1 von 1

BECKHOFF KS3012 Bus Terminal Analog Input Module

BECKHOFF KS3012 Bus Terminal Analog Input Module

Nur noch 10 Artikel auf Lager verfügbar
  • Hersteller: BECKHOFF

  • Produkt-Nr.: KS3012

  • Herkunftsland:Deutschland

  • Produkttyp: Bus Terminals

  • Zahlung: T/T, Western Union

  • Gewicht: 70g

  • Abmessungen: 6.8 cm x 1.2 cm x 10.0 cm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Anzahl
Vollständige Details anzeigen

Description

Processing analog standard signals in the range from 0 to 20 mA, the BECKHOFF KS3012 Bus Terminal provides reliable, galvanically isolated data acquisition directly to the K-bus system. Featuring two differential inputs with a 12-bit resolution, this unit offers high-accuracy signal conversion within approximately 2 ms. The pluggable wiring level characteristic of the KS series allows system operators to quickly exchange the terminal block during maintenance without disturbing existing field wiring connections.

This module operates with an internal resistance of 80 Ohms combined with a diode voltage of 0.7 V, supporting a maximum common-mode voltage of 35 V. It is designed to mount seamlessly onto standard 35 mm DIN rails, offering space-saving integration inside compact control cabinets.

Features

  • Two differential analog inputs designed for 0 to 20 mA standard signal currents.
  • Pluggable connection level simplifies field wiring, module swap-out, and cabinet commissioning.
  • High-resolution 12-bit digitization with a conversion time of approximately 2 ms.
  • Low measuring error of less than +/-0.3% relative to the full-scale value.
  • Electrical isolation of 500 V between the internal K-bus and the field signal voltage.
  • Robust polycarbonate housing with a double slot and key connection for reliable side-by-side mounting.

Applications

  • Chemical and petrochemical process control systems.
  • Water, wastewater, and environmental utility monitoring.
  • Industrial machine tool and assembly line automation.
  • Energy management and power generation systems.

Technical Specifications

Manufacturer BECKHOFF
Part Number / Model KS3012
Number of Inputs 2
Signal Current 0 to 20 mA
Technology Differential input
Internal Resistance 80 Ohm + diode voltage 0.7 V
Common-Mode Voltage (Ucm) Max. 35 V
Conversion Time ~2 ms
Resolution 12 bit
Measuring Error < +/-0.3 % (relative to full scale value)
Surge Voltage Resistance 35 V DC
Electrical Isolation 500 V (K-bus/signal voltage)
Current Consumption (K-bus) Typ. 60 mA
Current Consumption (Power Contacts) None (no power contacts)
Process Image Bit Width Input: 2 x 16-bit data (2 x 8-bit control/status optional)
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC
Relative Humidity 95 %, no condensation
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Dimensions (L x W x H) 6.8 cm x 1.2 cm x 10.0 cm
Weight 0.07 kg

Connections and Interfaces

Connection Parameter Specification
Wiring Mechanism Spring actuation by screwdriver
Solid Conductor Cross-Section (s) 0.08 to 1.5 mm² (AWG 28 to 16)
Stranded Conductor Cross-Section (st) 0.08 to 1.5 mm² (AWG 28 to 16)
Flexible Conductor Cross-Section (f) 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Length 9 to 10 mm
Power Contact Current Load (Imax) 10 A

Installation Guidelines

Mount the KS3012 terminal directly onto a standard 35 mm DIN rail (EN 60715) ensuring the locking mechanism clicks securely. When wiring, insert a small flat-head screwdriver into the spring release slot to open the clamp, insert the stripped wire (9 to 10 mm), and remove the tool to secure the connection. Ensure signal wiring is physically separated from high-power distribution lines to minimize electromagnetic interference.

Compliance and Certifications

  • CE / UL: Compliant
  • DNV GL: Certified for maritime environments
  • ATEX Ex Marking: II 3 G Ex nA IIC T4 Gc
  • IECEx Ex Marking: Ex nA IIC T4 Gc / Ex tc IIIC T135 degC Dc
  • cFMus Ex Marking: Class I, Division 2, Groups A, B, C, D / Class I, Zone 2, AEx ec IIC T4 Gc
Loading product navigation…

What is the primary operational difference between the Beckhoff KS and KL series?

The KS series terminals feature a pluggable wiring level. This allows the terminal block to be easily unplugged and replaced during maintenance without disconnecting the physical field wires, whereas standard KL terminals require individual wire extraction.

What signal range and resolution does the KS3012 support?

The KS3012 features two differential inputs supporting a standard signal current of 0 to 20 mA with a resolution of 12 bits.

Does the KS3012 module require external power contacts?

No, the KS3012 does not utilize power contacts. It is powered internally directly via the standard K-bus.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...