Allen-Bradley 1769-IF8 Compact I/O Analog Input Module
SKU 1769-IF8
In stock
No reviews
12-month warranty
Free returns within 30 days
Manufacturer:
Allen-Bradley
Product No.:
1769-IF8
Country of origin:Malaysia
Product Type:
Analog Input Module
Payment:
T/T, Western Union
Weight:
280g
Dimensions:
118 x 35 x 87 mm
Shipping port:
Xiamen
Warranty:
12 months
Description
The Allen-Bradley 1769-IF8 is an 8-channel analog current/voltage input module designed for process signal acquisition in industrial automation architectures. Operating within the CompactLogix platform, it converts analog field signals from sensors, transmitters, and transducers into digital values for control execution.
The module supports individual channel configuration across voltage ranges of +/-10V, 0…10V, and 0…5V, as well as current ranges including 0…20mA and 4…20mA. Built with an integrated communication bus and removable terminal block, it provides field-wire connection points while offering 500V AC or 710V DC optical isolation to shield control logic from field electrical transients.
As part of the Compact I/O family, the 1769-IF8 can be mounted directly on a DIN rail or panel. It integrates into local CompactLogix controller assemblies, expansion racks using standard power supplies, or distributed I/O stations linked through DeviceNet (1769-ADN) or EtherNet/IP (1769-AENTR) network adapters.
Features
Features 8 analog input channels supporting unipolar and bipolar voltage or current signal ranges.
Includes optical isolation rated at 500V AC or 710V DC for 1 minute between field circuits and system logic.
Equipped with a removable terminal block (RTB) behind a protective door for easier field wiring and module swapping.
Built with a patented movable bus connector and tongue-and-groove alignment slots for solid backplane communication.
Designed for flexible mounting options on standard DIN rail or direct panel installations.
Utilizes self-lifting field-wire pressure plates to streamline installation and maintenance workflows.
Applications
Scalable process signal monitoring in CompactLogix control architectures.
Analog data acquisition for pressure, temperature, flow, and level transmitters.
Distributed I/O expansion via EtherNet/IP (1769-AENTR) or DeviceNet (1769-ADN) communication adapters.
Local expansion I/O for MicroLogix 1500 controller assemblies.
Technical Specifications
Parameter
Specification
Manufacturer
Allen-Bradley / Rockwell Automation
Catalog Number
1769-IF8
Product Type
Analog Current/Voltage Input Module
Number of Inputs
8 channels
Input Signal Ranges
+/-10V, 0…10V, 0…5V, 1…5V, 0…20mA, 4…20mA
Current Draw @ 5.1V DC
120 mA
Current Draw @ 24V DC
70 mA
Isolation Voltage
500V AC or 710V DC for 1 min (qualifying test), 30V AC / 30V DC working voltage
Operating Temperature
0...60 degC (32...140 degF)
Nonoperating Temperature
-40...+85 degC (-40...+185 degF)
Relative Humidity
5...95% noncondensing
Operating Vibration
5 g @ 10...500 Hz
Operating Shock
30 g (Panel Mount), 20 g (DIN Rail Mount)
Nonoperating Shock
40 g (Panel Mount), 30 g (DIN Rail Mount)
Power Supply Distance Rating
8 modules
Dimensions (H x W x D)
118 x 35 x 87 mm (4.65 x 1.38 x 3.43 in.)
Dimensions with Mounting Tabs
Height 138 mm (5.43 in.)
Slot Width
1
Module Location
DIN Rail or Panel Mount
Country of Origin
Malaysia
Installation Guidelines
Confirm the catalog number (1769-IF8) and verify that power supply and bus specifications match system requirements before installation.
Ensure system power is completely disconnected before inserting or removing modules from the Compact I/O assembly.
Align the module tongue-and-groove slots with adjacent modules or the controller and slide into place until fully seated.
Secure the module to the DIN rail using the DIN rail latch, or mount directly to a panel using two mounting screws.
Move the bus connector slide switch to lock the backplane communication bus across adjacent modules.
Wire analog transmitters and sensors to the removable terminal block according to voltage or current input configurations, observing correct signal polarity and shielding practices.
Configuration and Replacement Recommendations
Parameter Backup: Upload and save the existing controller project, module configuration data, and scaling parameters prior to removing an active module.
Module Replacement: When replacing an existing module, ensure backplane power is off, loosen the terminal block retaining screws, pull the removable terminal block away, swap the module, and reconnect the terminal block.
Shielding: Use twisted-pair shielded cable for analog input signals and ground the shield at one end only to prevent ground loops and noise interference.
Distance Rating: Verify that the module is installed within its 8-module power supply distance rating relative to the system 1769 power supply.
FAQ
What input signal types does the Allen-Bradley 1769-IF8 analog module support?
The module supports both voltage and current analog field signals. Configurable range options include +/-10V, 0…10V, 0…5V, 1…5V, as well as 0…20mA and 4…20mA current loops.
What is the power supply distance rating for the 1769-IF8 module?
The module has a power supply distance rating of 8 modules. It must be installed within 8 module slots of a 1769 Compact I/O power supply.
Can the 1769-IF8 module be used in distributed I/O architectures?
Yes, the module can be installed in distributed expansion banks connected via network adapters such as the 1769-AENTR for EtherNet/IP or the 1769-ADN for DeviceNet.
How is the 1769-IF8 module mounted in a control cabinet?
The device can be installed directly on a standard 35 mm DIN rail or panel-mounted using two screws. It mechanically locks to adjacent Compact I/O modules using built-in tongue-and-groove guide slots.
A field replacement guide for GE Fanuc IC200MDL650 covering revision-dependent negative logic, four common groups, 24 VDC thresholds, input filtering, carrier checks and commissioning records.
A field-focused IC697CPX935 replacement guide covering fast memory, firmware-dependent serial behavior, rack power, cooling, I/O architecture and backup records.
A field-focused IC693DSM324 replacement guide covering Series 90-30 host checks, FSSB servo-chain records, 5 V power budget, firmware limits, follower control and commissioning.