1 daripada 1

Bently Nevada 3500/15-05-00-CN Universal AC Power Supply Module

Bently Nevada 3500/15-05-00-CN Universal AC Power Supply Module

Hanya 8 item tinggal dalam stok
  • Pengilang: Bently Nevada

  • No. Produk: 3500/15-05-00-CN

  • Negara asal:Amerika Syarikat

  • Jenis Produk: Power Supply Module

  • Pembayaran: T/T, Western Union

  • Berat: 1390g

  • Dimensi: 120.7 mm x 50.8 mm x 251.5 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

The 3500/15-05-00-CN is a half-height module designed to power the 3500 Series Machinery Protection System. It must be installed in designated slots on the left side of the 3500 rack to convert a wide range of input voltages into regulated voltages required by other system modules. The 3500/15-05-00-CN functions as a universal AC power supply and operates alongside a universal AC Power Input Module (PIM). The 3500 rack can hold either a single supply or two redundant power supplies. In a dual configuration, the module in the lower slot acts as the primary supply, while the module in the upper slot serves as the backup supply. Redundant operation allows for the removal or insertion of either supply module without disrupting system operation.

Features

  • Half-height format optimizes rack space efficiency.
  • Redundant power capability provides seamless automatic backup when dual modules are installed.
  • Hot-swappable design permits module insertion and removal without interrupting rack functions.
  • Front panel "Supply OK" LED provides direct visual confirmation of proper module operation.
  • Over-voltage protection causes the fuse to open on the PIM to isolate the system from damaging voltage levels.
  • Under-voltage protection ensures low-voltage conditions do not cause harm to the supply or the PIM.

Applications

  • Turbo-machinery protection and condition monitoring
  • Power generation gas and steam turbine vibration instrumentation
  • Oil and gas refinery rotating asset protection
  • Petrochemical plant machinery monitoring systems
  • Heavy industrial compressor and pump protection systems

Ordering Information

Option Code Description
A: Power Supply Type (Top Slot) 05 Universal AC Voltage (85 to 264 Vac rms) 
B: Power Supply Type (Bottom Slot) 00 No Supply (Used when no supply is required) 

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada (Baker Hughes) 
Country of Origin USA 
Nominal Input Voltage 110 to 220 Vac nominal 
Input Voltage Range (Non-hazardous) 85 to 264 Vac rms 
Input Voltage Range (Hazardous) 85 to 250 Vac rms 
Input Voltage Peak 120 to 373 Vac pk 
Input Frequency 47 to 63 Hz 
Full Rack Current Draw 2.8 A rms (maximum) 
Power Supply Dimensions (H x W x D) 120.7 mm x 50.8 mm x 251.5 mm (4.75 in x 2.0 in x 9.9 in) 
Power Supply Weight 1.39 kg (3.06 lb) 
Power Input Module Dimensions (H x W x D) 120.7 mm x 25.4 mm x 114.3 mm (4.75 in x 1.0 in x 4.5 in) 
Power Input Module Weight 0.34 kg (0.75 lb) 
Operating Temperature -30 degC to +65 degC (-22 degF to +150 degF) 
Storage Temperature -40 degC to +85 degC (-40 degF to +185 degF) 
Humidity 95%, non-condensing 
Minimum Loading No minimum rack load is required 

Connections/Interfaces

Component / Terminal Function
Supply OK LED Front panel indicator that illuminates when the power supply operates properly.
Universal AC PIM Terminals Rear connections for Line (LN) and Neutral (NEUT) high-voltage AC inputs.
GND Protective Earth Ground connection point on the PIM.
FUSE Slot Holds the replaceable primary over-voltage protection fuse.

Installation Guidelines

  • Rack Positioning: Install the module only in the dedicated half-height slots located on the far left side of the 3500 rack.
  • PIM Matching: Ensure the associated Universal AC Power Input Module (PIM) is mounted directly behind the power supply module in the rear of the chassis.
  • Redundancy Allocation: For redundant configurations, locate the primary supply in the lower slot and the secondary backup supply in the upper slot.
  • Electrical Safety: Connect the structural grounding system securely to the rear PIM ground terminal to reduce electrical noise and ensure safety.
  • Compatibility Check: Verify that the universal AC supply and its corresponding PIM are not mixed or cross-connected with legacy Bently Nevada high/low voltage AC components, as they are incompatible.

Compliance and Certifications

  • EMC Directives: 2014/30/EU 
  • EMC Standards: EN 61000-6-2 (Immunity for Industrial Environments), EN 61000-6-4 (Emissions for Industrial Environments) 
  • Electrical Safety: Low Voltage Directive 2014/35/EU, EN 61010-1 
  • RoHS: ROHS Directive 2011/65/EU 
  • Maritime Classifications: DNV GL rules for classification (Ships, offshore units, high speed and light craft), ABS Rules for Condition of Classification (Part 1, Steel Vessels, Offshore Units and Structures)
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 3500/15-05-00-CN Universal AC Power Supply Module

Can this power supply module be used in redundant configurations?

Yes, but this specific model (3500/15-05-00-CN) features a '00' option for the bottom slot, meaning it does not ship with a second supply. To achieve full physical utility redundancy, you must install an additional compatible input supply in the lower slot of the rack chassis.

What input voltages are supported by the 05 option?

The 05 option denotes a Universal AC input, which safely accepts alternating voltages from 85 to 264 Vac rms. It functions reliably on standard 110/120 Vac and 220/240 Vac global distribution systems.

Does this module require diagnostic software for commissioning?

No. The power supply works immediately upon receiving input power, supplying the necessary DC rails to the rack backplane automatically. Status LED indicators on the front panel provide real-time diagnostic health.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Perniagaan melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Bayaran Balik .

TECHNICAL SPECIFICATIONS

Country of origin
Amerika Syarikat

Produk yang Baru Dilihat

Pengetahuan teknikal

Logik Boolean Lanjutan dengan Pengaturcaraan PLC FBD: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan Pengapit Robotik: Dari Pengendalian Halus ke Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...

Throwback: Bagaimana Motor Elektrik Awal Mengubah Perlombongan Bawah Tanah

Dari pemampat DC yang digerakkan tali ke troli lombong bertenaga bateri, operasi perlombongan awal menandakan titik perubahan dalam elektrifikasi industri. Artikel ini meneroka bagaimana motor...

Factory I/O: Alat Simulasi PLC Moden untuk Latihan Automasi Industri

Factory I/O sedang mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang mendalam untuk pelajar, jurutera, dan pasukan penyelenggaraan. Platform ini merapatkan jurang antara teori dan...