1 z 1

Mitsubishi Electric Q64TCRT MELSEC Q Series Platinum Resistance Temperature Control Module

Mitsubishi Electric Q64TCRT MELSEC Q Series Platinum Resistance Temperature Control Module

Only 10 item(s) left in stock
  • Manufacturer: Mitsubishi Electric

  • Product No.: Q64TCRT

  • Country of origin:United States

  • Product Type: PLC Temperature Control Modules

  • Payment: T/T, Western Union

  • Weight: 1300g

  • Shipping port: Xiamen

  • Warranty: 12 months

Množství
Zobrazit veškeré podrobnosti

Description

Engineered for highly stable closed-loop thermal processes, the Mitsubishi Electric Q64TCRT handles direct interface to platinum resistance thermometers within a MELSEC Q Series PLC backplane. This module operates as an intelligent function block, executing PID control loop calculations independently of the main CPU cycle to guarantee real-time thermal response. By integrating temperature measurement, PID computation, and transistor outputs on a single hardware footprint, the unit minimizes network latency and eliminates external transmitter hardware.

Features

  • Four independent temperature control channels supporting Pt100 and JPt100 platinum resistance thermometer inputs.
  • Built-in PID engine supporting auto-tuning, self-tuning, and manual tuning profiles.
  • Transistor outputs (sink type) optimized for direct switching of Solid State Relays (SSRs).
  • Dedicated heating/cooling control output mode per channel for active thermal regulation.
  • Sensor disconnection detection to prevent thermal runaway in fault scenarios.

Applications

  • Plastic extrusion and injection molding barrel thermal zone management.
  • Semiconductor wafer processing chambers and heating blocks.
  • Food processing and packaging heat-sealing operations.
  • Precision environmental chambers and industrial drying ovens.

Technical Specifications Table

Parameter Value / Specification
Manufacturer Mitsubishi Electric
Model Number Q64TCRT
Compatible Series MELSEC Q Series
Number of Channels 4 channels
Sensor Input Types Pt100, JPt100 (3-wire resistance temperature detector)
Control Output Type Transistor output (Sink type), 24 VDC, 0.1A per point
Sampling Cycle 0.5 seconds for all 4 channels
I/O Points Occupied 16 points (Intelligent function module)
Internal Current Consumption 550 mA (5 VDC typical)
Country of Origin Japan
Shipping Weight (Calculated) 1.3 kg

Empirical Engineering Insights

Alternative Models & Compatibility

While the Q64TCRT uses platinum RTD inputs (Pt100/JPt100), sister modules like the Q64TCTT utilize thermocouple inputs. Ensure that your field sensing element matches the module interface precisely, as these modules are not interchangeable without rewiring and updating the buffer memory parameters in the GX Works PLC configuration.

Application Pitfalls & Engineering Notes

The integrated transistor outputs are rated for 0.1A at 24 VDC. Under no circumstances should inductive contactors or high-wattage heater loads be connected directly to these outputs. Always route the transistor outputs to intermediate solid-state relays (SSRs) or interposing relays to prevent thermal degradation of the internal optocouplers.

Commissioning & Wiring Tips

Use 3-wire shielded cables for all RTD connections to ensure automatic lead-wire resistance compensation. Keep the sensor input lines isolated from high-voltage AC lines and motor variable frequency drive (VFD) output cables. Ground the cable shields at a single point on the PLC side to mitigate high-frequency electrical noise from corrupting the PID sampling process.

Installation Guidelines

CRITICAL WARNING: ELECTRICAL HAZARD

Isolate and lock out all main system power sources before installing, removing, or wiring the module. Ensure any residual field-side voltage on the 24 VDC heater circuit is fully de-energized to prevent circuit card damage or electrical shock during installation.

1
Mount the module firmly onto the MELSEC Q series base unit, ensuring the lower module fixing projection is locked into the slot and the unit is securely fastened with the module fixing screw.
2
Wire the RTD inputs to the 18-point terminal block using crimp-type terminal lugs to ensure a gas-tight, vibration-resistant connection. Ensure no loose wire strands bridge adjacent terminals.
3
Connect the external 24 VDC power supply to the designated terminals to drive the transistor control outputs, verifying correct polarity before restoring power to the backplane.

What sensor types are supported by the Q64TCRT?

The module natively supports 3-wire Pt100 and JPt100 platinum resistance thermometer sensors across all four input channels.

Does this module require an external power supply?

Yes, an external 24 VDC power supply is required to power the integrated transistor control outputs.

What is the response rate of the built-in control loops?

The module features a sampling cycle of 0.5 seconds to process calculations and update control outputs for all four channels.

Can the Q64TCRT execute heating and cooling control simultaneously?

Yes, each channel can be configured for dual-action heating and cooling control, occupying adjacent output points to drive heating elements and cooling valves.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Elektrické pohony navržené jako náhrada hydraulických systémů: Praktická příručka průmyslové automatizace

Tento článek vysvětluje, jak integrované elektrické pohony, jako je řada e-Actuator od SMC, mění průmyslové řízení pohybu nahrazením tradičních pneumatických a hydraulických systémů. Zdůrazňuje...

Matematické operace pomocí OpenPLC pro průmyslové automatizační aplikace

Tento článek vysvětluje, jak PLC systémy provádějí základní matematické operace, jako jsou sčítání, odčítání, násobení, dělení, modulo a umocňování v rámci průmyslové automatizace. Ukazuje, jak tyto...

Pokročilá Booleovská logika s programováním FBD PLC: Praktické průmyslové aplikace nad rámec základní logiky

Článek vysvětluje několik pokročilých funkcí Booleovy logiky používaných v programování PLC nad rámec základních operací AND, OR a NOT. Popisuje, jak se v diagramu funkčních bloků (FBD) využívají...

Booleovská logika v programování PLC: Pochopení logických bran FBD

Booleovská logika je základem každého programu PLC. Od jednoduchých ovládání strojů až po složité průmyslové automatizační systémy určují logické hradla, jak řadiče reagují na měnící se vstupy a...