1 / 1

Bently Nevada 3500/05-02-04-00-00-01 3500 Series System Rack

Bently Nevada 3500/05-02-04-00-00-01 3500 Series System Rack

Only 2 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 3500/05-02-04-00-00-01

  • Country of origin:Egyesült Államok

  • Product Type: Machinery Protection System Racks

  • Payment: T/T, Western Union

  • Weight: 320g

  • Shipping port: Xiamen

  • Warranty: 12 months

Mennyiség
Minden részlet megtekintése

Description

Designed to serve as the structural and communication backbone for machinery protection systems, the Bently Nevada 3500/05-02-04-00-00-01 is a specialized 12-inch Mini-Rack chassis engineered to house and interconnect Bently Nevada 3500 series modules. This rack features 7 available module slots to consolidate vibration monitoring, keyphasor signals, and relay outputs into a compact footprint. It incorporates a high-integrity backplane that facilitates continuous power distribution and high-speed digital data transfer between installed monitoring modules and transient data interfaces, ensuring uninterrupted mechanical diagnostic capabilities for heavy industrial machinery.

Features

  • Compact Form Factor: 12-inch Mini-Rack architecture designed to save space in high-density control cabinets.
  • 7-Slot Capacity: Accommodates standard 3500 series monitoring and power supply modules within a reduced footprint.
  • Panel Mount Configuration: Purpose-built bezel and mounting flange for direct integration into control panel cutouts.
  • High-Integrity Backplane: Distributes operating power and manages system-wide digital bus communications without signal degradation.
  • CE Compliance: Meets European safety and electromagnetic compatibility standards for harsh industrial environments.

Applications

  • Vibration monitoring and asset protection for turbomachinery and generators.
  • Petrochemical and oil and gas pump, compressor, and fan diagnostic systems.
  • Hydroelectric and thermal power plant rotating asset monitoring.
  • Critical industrial machinery protection requiring compact cabinet installations.

Ordering Information

Option Code Option Description Selected Configuration Value
02 Rack Size 12-inch Mini-Rack (7 module slots)
04 Mounting Options Panel Mount Option, Mini-Rack
00 Agency Approval Option None Specified
00 Reserved Option None
01 European Compliance CE Certified

Technical Specifications Table

Specification Parameter Technical Value / Detail
Manufacturer Bently Nevada
Model Number 3500/05-02-04-00-00-01
System Series 3500 Series Machinery Protection System
Physical Rack Size 12-inch Mini-Rack
Module Capacity 7 slots (Includes dedicated power supply and rack interface slots)
Mounting Type Panel Mount (Front-secure installation)
Agency Approvals Standard Industrial (No hazardous area approvals specified)
Compliance Standards CE (European Conformity)
Country of Origin United States (USA)
Shipping Weight (Calculated) 6.0 kg (13.2 lbs)

Alternative Models & Compatibility

The 12-inch Mini-Rack system limits module slots to 7 compared to the standard 19-inch 14-slot 3500/05 rack. If your instrumentation loop expands to require additional monitoring channels, you must transition to a full-sized 19-inch 3500/05 rack configuration. Standard 3500 series input modules and power supplies are backward compatible with this mini-rack backplane, provided that power requirements do not exceed the threshold of the installed mini-rack power supply units.

Application Pitfalls & Engineering Notes

Because panel-mounted units sit inside enclosed environmental cabinets, thermal management is critical. A fully populated 7-slot mini-rack containing dual power supplies and multiple processing monitors generates significant heat density. Maintain a minimum of 50mm (2.0 inches) of clearance above and below the rack chassis to ensure adequate convective air circulation. Avoid placing heat-sensitive field-wiring barriers directly above the exhaust path of the rack.

Commissioning & Wiring Tips

Proper chassis grounding is vital to prevent high-frequency noise from corrupting low-voltage proximity probe and accelerometer signals. Connect a low-impedance copper ground strap directly from the designated rack grounding stud to the main panel safety ground bus. Do not rely solely on the panel-mounting screws for establishing an electrical ground pathway. All internal shield connections must be isolated and terminated according to Bently Nevada wiring diagrams to prevent ground loop interference.

Installation Guidelines

CRITICAL WARNING: De-energize all primary, redundant, and field-contact power sources before attempting panel cutout prep or physical installation. Verify that no residual static charges are present on the cabinet housing. Failure to isolate power can result in equipment damage, system-wide trips of machinery protection relays, or severe electrical shock.
1
Measure and execute the panel cutout precisely according to the 12-inch Bently Nevada mini-rack dimensional template. deburr all raw metal edges.
2
Position the rack bezel gasket to maintain cabinet environmental integrity, then insert the rack through the front cutout.
3
Secure the mini-rack to the panel bezel using the recommended mounting screws and torque-tighten to ensure a secure, vibration-resistant fit.
4
Connect the dedicated copper grounding strap to the chassis ground stud before installing modules or applying power to the backplane.

What is the difference between a mini-rack and a standard 3500/05 rack?

The mini-rack configuration features 7 module slots and a 12-inch width, whereas the standard rack features 14 module slots and a 19-inch width for EIA cabinet mounting.

Can I use standard 3500 series modules in this mini-rack?

Yes, standard 3500 Series modules are fully compatible with the mini-rack backplane, subject to the overall 7-slot physical limitation.

What are the mounting requirements for this panel-mount variant?

This variant is designed for panel cut-out installation. It mounts directly from the front of the panel and secures with fasteners around the perimeter bezel.

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Country of origin
Egyesült Államok

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...