The Honeywell TSDO-0824 is a high-reliability Safe Digital Output Field Termination Assembly (FTA) module specifically engineered for integration within the Honeywell Safety Manager platform. This module acts as the dedicated physical and electrical interface connecting the system interconnection cable SICC-0001/Lx directly to external field circuitry via robust onboard screw terminals.

Designed to support critical safety-instrumented functions, the TSDO-0824 handles the eight independent channels of a single or redundant pair of SDO-0824 safe digital output modules. The assembly features a universal snap-in mounting provision designed for standard DIN EN rails, offering structured, secure, and vibration-resistant field terminal assignments for high-availability industrial safety applications.

Features

  • Seamlessly interfaces 8 independent safe digital output channels to the field.
  • Designed as the direct terminal companion for the SICC-0001/Lx system interconnection cable.
  • Fully supports redundant pairing topologies with SDO-0824 safety output modules.
  • Integrated universal snap-in hardware for secure and direct DIN rail mounting.
  • Durable built-in screw terminal blocks provide standard, gas-tight field wiring connections.
  • Confirmed high electrical compliance matching overvoltage category 3 parameters.

Applications

  • Safety Instrumented Systems (SIS)
  • Emergency Shutdown Systems (ESD)
  • Burner Management Systems (BMS)
  • High-integrity Fire and Gas (F&G) output systems
  • Distributed Control System (DCS) safety loop interlocks

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Product Number TSDO-0824
Product Type Safe Digital Output FTA
System Series Safety Manager
Number of Channels 8
Maximum Voltage 36 Vdc – IEC 1010 (1990), overvoltage category 3
Maximum Continuous Current per Channel 1.5 A
Actual Maximum Current Defined by connected output module
DIN EN Rails TS32 / TS35 x 7.5
Used Rail Length 171 mm (6.73 in)
Screw Terminals Max Wire Diameter 2.5 mm² (AWG 14)
Screw Terminals Strip Length 7 mm (0.28 in)
Screw Terminals Tightening Torque 0.5 Nm (0.37 ft-lb)
Module Dimensions (L x W x H) 170 x 70 x 64 mm (6.72 x 2.76 x 2.52 in)
Shipping Weight 3 Kg
Country of Origin Netherlands

Installation Guidelines

  • DIN Rail Installation: Snap the module firmly onto standard TS32 or TS35 x 7.5 DIN EN rails. Verify that the targeted rail segment leaves at least 171 mm of usable horizontal space to properly accommodate the base alignment.
  • Cable Termination: Plug the multi-pin interface plug of the SICC-0001/Lx system interconnection cable completely into the module's onboard SIC header to establish the internal link with the SDO-0824 output modules.
  • Field Wiring Connection: Carefully strip field conductor ends to a precise length of 7 mm (0.28 in). Insert the conductors into the terminal blocks (accepting up to 2.5 mm² / AWG 14 max wire size) and securely tighten the screws to a nominal torque of 0.5 Nm (0.37 ft-lb).
  • Enclosure Protection: Mount the assembly within a clean, climate-controlled electrical panel or marshalling cabinet to provide appropriate moisture, environmental dust protection, and effective shielding against industrial EMI/RFI noise.

Compliance and Certifications

  • CE
  • TUV
  • UL
  • CSA
  • FM

FAQ

What is the primary role of the TSDO-0824 module in a safety system?

It acts as the physical field termination assembly interface that bridges the Honeywell Safety Manager system interconnection cabling to the external field equipment wiring.

How many output channels are built into this termination assembly?

The module is equipped with exactly 8 safe digital output channels.

Which system cable must be used to connect this FTA to the system rack?

This module requires the standard SICC-0001/Lx system interconnection cable.

Can this field termination module handle redundant output signals?

Yes, it can seamlessly accommodate the eight combined channels of a redundant pair of SDO-0824 modules.

What is the maximum absolute voltage limit permitted for the field contacts?

The maximum voltage limit is defined as 36 Vdc under IEC 1010 (1990) overvoltage category 3 parameters.

Does the TSDO-0824 strictly limit channel current to 1.5 A?

While the hardware continuous current limit per channel is 1.5 A, the actual maximum current limit is determined by the specific output module connected upstream.

What specific profile types of DIN EN rails can this module be snapped onto?

