1 z 1

BECKHOFF KL2828 Digital Output Terminal

BECKHOFF KL2828 Digital Output Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KL2828

  • Country of origin:Germany

  • Payment: T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Množství
Zobrazit veškeré podrobnosti

The KL2828 is an 8-channel digital output terminal manufactured by BECKHOFF, designed for switching 24 V DC actuators in industrial control applications. This Bus Terminal module provides high-density output control, capable of driving ohmic, inductive, or capacitive loads with a maximum current of 2 A per channel, totaling up to 10 A for the entire module. Engineered for durability, the KL2828 includes robust short-circuit protection and reverse voltage protection, ensuring reliable performance in demanding automation environments.

Features

  • 8 digital output channels with 2-wire connection technology
  • Supports ohmic, inductive, and capacitive load types
  • High load capacity: 2 A per channel (10 A total sum current)
  • Integrated short-circuit protection and reverse voltage protection
  • Electrical isolation of 500 V between K-bus and field potential
  • Compact design for vertical installation
  • Plug-and-play operation; no address or configuration settings required

Applications

  • Distributed I/O systems for factory automation
  • High-density actuator control (solenoids, contactors, pilot lamps)
  • Machine and process control signaling
  • Industrial control panels with space constraints

Technical Specifications

Category Specification
Manufacturer BECKHOFF
Model KL2828
Number of Outputs 8
Nominal Voltage 24 V DC (-15 %/+20 %)
Max. Output Current 2 A per channel (10 A sum)
Short-Circuit Current typ. < 40 A
Breaking Energy < 1.2 J/channel
Current Consumption (K-bus) typ. 18 mA
Electrical Isolation 500 V (K-bus/field potential)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Protection Rating IP20
Weight approx. 70 g

Installation Guidelines

  • The terminal is designed for vertical installation on a standard 35 mm DIN rail.
  • Ensure that the total current draw does not exceed 10 A across all 8 channels simultaneously.
  • Use 2-wire connection technology to interface actuators directly with the module.
  • Maintain ambient conditions between -25 and +60 degC to ensure operational longevity.
  • Observe standard EMC guidelines (EN 61000-6-2/EN 61000-6-4) during cable routing and cabinet assembly to minimize interference.

Compliance and Certifications

  • CE
  • UL

What is the maximum current rating per channel for the KL2828?

Each channel is rated for a maximum output current of 2 A, with a total sum current limit of 10 A for the entire module.

Does this terminal require configuration via software?

No, the KL2828 does not require any address or configuration settings; it operates as a plug-and-play device.

What types of loads can be connected to this module?

The module is designed to handle ohmic, inductive, and capacitive loads.

What is the required installation orientation for this terminal?

This module is designed for vertical installation to maintain specified thermal and operational performance.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
White
Country of origin
Germany
Power source
DC Power

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...