1 z 3

Bently Nevada 3500/33 149986-01 16-Channel Relay Module

Bently Nevada 3500/33 149986-01 16-Channel Relay Module

Only 7 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 3500/33 149986-01

  • Country of origin:Stany Zjednoczone

  • Product Type: 16-Channel Relay Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 1300g

  • Dimensions: 241 mm x 24.4 mm x 242 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

The 3500/33 with spare part number 149986-01 is a full-height module that provides 16 independent programmable relay outputs for machinery protection and control switching. This 3500/33 149986-01 module functions within the 3500 Series Machinery Protection System and installs into any standard slot to the right of the Transient Data Interface (TDI) module. Each relay output features independent voting logic configuration and dedicated Alarm Drive Logic, which processes alert, danger, and Not-OK statuses derived from any combination of monitor channels across the rack via the configuration software. Internal communication link tracking is visually monitored via integrated front panel status indicators.

Features

  • 16 fully independent single-pole double-throw (SPDT) relay output channels.
  • Custom voting logic and Alarm Drive Logic supporting complex AND/OR logic configurations.
  • Integrated onboard 250 Vrms arc suppressors installed as a standard protection feature.
  • Switch-selectable operations for Normally De-energized (ND) or Normally Energized (NE) modes in groups of four channels.
  • Visual status verification via OK, TX/RX, and individual channel alarm LEDs.

Applications

  • Automated machinery trip and emergency shutdown logic initialization.
  • Interlocking and annunciator panel control in heavy industrial processing.
  • Critical alarm state relay signaling for turbines, large pumps, and industrial compressors.

Technical Specifications

Parameter Specification
Manufacturer Bently Nevada
Model Number 3500/33
Spare Part Number 149986-01
Product Type 16-Channel Relay Control Module
Power Consumption 5.8 watts typical
Relay Contact Type Single-pole Double-throw (SPDT), epoxy-sealed
Relay Arc Suppressor 250 Vrms standard
Relay Contact Life 10,000 cycles
Standard System Min Load 100 mA @ 5 Vdc
Standard DC Max Load 5 A, 70 W @ 24 Vdc, 10 W @ 48 Vdc, 9 W @ 60 Vdc, 125 Vdc max
Standard AC Max Load 5 A, 1200 VA, 250 Vac max
Failsafe System Max DC 5 A, 30 Vdc max
Low Current System Min Load 1 mA @ 1 Vdc (Gold-plated contacts)
Low Current System Max DC 100 mA @ 48 Vdc
Low Current System Max AC 5 mA max (Specific to AC up to 120Vac)
Main Module Dimensions 241 mm x 24.4 mm x 242 mm (9.50 in x 0.96 in x 9.52 in)
I/O Module Dimensions 241 mm x 24.4 mm x 99.1 mm (9.50 in x 0.96 in x 3.90 in)
Main Module Weight 0.7 kg (1.6 lb)
I/O Module Weight 0.4 kg (1.0 lb)
Rack Space Required 1 full-height front slot (Main), 1 full-height rear slot (I/O)
Country of Origin United States

Installation Guidelines

  • Slot Placement: Seat the full-height main control module into any available chassis slot located directly to the right of the primary TDI module.
  • Redundant Pairs: Pair the main front-panel module with its corresponding 16-channel relay I/O module positioned directly behind it in the rear chassis space.
  • Logic Programming: Configure the voting logic structures and operational parameters via the 3500 Rack Configuration Software prior to putting the instrumentation loop online.
  • Operation Mode Setup: Set the physical switches to select between Normally De-energized (ND) and Normally Energized (NE) setups for each four-channel group based on plant safety specifications.
  • Hazardous Voltage Warning: Ensure all field terminal wiring points are completely isolated from source power lines prior to installation or maintenance to eliminate high-voltage shock risks.
  • Explosion Hazard Precaution: Do not connect or disconnect any components or field terminations while the active instrumentation circuit is live unless the surrounding zone is verified to be non-hazardous.
Key Features:

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 3500/33 149986-01 16-Channel Relay Module

Where can this 16-channel relay module be installed inside the rack?

The module is full-height and can be placed in any of the slots located to the right of the Transient Data Interface (TDI) module.

How are the Normally Energized or Normally De-energized operations chosen?

The relay operations are switch-selectable on the hardware in four distinct groups of four channels each.

What is the maximum current rating for standard relays in AC applications?

Standard relays support a maximum switched current of 5 A and a maximum switched power of 1200 VA, up to a maximum voltage of 250 Vac under resistive loads.

What happens if standard electrical loads are applied to gold-plated low current relays?

For low current gold-plated relays, the maximum switching current before sustaining component damage is strictly limited to 5 mA for AC up to 120Vac.

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Color pattern
Szaro-biały Srebro
Country of origin
Stany Zjednoczone
Power source
Zasilanie prądem stałym

Ostatnio oglądane produkty

Wiedza techniczna

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...