Description

Designed for intrinsically safe signal processing, the Weidmuller 8965350000 functions as a high-reliability isolating switch amplifier within the ACT20X series. This module is engineered to safely isolate and transmit digital signals from hazardous areas (Zone 0, 1, 2) to safe-area control environments. It supports inputs from NAMUR sensors or mechanical switch contacts and converts them into relay outputs.

The ACT20X-HDI-SDO-RNC-S features comprehensive galvanic isolation between the input, output, and power supply circuits, ensuring superior signal integrity and system protection. Configuration is managed via standard FDT/DTM software, allowing operators to easily set parameters, monitor device status, and configure line fault detection (LFD) for open-circuit or short-circuit conditions.

Features

  • Intrinsically safe digital inputs compatible with NAMUR sensors and mechanical switches.
  • Relay output configuration for reliable safe-area signal switching.
  • Galvanic isolation across input, output, and power supply channels.
  • Software-based configuration utilizing standard FDT/DTM tools.
  • Integrated line fault detection (LFD) to identify open and short circuits in the field wiring.
  • Compact 22.5 mm housing designed for standard DIN-rail mounting.

Applications

  • Oil and gas processing and refining facilities.
  • Chemical and petrochemical manufacturing plants.
  • Water and wastewater treatment systems.
  • Power generation and distribution utilities.
  • Hazardous area signal isolation and safety instrumented systems (SIS).

Technical Specifications

ManufacturerPart Number/ModelProduct SeriesInput TypeSensor SupplyOutput TypeNominal Switching VoltageSupply VoltagePower ConsumptionConfiguration InterfaceConnection TypeIP RatingOperating TemperatureStorage TemperatureHumidityDimensions (H x W x D)Weight
Weidmuller
8965350000 (ACT20X-HDI-SDO-RNC-S)
ACT20X
NAMUR sensor (DIN EN 60947-5-6), switch contact
8 V DC / 8 mA
Relay
<= 125 V AC / 110 V DC (safe area), <= 32 V AC / 32 V DC (Zone 2)
19.2 to 31.2 V DC
<= 1.3 W
FDT/DTM software
Screw connection
IP20
-20 to +60 Celsius
-20 to +85 Celsius
0 to 95% (non-condensing)
117.2 mm x 22.5 mm x 113.6 mm
175 g

Installation Guidelines

  • Mounting: Snap securely onto a standard TS 35 DIN rail in a vertical orientation to optimize heat dissipation.
  • Wiring Separation: Maintain a minimum physical distance of 50 mm between intrinsically safe (Ex i) field wiring and non-intrinsically safe wiring.
  • Grounding: Ensure the DIN rail is properly bonded to the functional earth ground of the control cabinet.
  • Cabinet Protection: For installation in Zone 2 environments, the module must be mounted inside an enclosure providing a minimum protection rating of IP54.

Compliance and Certifications

  • ATEX
  • IECEx
  • CE
  • UL
Loading product navigation…

What is the primary function of the Weidmuller 8965350000?

The Weidmuller 8965350000 (ACT20X-HDI-SDO-RNC-S) is an intrinsically safe isolating switch amplifier designed to safely transmit digital signals from hazardous areas (such as NAMUR sensors or mechanical switches) to safe-area control systems via relay outputs.

How is the ACT20X-HDI-SDO-RNC-S configured?

This module is configured using standard FDT/DTM software, allowing operators to parameterize input types, configure line fault detection, and monitor device diagnostics.

What are the power supply requirements for this module?

The module requires a nominal supply voltage of 19.2 V DC to 31.2 V DC and has a maximum power consumption of 1.3 W.

Does the module support line fault detection?

Yes, the ACT20X-HDI-SDO-RNC-S features integrated line fault detection (LFD) to monitor the field wiring for open-circuit and short-circuit conditions.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage per DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) eingehen.
  • Weltweite Abdeckung: Wir beliefern über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden von Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabebedingungen lesen Sie bitte unsere offiziellen Rückerstattungs- & Rückgaberecht .

TECHNICAL SPECIFICATIONS

Country of origin
Deutschland

Kürzlich angesehene Produkte

Technisches Wissen

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Die boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie PLC-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...

Rückblick: Wie frühe Elektromotoren den Untertagebergbau veränderten

Von seilgetriebenen Gleichstromkompressoren bis hin zu batteriebetriebenen Grubenwagen markierten frühe Bergbauoperationen einen Wendepunkt in der industriellen Elektrifizierung. Dieser Artikel...

Factory I/O: Ein modernes PLC-Simulationswerkzeug für die Ausbildung in der Industrieautomatisierung

Factory I/O revolutioniert die SPS-Ausbildung, indem es immersive 3D-Industriesimulationen für Studenten, Ingenieure und Wartungsteams bereitstellt. Die Plattform überbrückt die Lücke zwischen...

Programmierung von Ein-Achsen-Bewegungszyklen auf einem CMZ-Servoantrieb

Dieses Tutorial untersucht, wie die integrierte SPS-Funktionalität in einem CMZ SBD-Servoantrieb eigenständige Bewegungsprogramme ausführen kann, einschließlich Referenzfahrt-Logik,...