The Allen-Bradley 1783-MS06T is a Stratix 8000 Layer 2 6-port managed Ethernet switch engineered for industrial networking applications. The 1783-MS06T switch provides secure, high-performance connectivity within plant-floor environments and industrial control networks.

Designed with an open-style enclosure, the device supports DC power inputs ranging from 18 to 60V DC (Class 2/SELV) with a maximum input rating of 2 A and maximum power dissipation of 15.7 W. It features RJ45 Ethernet connectors compliant with IEC 60603-7, supporting Category 5e minimum or Category 5 cabling. The module also provides basic isolation rated at 75V continuous between power and ground, power to network channels, and power to alarm ports.

Features

  • Layer 2 managed switch functionality with 6 Ethernet ports.
  • Operating power input rating of 2 A max at 18...60V DC, Class 2/SELV.
  • Maximum power dissipation of 15.7 W.
  • Alarm relay output rated at 1 A max at 30V DC, Class 2/SELV.
  • RJ45 Ethernet connection using Category 5e minimum (TIA 568-B.1) or Category 5 (ISO/IEC 24702) cabling.
  • Dedicated terminal connections for DC power, alarm relay, and functional ground.
  • Open-style enclosure with T4 North American and IEC temperature codes.
  • Compatible with optional Stratix expansion modules (such as 1783-MX08T, 1783-MX08F, 1783-MX04S, 1783-MX08S, 1783-MX04E, and 1783-MX04T04E).
  • Compatible with optional SFP modules (1783-SFP100FX, 1783-SFP1GSX, 1783-SFP100LX, 1783-SFP1GLX) and memory cards (1783-RMCF, 1783-MCF).

Applications

  • Industrial EtherNet/IP control networks.
  • Plant-floor automation and distributed control systems.
  • Harsh industrial environments requiring wide operating temperature ranges.

Technical Specifications

Category Specification
Manufacturer Allen-Bradley / Rockwell Automation
Model 1783-MS06T
Switch Type Stratix 8000 Managed Switch, Layer 2 (6 ports)
Switch Input Rating 2 A max @ 18...60V DC, Class 2/SELV
Inrush Current 2.0 A max
Power Dissipation 15.7 W
Alarm Relay Rating 1 A max @ 30V DC, Class 2/SELV
Isolation Voltage 75V (continuous), basic insulation type (power to ground, power to network channels, power to alarm); Type tested at 1000V AC for 60 s
Ethernet Connections RJ45 connector per IEC 60603-7; 2- or 4-pair Cat 5e minimum (TIA 568-B.1) or Cat 5 (ISO/IEC 24702)
DC Power & Alarm Wiring 0.5...0.8 mm² (20...18 AWG) solid or stranded copper wire rated at 90 degC or greater, 1.2 mm insulation max
Functional Ground Wiring 3.3...5.3 mm² (12...10 AWG) solid or stranded copper wire rated at 75 degC or greater
Terminal Torque 0.23 N-m (2.0 lb-in) on power and alarm connectors
Wiring Category 2-on alarm ports, 2-on power ports, 2-on Ethernet ports
Enclosure Type Rating None (open-style)
North American Temp Code T4
IEC Temp Code T4
Operating Temperature -40...60 degC (-40...140 degF)
Max Surrounding Air Temp 60 degC (140 degF)
Nonoperating Temperature -40...85 degC (-40...185 degF)
Relative Humidity 5...95% noncondensing
Vibration 2 g @ 10...500 Hz (IEC 60068-2-6)
Operating Shock 20 g (IEC 60068-2-27)
Nonoperating Shock 30 g (IEC 60068-2-27)
Emissions CISPR11 (IEC 61000-6-4) Class A
ESD Immunity 8 kV contact discharges, 15 kV air discharges (IEC 61000-4-2)
Radiated RF Immunity 20V/m (80...1000 MHz), 10V/m (900 MHz, 1890 MHz, 1000...2700 MHz) (IEC 61000-4-3)
EFT/B Immunity ±4 kV @ 2.5 kHz and ±2 kV @ 5 kHz on power, alarm, and Ethernet ports (IEC 61000-4-4)
Surge Transient Immunity ±1 kV DM / ±2 kV CM on power & alarm ports; ±2 kV CM on Ethernet ports (IEC 61000-4-5)
Conducted RF Immunity 10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz (IEC 61000-4-6)
Magnetic Field Immunity 30 A/m long duration, 300 A/m short duration at 50/60 Hz (IEC 61000-4-8)
Oscillatory Surge Withstand 2.5 kV (IEEE C37.90.1)
Voltage Variation 10 ms interruption on DC supply ports (IEC 61000-4-29)
Dimensions 14.8 cm x 15.3 cm x 11.75 cm (H x W x D)

Installation Guidelines

  • Maintain unrestricted airflow around the switch by adhering to the minimum clearance distances: top and bottom 105 mm (4.13 in.), left and right 90 mm (3.54 in.), and front 65 mm (2.56 in.).
  • Connect functional ground using 3.3...5.3 mm² (12...10 AWG) copper wire rated for at least 75 degC.
  • Connect DC power supply and alarm wiring using 0.5...0.8 mm² (20...18 AWG) copper wire rated for at least 90 degC.
  • Tighten power and alarm connector screws to a torque specification of 0.23 N-m (2.0 lb-in).
  • For panel-mounting, ensure tab hole center-to-center spacing on the base unit is 6.83 cm (2.69 in.).

Compliance and Certifications

  • c-UL-us: UL Listed Industrial Control Equipment (File E65584); UL Listed for Class I, Division 2 Group A, B, C, D Hazardous Locations (File E194810).
  • CE: European Union EMC Directive (2004/108/EC) compliant with EN 61326-1, EN 61000-6-2, EN 61000-6-4, EN 61131-2; RoHS Directive (2011/65/EU) compliant with EN 50581.
  • C-Tick: Australian Radiocommunications Act compliant with AS/NZS CISPR 11.
  • Ex (ATEX): European Union ATEX Directive (94/9/EC) compliant with EN 60079-15, EN 60079-0 (II 3 G Ex nA nC IIC T4 Gc).
  • KC: Korean Certification of Broadcasting and Communications Equipment.
  • EtherNet/IP: ODVA conformance tested to EtherNet/IP specifications.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Allen-Bradley 1783-MS06T Stratix 8000 6 Port Managed Switch

What is the Allen-Bradley 1783-MS06T used for?

The Allen-Bradley 1783-MS06T is a Stratix 8000 Layer 2 6-port managed Ethernet switch used to provide managed network connectivity in industrial automation environments.

What is the power input requirement for the switch?

The switch requires a DC input rating of 2 A max at 18 to 60V DC (Class 2/SELV).

What is the operating temperature range for the switch?

The operating temperature range for the device is -40 to 60 degC (-40 to 140 degF).

What hazardous location certifications does the 1783-MS06T carry?

The switch is c-UL-us Listed for Class I, Division 2, Groups A, B, C, D Hazardous Locations and ATEX certified (Ex II 3 G Ex nA nC IIC T4 Gc).

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

What Is a VFD? Variable Frequency Drives That Actually Move the Needle

A VFD turns fixed-frequency mains into controlled voltage and frequency so AC motors match real load—cutting pump and fan energy while tightening torque, soft-start, and braking behavior.

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.

What It Really Takes to Learn Industrial Automation in 2026

Learning industrial automation now means mastering PLCs, networks, and protection systems—not just robots. This guide maps skills, pitfalls, and career paths for engineers entering control-heavy...

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...