 63000, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61204, IEC/EN 61010-1 
  • UL 508, UL 61010-1, UL 61010-2-201 
  • ABS (ABS_17-HG1591548-2-PDA) 
  • CB Scheme (CB_DK_103862_A2_UL) 
  • cULus (cULus508_20161102-E174460) 
  • cURus (CURus60950 E196145-A11-UL / CURUSANSI12-12_20161122_E317914-) 
  • CE (1SVD982010-00) 
  • UKCA (1SVD982010-10) 
  • DNV GL (DNV_GL_TAA00000YB_1) 
  • SEMI F47 (SEMI_F47 4787681819-2) 

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

ABB 1SVR427026R0000 CP-C 24/20.0 Power Supply Module

Can the 1SVR427026R0000 handle inductive and high-inrush startup loads?

Yes. This power supply features an integrated 10 percent continuous power reserve, enabling it to deliver up to 22 A instead of the nominal 20 A at temperatures below 40 degC to easily manage short-duration high-inrush loads.

What is the recommended ventilation clearance for the CP-C 24/20.0?

To maintain optimal natural convection cooling, a vertical clearance of at least 80 mm is required on both top and bottom, and a horizontal clearance of 10 mm from other active DIN rail equipment.

Can I configure multiple 1SVR427026R0000 units in redundant parallel operation?

Yes. Multiple units can be operated in parallel. For strict N+1 redundant operation, it is recommended to integrate the external CP-C CO redundancy unit block.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
Sweden

Recently Viewed Products

Technical knowledge

Modernizace HMI Bailey INFI 90 Symphony běžících na OpenVMS Alpha

Praktický průvodce výměnou zastaralých operátorských stanic Bailey Symphony běžících na OpenVMS Alpha. Porovnává emulaci Alpha, migraci OpenVMS na x86, přemostění OPC a postupnou modernizaci ABB.

Proč jsou údaje o údržbě nezbytné pro průmyslovou spolehlivost

Údaje o údržbě propojují pracovní příkazy, signály ze senzorů, historii majetku, náklady a znalosti techniků. Správné využití těchto dat zlepšuje plánování, spolehlivost, prediktivní údržbu, kontrolu...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...