Dimensions:
3.0 cm x 17.8 cm x 29.8 cm (W x H x D)
Shipping port:
Xiamen
Warranty:
12 months
The ABB Bailey IMCIS02 is a Control I/O Slave (CIS) module designed to interface process field signals with the Infi 90 Process Management System. Occupying a single slot in a Module Mounting Unit (MMU), the IMCIS02 acts as an input/output bridge, processing field signals to be monitored and executed by master modules like the Multi-Function Processor (MFP).
The module conditions four analog inputs and three digital inputs from field equipment, while driving two analog outputs and four digital outputs to control industrial processes. Front-panel switch configurations allow customization of analog output behavior and digital input response times to handle process contact debouncing.
Features
Accepts up to 4 analog inputs and 3 digital inputs.
Provides 2 analog outputs and 4 digital outputs.
Supports selectable analog output modes (1 to 5 VDC or 4 to 20 mA).
Optically isolated digital I/O for enhanced field circuit noise isolation.
Configurable digital input response times (1.5 ms Fast / 17 ms Slow) for contact debounce filtering.
Automatic online analog input calibration utilizing integrated reference voltages.
Onboard bus fault timer for process safety and default output state enforcement upon communication loss.
Front-panel status LED indicator for operational diagnostics and bus fault tracking.
Applications
Distributed Control Systems (DCS) process monitoring and control
Analog loop field signal interface and conditioning
Discrete device field status monitoring and control
System expansion and signal integration within Infi 90 systems
Technical Specifications
Parameter
Specification
Manufacturer
ABB / Elsag Bailey
Model
IMCIS02
Module Type
Control I/O Slave Module
Logic Power Requirements
+5 VDC (±5%) @ 332 mA max
+15 VDC (-2.5%, +5%) @ 35 mA max
-15 VDC (-5%, +2.5%) @ 30 mA max
+24 VDC (±10%) @ 50 mA max
Power Dissipation
1.65 W @ +5 VDC
525 mW @ +15 VDC
450 mW @ -15 VDC
1.20 W @ +24 VDC
Analog Inputs
4 differential/single-ended (1-5 VDC, or 4-20 mA via TU/TM)
A/D Resolution
12 bits
Analog Input Accuracy
±0.10% of Full Scale Range (FSR)
Analog Outputs
2 selectable (1-5 VDC or 4-20 mA)
D/A Resolution
10 bits
Analog Output Accuracy
Voltage: ±0.15% of FSR
Current: ±0.25% of FSR
Digital Inputs
3 optically isolated (24 VDC, 125 VDC, 120 VAC)
Digital Outputs
4 open collector, optically isolated (24 VDC, 250 mA max sink)
Mounting
Occupies 1 slot in standard Infi 90 Module Mounting Unit (MMU)
Operating Temperature
0 to 70 degC
Relative Humidity
0% to 95% up to 55 degC (non-condensing)
0% to 45% up to 70 degC (non-condensing)
Altitude
Sea Level to 3 Km
Connections/Interfaces
Connector Pin
Function
P1-1, P1-2
+5 VDC Power
P1-5, P1-6
Power Common
P1-7
+15 VDC Power
P1-8
-15 VDC Power
P1-9, P1-10
Power Fail Interrupt (PFI)
P2 (1-10)
Slave Expander Bus (Data 0-7, Clock, Sync)
P3-A / P3-1
Digital Output 1 (+ / -)
P3-B / P3-2
Digital Output 2 (+ / -)
P3-C / P3-3
Digital Output 3 (+ / -)
P3-D / P3-4
Digital Output 4 (+ / -)
P3-F / P3-6
Digital Input 1 (+ / -)
P3-H / P3-7
Digital Input 2 (+ / -)
P3-J / P3-8
Digital Input 3 (+ / -)
P3-K / P3-9
+24 VDC Power
P3-L / P3-10
Analog Output 1 (+ / -)
P3-M / P3-11
Analog Output 2 (+ / -)
P3-N / P3-12
Analog Input 1 (+ / -)
P3-P / P3-13
Analog Input 2 (+ / -)
P3-R / P3-14
Analog Input 3 (+ / -)
P3-S / P3-15
Analog Input 4 (+ / -)
Installation Guidelines
ESD Handling: Use a static dissipative grounding wrist strap and anti-static field kit when handling or installing the module to prevent electrostatic damage to sensitive components.
MMU Mounting: Align the circuit board with the top and bottom plastic guide rails of the designated MMU slot and slide in until flush with the rack frame. Lock the captive retaining screws by turning them half a turn into the vertical latched position.
Expander Bus Setup: Ensure a dipshunt is correctly installed in the backplane socket between the master controller and the slave module to establish communication on the slave expander bus.
Configuration Verification: Set DIP switches S1 (Slave Address), S2 (Analog Output Default), S3 (Analog Output Mode), and jumpers J1 through J6 (Digital Input Voltages/Speed) prior to sliding the board into the MMU.
Wiring & Cabling: Route field signals using compatible termination devices (NTCS02 Termination Unit or NICS01 Termination Module) connected via standard NKTU or NKTM cables to connector P3.
Compliance and Certifications
CSA: Certified for use as process control equipment in ordinary (non-hazardous) locations.
FAQ
What is the primary function of the module?
The device acts as an interface between process field signals and the Infi 90 Process Management System, transferring analog and digital field values to and from a master controller.
How are the analog outputs configured for voltage or current mode?
The analog output operating mode is set using on-board switch S3, which allows each output to be independently configured for 1 to 5 VDC or 4 to 20 mA operation.
What happens to the outputs if communication with the master module is lost?
An onboard bus fault timer monitors communication. If a timeout occurs, digital outputs de-energize and analog outputs transition to pre-configured default values (0%, 100%, or hold last value) based on switch S2 settings.
Can the module be inserted or removed while system power is applied?
Yes, the module can be removed or installed without shutting down system power, provided proper ESD protocols and process safety precautions are followed.
A PLC and a microcontroller can both generate step-and-direction motion, but arc welding exposes major differences in EMC, I/O protection, diagnostics, maintainability, safety integration, and...
Piezo pneumatic valves offer low holding power and fine proportional control, but they are not universal solenoid replacements. This guide covers driver electronics, flow limits, contamination, fail...
Built-in sensor timers can reject chatter, stretch short pulses, and simplify local timing—but they do not replace PLC diagnostics or safety logic. Learn how to apply on-delay, off-delay, and...
Reversing a three-phase motor is more than swapping two leads. This guide covers phase sequence, VFD settings, reversing contactors, encoder feedback, load checks, lockout, and commissioning tests.
Grounding one side of a 24 VDC supply can improve fault detection and voltage reference, while floating circuits support isolation. This guide explains bonding, noise, first-fault behavior, and...
Seal-in circuits and OTL/OTU instructions can hold the same command, but they fail differently. This guide compares scan behavior, restart risk, troubleshooting, permissives, and safer PLC design...
Choosing a selection results in a full page refresh.