Yokogawa SAI143-S33 ProSafe-RS Analog Input Module

Yokogawa SAI143-S33 ProSafe-RS Analog Input Module

Nur noch 8 Artikel auf Lager verfügbar
  • Hersteller: Yokogawa

  • Produkt-Nr.: SAI143-S33

  • Herkunftsland:Japan

  • Produkttyp: Analog Input Module

  • Strichcode: 8537101190

  • Zahlung: T/T, Western Union

  • Gewicht: 340g

  • Abmessungen: 32.8 mm x 130 mm x 107.5 mm

  • Versandhafen: Xiamen

  • Garantie: 12 Monate

Menge
Vollständige Details anzeigen

Description

The Yokogawa SAI143-S33 is a high-reliability current input module designed for mounting on the safety node unit and safety control unit within the ProSafe-RS safety instrumented system. This module plays a critical role in safety functions by inputting 4 to 20 mA signals from field instruments directly into the Safety Control Station (SCS). It supports dual-redundant configurations to achieve enhanced system availability and fault tolerance. The SAI143-S33 features standard individual channel configuration pins for 2-wire or 4-wire transmitters and provides module isolation for its 16 processing channels.

Features

  • Dual Redundancy: Supports full dual-redundant configuration to eliminate single points of failure in safety-critical applications.
  • Flexible Sensor Hookup: Individual channel setting via pins to accommodate both 2-wire and 4-wire field transmitter arrangements.
  • Simultaneous Power Management: Built-in transmitter power supply ON/OFF function across all 16 channels simultaneously, facilitating alarm resets for Fire and Gas devices.
  • Robust Isolation: Delivers module-level galvanic isolation protecting internal system electronics from hazardous field transients.

Applications

  • Safety Instrumented Systems (SIS) 
  • Emergency Shutdown Systems (ESD)
  • Fire and Gas (F&G) System integration and device resetting 
  • Process industry safety monitoring and critical current loop sourcing 

Ordering Information

Model Suffix Codes Description
SAI143   Analog Input Module (4 to 20 mA, 16 channels, module isolation) 
  -S Standard type 
  3 For pressure clamp terminal block or MIL cable with no explosion protection
3 With ISA Standard G3 and temperature (-20 to 70 degC) 

Technical Specifications

Item Specifications
Manufacturer Yokogawa Electric Corporation 
Model SAI143-S33 
Number of Input Channels 16 channels, module isolation 
Rated Input Range 4 to 20 mA 
Permissible Input Range 0 to 25 mA 
Input Impedance (Power-ON) 250 Ohm + Voltage drop in the input protection circuit inside the module / Current value 
Input Impedance (Power-OFF) 500 Ohm minimum 
Maximum Voltage Drop 0.45 V (in the input protection circuit) 
Rated Accuracy ±16 uA (Input range 1 to 23 mA for Style S3) 
Data Update Frequency 40 ms 
Temperature Drift ±16 uA/10 degC 
Transmitter Power Supply 16.15 V minimum (at 20 mA), 26.4 V maximum (at 0 mA) 
Output Current Limit 25 mA 
Withstand Voltage 1.5 kV AC between input signal and system for 1 minute 
Maximum Current Consumption 5 V system: 320 mA, 24 V system: 550 mA 
Ambient Temperature -20 to 70 degC 
Environmental Code ISA Standard G3 
Weight Approx. 0.34 kg (For pressure clamp terminal block or MIL cable) 
Dimensions (W x H x D) 32.8 mm x 130 mm x 107.5 mm (For pressure clamp and MIL cable) 

Installation Guidelines

  • Module Siting: Mount the current input module onto a compatible safety node unit or safety control unit chassis.
  • Redundancy Setup: When implementing dual-redundant pairs, order an additional tracking module with identical technical specifications but without specific optional suffix accessories.
  • Safety Isolation Barriers: Do not connect Zener barriers directly to this hardware. Utilize an approved isolation barrier when deploying an intrinsically safe instrumented loop.
  • False Insertion Prevention: When deploying option /PRP, utilize the specified matching field signaling cable variant equipped with the corresponding option /SAI143 to ensure functional physical key alignment.