The integrated universal snap-in assembly is fully compatible with TS32 and TS35 x 7.5 DIN EN rails.

How much horizontal space on the DIN rail does the unit require?

The module has a specified used rail length of 171 mm (6.73 inches).

What is the required insulation stripping length for preparing field wiring?

External field wires must be stripped to an exact length of 7 mm (0.28 inches) before termination.

What torque level should be applied when securing the field screws?

All onboard field screw terminals must be tightened to a torque rating of 0.5 Nm (0.37 ft-lb).

What is the maximum allowable wire gauge size for the terminal block?

The terminal blocks accept a maximum solid or stranded conductor diameter up to 2.5 mm², which matches AWG 14.

What independent product testing certifications does this hardware hold?

The field termination assembly holds official, fully verified approvals from CE, TUV, UL, CSA, and FM.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell TSDO-0824 Safety Manager Safe Digital Output FTA

Globális expressz szállítás

  • Normál szállítás: 4-6 munkanap a DHL, FedEx és UPS szolgáltatásával.
  • Gyors kiszállítás: A raktáron lévő, 14:00 (GMT+8) előtt leadott megrendeléseket aznap feladjuk.
  • Világszintű lefedettség: Több mint 150 országban szolgálunk ki, beleértve a gyors szállítást Szaúd-Arábiába és az Egyesült Arab Emírségekbe.

Visszaküldés és garancia

  • 30 napos garancia: Csak a raktáron lévő termékek eredeti, gyári zárt csomagolásban történő visszaküldését fogadjuk el.
  • 12 hónapos garancia: Minden ipari alkatrészünket szakmai műszaki garancia védi.

A megrendeléseket hétfőtől péntekig dolgozzuk fel és szállítjuk (állami ünnepnapok kivételével).


A teljes jogosultság, a készletfeltöltési díjak és a nemzetközi visszaküldési részletek megtekintéséhez kérjük, tekintse meg hivatalos oldalunkat Visszatérítési és Visszaküldési Szabályzat .

TECHNICAL SPECIFICATIONS

Color pattern
Narancssárga Zöld
Country of origin
Egyesült Államok
Power source
DC áram

Nemrég megtekintett termékek

Műszaki ismeretek

Elektromos működtetők, amelyek a folyadékenergia-rendszereket váltják ki: Gyakorlati ipari automatizálási útmutató

Ez a cikk bemutatja, hogyan alakítják át az integrált elektromos működtetők, például az SMC e-Actuator sorozata, az ipari mozgásvezérlést azáltal, hogy kiváltják a hagyományos pneumatikus és...

Matematikai műveletek OpenPLC-vel ipari automatizálási alkalmazásokhoz

Ez a cikk bemutatja, hogyan hajtanak végre a PLC rendszerek alapvető matematikai műveleteket, mint az összeadás, kivonás, szorzás, osztás, modulo és hatványozás az ipari automatizálásban. Megmutatja,...

Fejlett Boole-logika FBD PLC programozással: Gyakorlati ipari alkalmazások a alapvető logikán túl

A cikk több fejlett Boole-logikai függvényt ismertet, amelyeket a PLC programozásban használnak az alapvető ÉS, VAGY és NEM műveleteken túl. Bemutatja, hogyan alkalmazhatók olyan eszközök, mint az...

Boole-logika a PLC programozásban: Az FBD logikai kapuk megértése

A Boole-logika minden PLC program alapja. Az egyszerű gépvezérlésektől a bonyolult ipari automatizálási rendszerekig a logikai kapuk határozzák meg, hogyan reagálnak a vezérlők a változó bemenetekre...

Részletes útmutató az ipari tűzfalakról és az OT hálózati szegmentációról

Az ipari tűzfalak kulcsfontosságú szerepet játszanak az OT kiberbiztonságban, védve a PLC, DCS és SCADA hálózatokat szegmentálás, be- és kimeneti forgalom szabályozás, valamint az IEC 62443 elveivel...

Útmutató a robotikus fogókhoz: a finomkezeléstől a nehézüzemi automatizálásig

A modern robotfogók túlmutatnak a hagyományos mechanikus állkapcsokon. A gyíkok tapadó rendszerétől és az élelmiszeripari puha fogóktól az MI-vezérelt raktári eszközökig a fejlett fogástechnológiák...