1 von 1

Omron CJ1W-AD041-V1 CJ1 Series Analog Input Module

Omron CJ1W-AD041-V1 CJ1 Series Analog Input Module

Nur noch 4 Artikel auf Lager verfügbar
  • Hersteller: Omron

  • Produkt-Nr.: CJ1W-AD041-V1

  • Herkunftsland:Japan

  • Produkttyp: Analog Input Modules

  • Zahlung: T/T, Western Union

  • Gewicht: 2000g

  • Abmessungen: 3.1 cm x 9.0 cm x 6.5 cm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

Engineered for high-density data acquisition within industrial PLC networks, the Omron CJ1W-AD041-V1 analog input module delivers high-speed, multi-channel digitization for the compact CJ1 Series architecture. This module enables direct connection to standard process sensors, transmitters, and flowmeters, converting analog physical measurements into highly precise digital data. With a robust design focused on industrial reliability, it provides selectable resolution rates and integrated signal processing functions directly at the hardware layer, reducing processing overhead on the central CPU.

Features

  • High-Speed Digitization: Selectable conversion period down to 250 microseconds per point for dynamic, real-time control loops.
  • Flexible Resolution Modes: Configurable digital output resolution of either 1/4000 or 1/8000 depending on application precision requirements.
  • Integrated Signal Conditioning: On-board mean value processing, peak value holding, and sensor disconnection detection minimize the need for complex PLC ladder logic.
  • Detachable Wiring Architecture: Features an 18-point detachable terminal block with M3 screws, allowing rapid pre-wiring or module swap-outs without disrupting field wiring.

Applications

  • Chemical and water treatment flow, level, and pressure monitoring.
  • Temperature monitoring systems using external signal transmitters.
  • Multi-axis mechanical position and displacement feedback.
  • Factory utility tracking and environmental control systems.

Technical Specifications

Parameter Specification
Manufacturer Omron
Model Number CJ1W-AD041-V1
Series CJ Series (CJ1)
Module Type Analog Input Unit
Number of Analog Inputs 4 channels
Input Signal Range (Voltage) 1 to 5 V, 0 to 5 V, 0 to 10 V, -10 to 10 V
Input Signal Range (Current) 4 to 20 mA
Maximum Rated Input Voltage: +/-15 V, Current: +/-30 mA
Input Impedance Voltage Input: 1 MOhm minimum, Current Input: 250 Ohms (rated value)
A/D Conversion Period 1 ms per point or 250 microseconds per point (configurable)
Resolution 1/4,000 or 1/8,000 (configurable)
Isolation Photocoupler between I/O and controller signals (No isolation between individual input channels)
External Terminals 18-point detachable terminal block (M3 screws)
Current Consumption 420 mA maximum at 5 VDC
Operating Temperature 0 to 55 degC
Dimensions (W x H x D) 3.1 cm x 9.0 cm x 6.5 cm
Shipping Weight (Calculated) 2.0 kg

Empirical Engineering Insights

Alternative Models & Compatibility

The CJ1W-AD041-V1 is an updated hardware revision of the classic CJ1W-AD041. While maintaining standard physical mounting and logic allocations, the V1 revision introduces the high-speed conversion mode (250 microseconds/point) which is compatible with newer CJ1M, CJ2M, and CJ2H CPU units. When replacing an older non-V1 module in legacy systems, confirm that the system's software configurations match the conversion speed and resolution profiles set via the PLC unit parameters.

Application Pitfalls & Engineering Notes

Note that the module provides electrical isolation between the inputs and the internal controller logic, but does not provide isolation between individual input channels. If your system involves field devices that sit at different ground potentials, you will experience ground loop issues, causing signal drift or eventual hardware damage. To prevent this, always utilize external, channel-to-channel signal isolators for multi-point field devices in high-noise or split-ground environments.

Commissioning & Wiring Tips

For current inputs (4 to 20 mA), you must short-circuit the voltage input (V IN) and common (COM) terminals for the corresponding channel before powering the loop. Failing to jump these terminals on active current loop configurations can damage the internal 250 Ohm resistor due to high-impedance voltage floating. Always route analog signal wires separately from high-voltage AC lines to prevent magnetic noise induction.

Installation Guidelines

CRITICAL WARNING

Ensure the entire PLC rack and associated field instrumentation loop power supplies are completely de-energized before mounting, removing, or wiring this module. Hot-swapping the module on an active rack can corrupt CPU memory states, trigger systemic Bus Errors, and cause permanent hardware degradation.

1 Align the bottom notch of the CJ1W-AD041-V1 module with the slot on the backplane or adjacent module, and pivot it upward into place.
2 Securely lock the yellow sliders at both the top and bottom of the module to physically link the unit into the rack bus assembly.
3 Wire the M3 terminal block using shielded twisted-pair cables. Ground the shield at only one end (typically at the PLC's ground terminal) to mitigate electromagnetic interference.
4 Double-check the range selector switches on the physical module body (if applicable) and align the software DM area settings in CX-Programmer to match.
Loading product navigation…

Does the CJ1W-AD041-V1 provide electrical isolation between individual input channels?

No, while there is photocoupler isolation between the external inputs and the internal controller backplane, the individual analog input channels share a common ground line and are not isolated from one another.

How do I configure a channel on the CJ1W-AD041-V1 for a 4-20 mA current signal?

You must physically short-circuit the voltage input (V IN) and common (COM) terminal screws for the corresponding channel, then configure the input range configuration bits to the current input range within the PLC memory layout.

What is the difference between the legacy CJ1W-AD041 and the CJ1W-AD041-V1?

The V1 revision offers a much faster 250 us per point high-speed conversion mode (compared to the legacy 1 ms rate) and improved firmware compatibility with newer CJ2-series PLC processors.

What happens if a sensor wire breaks or gets disconnected from an input channel?

When the input range is configured to 1-5 V or 4-20 mA, the module automatically detects the voltage/current drop, triggers the Input Disconnection Detection flag, and updates the status bit in the PLC's allocated memory area.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage via DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir bedienen über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails, sehen Sie bitte unsere offizielle Seite ein Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe zur Ablösung von Fluidkraftsystemen: Ein praktischer Leitfaden für die industrielle Automatisierung

Dieser Artikel erklärt, wie integrierte elektrische Antriebe, wie die e-Actuator-Serie von SMC, die industrielle Bewegungssteuerung revolutionieren, indem sie herkömmliche pneumatische und...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie SPS-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...