1 z 3

GE Multilin UR-8NH Standard 8CT With Enhanced Diagnostics

GE Multilin UR-8NH Standard 8CT With Enhanced Diagnostics

Only 7 item(s) left in stock
  • Manufacturer: General Electric

  • Product No.: UR-8NH

  • Country of origin:Kanada

  • Product Type: Multilin UR Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 500g

  • Dimensions: 8.2cm x 12.2cm x 6cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

The GE Multilin UR-8NH Standard 8CT with enhanced diagnostics is a modular component designed for the Universal Relay (UR) platform, specialized for transformer, transmission line, and substation protection management. This specific hardware assembly couples the 8N current transformer (CT) input module with the H high-voltage universal power supply module within a heavy-duty automation chassis. The 8N module offers 8 independent current transformer inputs engineered with enhanced diagnostics to continuously verify internal digital signal processor paths and safeguard external CT circuit connectivity against undetected open-circuit faults. Operating as a core analog measurement and power management unit, the GE Multilin UR-8NH Standard 8CT with enhanced diagnostics interfaces seamlessly with updated protective processing cores to deliver real-time telemetry, oscillography, and high-speed protection routing across industrial electrical systems.

Features

  • Continuous Input Verification: Integrated enhanced diagnostics within the 8N module continuously monitor internal hardware health and analog-to-digital signal path status.
  • High-Density CT Monitoring: Provides 8 separate current transformer inputs optimized for comprehensive three-phase and neutral current telemetry.
  • Universal Power Architecture: Equipped with the H power supply module designed to tolerate a wide input range across both AC and DC auxiliary power networks.
  • Blue-Label Alignment Warning: Features blue color-coded physical labeling to guarantee correct hardware compatibility with corresponding high-performance CPU architectures.
  • Advanced Transient Recording: Facilitates data routing for high-capacity event recording and non-volatile oscillography storage.

Applications

  • Utility and primary substation transformer protection.
  • Transmission line and feeder management distribution networks.
  • Industrial power distribution automated switchgear configurations.
  • Substation automation schemes interfacing via high-speed communication networks.

Ordering Information

Suffix Code Description
8N Standard 8CT with enhanced diagnostics 
H 125 / 250 V AC/DC power supply 

Technical Specifications

Parameter Specification
Manufacturer GE Multilin 
Country of Origin Canada / USA 
Module System Type Universal Relay (UR) Series Platform 
CT Configuration Suffix 8N (Standard 8CT with enhanced diagnostics) 
Power Supply Suffix H (125 / 250 V AC/DC power supply) 
Current Metering Accuracy ±0.25% of reading or ±0.1% of rated at 0.1 to 2.0 x CT rating 
Diagnostic Triggers Hardware watchdog, DSP mismatch check, circuit fault states 
Event Recorder Capacity Up to 1024 events time-tagged to 1 microsecond accuracy 
Oscillography Records Maximum 64 records stored in non-volatile memory 
Operating Temperature -40 degC to +60 degC
Storage Temperature -40 degC to +85 degC
Relative Humidity 5% to 95% non-condensing

Installation Guidelines

Panel Mounting

Mount the chassis containing the modules securely inside a standard 19-inch equipment rack system or a designated panel cutout. Verify that the structural framework supports the collective weight of the populated unit and heavy-gauge rear terminal wiring harnesses.

Grounding

Establish a secure grounding path from the rear-chassis grounding stud to the main station ground busbar. Use a low-impedance copper wire with a minimum gauge of 10 AWG (or 4.0 mm square), ensuring all non-conductive coatings or paint are scraped away at the terminal junction point.

CT Terminal Connections

All secondary lines coming from external current transformers must pass through an dedicated external shorting block mechanism before connecting to the rear terminal blocks of the unit. Never clear or open-circuit an active CT secondary circuit. Use proper ring-tongue terminal lugs and copper conductors rated for 90 degC or higher.

CPU Module Alignment

The 8N module utilizes modern blue labeling characteristics. Ensure it is exclusively paired with matching blue-labeled central processing units (including variants 9E, 9G, 9H, 9J, 9K, 9L, 9M, 9N, 9P, 9R, or 9S) to prevent physical hardware mismatches or critical system faults.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

GE Multilin UR-8NH Standard 8CT With Enhanced Diagnostics

What happens if an 8N module is mistakenly paired with an older 9A, 9C, or 9D CPU module?

The new 8N CT modules with enhanced diagnostics are strictly incompatible with older CPU series. If a mismatch occurs, the relay will fail to initialize and will generate a DSP ERROR or HARDWARE MISMATCH system fault.

What is the physical indication used to verify hardware compatibility during installation?

Compatible modules feature distinctive blue-colored identification labels on their physical framing accompanied by warning stickers indicating that both the CPU and DSP module label colors must match.

Does the H suffix power supply accept both alternating and direct currents?

Yes, the H suffix power supply is a universal high-voltage module engineered to operate efficiently across standard nominal 125 V AC/DC and 250 V AC/DC power networks.

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Color pattern
Czarny
Country of origin
Kanada
Power source
Zasilany prądem zmiennym Zasilanie prądem stałym

Ostatnio oglądane produkty

Wiedza techniczna

Siłowniki elektryczne zaprojektowane do zastąpienia systemów hydraulicznych: praktyczny przewodnik po automatyce przemysłowej

Ten artykuł wyjaśnia, jak zintegrowane siłowniki elektryczne, takie jak seria e-Actuator firmy SMC, rewolucjonizują przemysłową kontrolę ruchu, zastępując tradycyjne systemy pneumatyczne i...

Operacje matematyczne z wykorzystaniem OpenPLC w zastosowaniach automatyki przemysłowej

Ten artykuł wyjaśnia, jak systemy PLC wykonują podstawowe operacje matematyczne, takie jak dodawanie, odejmowanie, mnożenie, dzielenie, modulo oraz potęgowanie w automatyce przemysłowej. Pokazuje,...

Zaawansowana logika boolowska w programowaniu PLC za pomocą FBD: praktyczne zastosowania przemysłowe wykraczające poza podstawową logikę

Artykuł wyjaśnia kilka zaawansowanych funkcji logiki boolowskiej stosowanych w programowaniu PLC, wykraczających poza podstawowe operacje AND, OR i NOT. Omawia, jak narzędzia takie jak tabele prawdy,...

Logika boolowska w programowaniu PLC: Zrozumienie bramek logicznych FBD

Logika boolowska jest podstawą każdego programu PLC. Od prostych sterowań maszyn po złożone systemy automatyki przemysłowej, bramki logiczne decydują o tym, jak sterowniki reagują na zmieniające się...

Szczegółowy przewodnik po przemysłowych zaporach sieciowych i segmentacji sieci OT

Przemysłowe zapory sieciowe odgrywają kluczową rolę w cyberbezpieczeństwie OT, chroniąc sieci PLC, DCS i SCADA poprzez segmentację, kontrolę ruchu przychodzącego/wychodzącego oraz integrację IDS/IPS...

Przewodnik po chwytakach robotycznych: od delikatnego manipulowania po ciężką automatykę

Nowoczesne chwytaki robotyczne ewoluują poza tradycyjne mechaniczne szczęki. Od systemów adhezyjnych inspirowanych gekonem i miękkich chwytaków spożywczych po narzędzia magazynowe zasilane sztuczną...