Integrating safety control logic directly into the EtherCAT I/O network, the Beckhoff EK1960-2600 establishes a highly compact safety link between safe digital input and output channels. This TwinSAFE compact controller serves as a standalone safety PLC, managing localized safety logic and executing secure functional operations over networks using the Safety over EtherCAT (FSoE) protocol. Housing 20 safe digital inputs and up to 24 safe digital outputs (including optional potential-free relay contacts) within a single physical form factor, the module optimizes panel space while executing safety tasks up to SIL 3 and PL e standards.

Features

  • High-Density Integrated Safety: Consolidates safety logic, 20 safe inputs, and 24 safe outputs within a unified compact layout.
  • Safety over EtherCAT (FSoE): Directly acts as a master or slave link unit communicating safe state variables over standard Ethernet wiring.
  • Parameterizable Watchdog: Configurable watchdog timer values ensure precise and dynamic fault response time calculations.
  • Hybrid Output Configuration: Built-in provision for safe potential-free make contacts alongside standard 1-wire digital outputs.
  • Standardized Compliance: Meets rigorous global standards up to EN ISO 13849-1:2015 (Cat. 4, PL e) and EN 61508:2010 (SIL 3).

Applications

  • Automated Assembly Lines: Distributed functional safety zoning for emergency stops, light curtains, and interlocking doors.
  • Machine Tool Safety: Interfacing with safety switches and control loops in localized machine centers.
  • Material Handling Systems: Managing safety limits, muting, and zone control across large conveyor operations.
  • Robotics Integration: Centralized processing of safe coordinate limits and emergency stop feedback chains.

Technical Specifications

Parameter / Metric Specification Value
Manufacturer Beckhoff Automation
Model / SKU EK1960-2600
Safety Protocol TwinSAFE / Safety over EtherCAT (FSoE)
Number of Inputs 20 safe digital inputs (24 V DC)
Number of Outputs 24 safe digital outputs (includes 4 potential-free relay make contacts)
Connection Technology 1-wire system
Maximum Output Current 2 A (simultaneity factor 50% at 2 A)
Cycle Time Typically 1 ms (dependent on functional logic project size)
Fault Response Time ≤ watchdog time (parameterizable)
Current Consumption (US / UP) Typ. 80 mA / Typ. 2 mA
Safety Standard Compliance EN ISO 13849-1:2015 (Cat. 4, PL e), EN 61508:2010 (SIL 3)
IP Protection Rating IP20
Interface Connection RJ45 port
Installation Orientation Horizontal
Shipping Weight (Calculated) 1.0 kg

Connections and Interfaces

Terminal / Connection Port Functional Assignment
RJ45 Socket EtherCAT and TwinSAFE network communication interface
Safe Inputs (1 to 20) 1-wire safe sensor digital input connection points (24 V DC)
Safe Outputs (1 to 20) 1-wire safe semiconductor digital output connection points (24 V DC, 2 A)
Relay Outputs (21 to 24) Potential-free safe relay contacts (make contacts)

Empirical Engineering Insights

Alternative Models & Compatibility

Unlike traditional distributed safety architectures where discrete logic modules (such as EL6900) must interface with isolated safety input and output terminals, the EK1960-2600 integrates these blocks into a single piece of hardware. This unit requires TwinCAT 2.11 or higher, featuring the integrated TwinSAFE System Manager, to compile and download functional safety projects. Upgrading standard EtherCAT networks to run with this unit requires no physical changes to structural EtherCAT lines outside of standard addressing configurations.

Application Pitfalls & Engineering Notes

The thermal profile of the compact housing limits the allowable simultaneous load. Even though outputs support up to 2 A currents individually, continuous operation at full current must respect the 50% simultaneity factor constraint. Running more than 12 outputs at 2 A continuously inside unventilated, high-ambient enclosures will lead to internal over-temperature warnings or safety shutdowns.

Commissioning & Wiring Tips

When switching inductive loads (such as heavy contactor coils) with the 4 potential-free relay outputs, always install suppression elements (flyback diodes or RC snubbers) directly across the inductive loads. Voltage spikes generated by unsuppressed coils can induce electromagnetic noise into the logic circuitry of the safety controller, leading to safety diagnostic faults. Use shielded S/FTP cabling for the RJ45 industrial Ethernet connection to isolate the safety communication stream from heavy-current motor drives.

Installation Guidelines

CRITICAL WARNING: Prior to attempting any mechanical installation, terminal wiring, or maintenance of the Beckhoff EK1960-2600, isolate all physical supply power lines from the system. Use a verified, calibrated voltage tester to ensure all system parts are fully de-energized. Failure to execute total isolation can result in dangerous structural electrical shocks, unintended safe output closures, or immediate physical logic damage.
1

Mount the controller horizontally onto a grounded 35 mm DIN rail. Secure the lock mechanism to ensure the device cannot slide or vibrate loose.

2

Verify that ambient air circulation is unhindered around the top and bottom ventilation slots of the IP20 housing.

3

Connect the safe input and output lines using appropriate 1-wire connection practices, taking care not to exceed wire gauge limits for the terminals.

4

Plug the standard RJ45 cable from the EtherCAT network into the Ethernet interface, confirming structural locking. Apply system control logic voltage after checking polarity.

What software is required to program the safe logic on this controller?

Configuration and safety logic programming require TwinCAT 2.11 or higher with the integrated TwinSAFE System Manager environment.

Can standard EtherCAT terminals connect directly to the side of the EK1960-2600?

This unit is designed as a standalone compact controller utilizing RJ45 network lines and onboard I/O, rather than functioning as a standard DIN-rail slice bus coupler.

What does the 50 percent simultaneity factor mean for the safe outputs?

It means that under full load, only half of the 24 safe digital outputs should carry the maximum 2 A current simultaneously to keep thermal levels within limits.

Are the relay outputs on this module potential-free?

Yes, outputs 21 through 24 are potential-free, safe make contacts, meaning they are isolated from internal control voltages.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Modernizace HMI Bailey INFI 90 Symphony běžících na OpenVMS Alpha

Praktický průvodce výměnou zastaralých operátorských stanic Bailey Symphony běžících na OpenVMS Alpha. Porovnává emulaci Alpha, migraci OpenVMS na x86, přemostění OPC a postupnou modernizaci ABB.

Proč jsou údaje o údržbě nezbytné pro průmyslovou spolehlivost

Údaje o údržbě propojují pracovní příkazy, signály ze senzorů, historii majetku, náklady a znalosti techniků. Správné využití těchto dat zlepšuje plánování, spolehlivost, prediktivní údržbu, kontrolu...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...