Compliance and Certifications

  • ISA Standard G3: Certified for installation within corrosive industrial environments meeting the G3 severity specifications.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Yokogawa SAI143-S33 ProSafe-RS Analog Input Module

Can Zener barriers be connected directly to the module?

No, Zener barriers cannot be connected to this module. An isolation barrier must be used when an intrinsically safe instrumented system is required.

What is the purpose of the transmitter power supply ON/OFF function?

This function allows the module to turn off the transmitter power supplied to all 16 channels simultaneously under a 2-wire setting, which enables resetting the alarm state of Fire and Gas devices.

How is the 2-wire or 4-wire mode configured on the module?

The 2-wire or 4-wire operational mode is set individually for each channel using dedicated physical setting pins on the module.

Globaler Expressversand

  • Standardlieferung: 4-6 Werktage via DHL, FedEx und UPS.
  • Expressversand: Versand am selben Tag für vorrätige Bestellungen, die vor 14:00 Uhr (GMT+8) aufgegeben werden.
  • Weltweite Abdeckung: Wir bedienen über 150 Länder, einschließlich schneller Lieferung nach Saudi-Arabien und in die VAE.

Rückgaben & Garantie

  • 30-Tage-Garantie: Rückgaben werden für vorrätige Produkte in originaler, werkversiegelter Verpackung akzeptiert.
  • 12-Monats-Garantie: Jede Industriekomponente ist durch unsere professionelle technische Garantie abgesichert.

Bestellungen werden Montag bis Freitag bearbeitet und geliefert (außer an Feiertagen).


Für vollständige Anspruchsvoraussetzungen, Wiedereinlagerungsgebühren und internationale Rückgabedetails, sehen Sie bitte unsere offizielle Seite ein Rückerstattungs- & Rückgabebedingungen .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Kürzlich angesehene Produkte

Technisches Wissen

Elektrische Antriebe als Ersatz für Flüssigkeiten: Praktisches Tutorial

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Mathematische Operationen mit OpenPLC für industrielle Automatisierungsanwendungen

Dieser Artikel erklärt, wie SPS-Systeme grundlegende mathematische Operationen wie Addition, Subtraktion, Multiplikation, Division, Modulo und Exponentiation in der industriellen Automatisierung...

Fortgeschrittene Boolesche Logik mit FBD-SPS-Programmierung: Praktische industrielle Anwendungen über die Grundlogik hinaus

Der Artikel erklärt mehrere erweiterte Boolesche Logikfunktionen, die in der SPS-Programmierung über die grundlegenden AND-, OR- und NOT-Operationen hinaus verwendet werden. Er behandelt, wie...

Boolesche Logik in der SPS-Programmierung: Verständnis von FBD-Logikgattern

Boolesche Logik ist die Grundlage jedes SPS-Programms. Von einfachen Maschinensteuerungen bis hin zu komplexen industriellen Automatisierungssystemen bestimmen Logikgatter, wie Steuerungen auf sich...

Umfassender Leitfaden zu industriellen Firewalls und OT-Netzwerksegmentierung

Industrielle Firewalls spielen eine entscheidende Rolle in der OT-Cybersicherheit, indem sie SPS-, DCS- und SCADA-Netzwerke durch Segmentierung, Ein- und Ausgangskontrolle sowie IDS/IPS-Integration...

Leitfaden für Roboter-Greifer: Von der schonenden Handhabung bis zur Schwerlastautomatisierung

Moderne robotische Greifer entwickeln sich über traditionelle mechanische Greifbacken hinaus. Von gecko-inspirierten Haftsystemen und weichen, lebensmittelechten Greifern bis hin zu KI-gestützten...