1 z 1

BECKHOFF KS4004 KS Series Bus Terminal

BECKHOFF KS4004 KS Series Bus Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KS4004

  • Country of origin:Germany

  • Product Type: Bus Terminals

  • Payment: T/T, Western Union

  • Weight: 85g

  • Dimensions: 6.8 cm x 1.2 cm x 10.0 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Množství
Zobrazit veškeré podrobnosti

Description

The KS4004 analog output terminal is designed to generate highly accurate analog signals within the range of 0 to 10 V. Engineered as part of the Beckhoff KS series, this 4-channel module features a pluggable wiring level that permits swift replacement during maintenance without disconnecting active field wiring. The terminal processes electrical signals with a resolution of 12 bits and transfers them, electrically isolated, to the process level. The power required to operate the module is drawn directly from the K-bus, eliminating the need for separate external power contacts.

This single-ended output terminal is optimized for compact control cabinets where high-density analog output signals and quick-disassembly capabilities are critical. With built-in short-circuit protection and an exceptionally low output error margin, the KS4004 guarantees stable command signal delivery to actuator drives, control valves, and other analog-driven field devices in complex process environments.

Features

  • Four analog output channels with a 0 to 10 V signal range.
  • Pluggable connection level for easy installation and tool-free module swap-outs.
  • Internal power supply driven directly via the Beckhoff K-bus interface.
  • Short-circuit proof outputs designed to handle loads greater than 5 kOhm.
  • High-accuracy performance with a relative output error of less than +/-0.1 % of the full-scale value.
  • No address or hardware configuration required prior to deployment.

Applications

  • Industrial positioning systems and actuator control loops.
  • Variable frequency drive (VFD) speed reference signaling.
  • HVAC dampers and climate control system modulation.
  • Standard machine building and process plant automation.

Technical Specifications

ManufacturerPart Number / ModelTechnologyNumber of OutputsPower SupplySignal VoltageLoadOutput ErrorResolutionConversion TimeElectrical IsolationCurrent Consumption K-BusCurrent Consumption Power ContactsBit Width in Process ImageOperating TemperatureStorage TemperatureRelative HumidityVibration and Shock ResistanceEMC Immunity and EmissionProtection RatingDesignMaterialInstallationDimensions (L x W x H)Weight
BECKHOFF
KS4004
Single-ended
4
Via the K-bus
0 to 10 V
> 5 kOhm (short-circuit proof)
< +/-0.1 % (relative to end value)
12 bit
Approx. 2 ms
500 V (K-bus/signal voltage)
Typ. 85 mA
None (no power contacts)
Output: 4 x 16 bit data (optional 4 x 8 bit control/status)
0 to +55 degC
-25 to +85 degC
95 %, no condensation
Conforms to EN 60068-2-6 / EN 60068-2-27
Conforms to EN 61000-6-2 / EN 61000-6-4
IP20 (variable installation position)
Terminal housing with pluggable wiring level
Polycarbonate
35 mm DIN rail (conforming to EN 60715) with lock
6.8 cm x 1.2 cm x 10.0 cm
0.085 kg

Connections and Interfaces

Wiring MethodSolid Wire Cross-SectionStranded Wire Cross-SectionFine-Wire Cross-SectionStripping Length
Connection Property Specification
Spring actuation by screwdriver
0.08 to 1.5 mm² (AWG 28 to 16)
0.08 to 1.5 mm² (AWG 28 to 16)
0.14 to 1.5 mm² (AWG 26 to 16)
9 to 10 mm

Installation Guidelines

  • Mount the module vertically or horizontally on a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking slide mechanism snaps securely into place.
  • To prevent electromagnetic interference on sensitive 0-10 V analog lines, use shielded cables and connect the shield to a low-resistance ground terminal near the entry point of the control panel.
  • Ensure that no field wiring is connected when plugging or unplugging the terminal wiring level to avoid transient electrical spikes.

Compliance and Certifications

  • CE
  • UL
  • ATEX: II 3 G Ex nA IIC T4 Gc

What is the primary difference between Beckhoff KS and KL series terminals?

The KS series terminals (such as the KS4004) feature a pluggable connection level that can be detached from the housing. This allows the terminal electronics to be replaced without disconnecting the pre-wired terminal blocks.

Does the KS4004 require an external power supply connection?

No, the KS4004 does not use external power contacts. It is powered internally via the standard Beckhoff K-bus, consuming typically 85 mA.

What is the output voltage and channel capability of the KS4004?

The KS4004 provides 4 analog output channels, each capable of outputting a 0 to 10 V signal with 12-bit resolution.

Is the analog output protected against short circuits?

Yes, the analog outputs on the KS4004 are short-circuit proof for loads greater than 5 kOhm.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...